Plan Review Notes
Plan Review Notes For Permit 06110410
Permit Number 06110410
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-28 10:24:48 
  
 1} PROVIDE A LOAD CALCULATION PER220 SECTION I OR
 220.31, INCLUDE EXISTING AND ADDED LOADS. THIS
 CALCULATION MUST BE DONE TO REVIEW COMPLIANCE OF THE
 ENTIRE SERVICE LOAD. INDICATE SERVICE RATING.
  
 2} PLEASE PROVIDE A RISER DIAGRAM PER 215.5. THE RISER
 SHOWN DOES NOT INDICATE DISCONNECTING MEANS OR
 OVERCURRECT PROTECTION FOR THE FEEDERS.
  
 3} PLEASE PROVIDE A SITE PLAN AND INDICATE THE AREA OF
 WORK APPLIED FOR 106.3.5.4 FBC AS AMMENDED.
  
 4} THE APPLIANCE LOCATED IN THE CLOSET IS DESIGNATED
 "EWC" ON THE PLAN AND LISTED AS A HEATER ON THE PANEL
 SCHEDULE, PLEASE CORRELATE.
  
 5} INDICATE THE LOCATION OF THE DISCONNECTING MEANS FOR
 THE WATER HEATER, SEE 422.31(B).
  
 6}A RECEPTACLE NEEDS TO BE ADDED IN THE BEDROOM FOR
 210.52 SPACING REQUIREMENTS, SEE REVIEWED SET FOR
 APPROXIMATE LOCATION.
  
 7}SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]