| 2006-11-30 17:00:49 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH | | | INSPECTION. | | | | | | | | | 1} PROVIDE MANUFACTURERS SPECIFICATIONS AND | | | RECOMMENDATION, REGARDING CLEARANCES FOR THE | | | GENERATOR. | | | | | | 2} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH. | | | | | | 3}PROVIDE A PANEL SCHEDULE FOR THE | | | EMERGENCY/GENERATOR PANEL. | | | | | | 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3 | | | FBC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|