| Plan Review Notes For Permit 06110392 |
| Permit Number |
06110392 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-30 15:25:58 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} PLEASE PROVIDE A FLOOR PLAN LOCATING THE EQUIPMENT | | | TO BE ADDED, AND EXISTIONG EQUIPMENT AT THE SAME | | | LOCATION SO THAT A REVIEW CAN BE MADE TO DETERMINE | | | COMPLIANCE WITH 110.26INDICATE FIRE RATED WALLS, | | | FLOORS OR OTHER ITEMS PENETRATED BY THE CONDUITS. | | | | | | 2} PROVIDE A LOAD CALCULATION FOR THE EXISTING 400 AMP | | | PANEL THAT FEEDS THE NEW EQUIPMENT. INDICATE EXISTING | | | LOADS AND THE ADDED TRANSFORMER LOAD. 215.5 NEC. | | | | | | 3} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED. | | | | | | 4} PLEASE PROVIDE A PANEL SCHEDULE AND DESIGNATION FOR | | | THE 200 AMP PANEL BEING ADDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | |
|