Plan Review Notes
Plan Review Notes For Permit 06110378
Permit Number 06110378
Review Stop G
Sequence Number 1
Notes
Date Text
2006-12-12 14:26:30DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 THE DRAWINGS. THE PERMIT APPLICATION INDICATES NATURAL
 GAS BUT THE SUBMITTED DRAWINGS INDICATE A 1ST AND 2ND
 STAGE REGULATOR WHICH ARE USED FOR LP GAS SYSTEMS.
 PLEASE CORRELATE THIS ON THE RESUBMITTAL.
  
 2. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) ON THE
 DRAWINGS
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 3. PLEASE SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT (MP REGULATORS IF DELIVERY PRESSURE IS 2LB)
 TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 4. PLEASE SUBMIT MANUFACTURE INSTALLATION INSTRUCTIONS
 FOR THE GENERATOR TO VERIFY MANUFACTURER'S
 RECOMMENDATIONS FOR SETBACK FROM STRUCTURES.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved