Plan Review Notes
Plan Review Notes For Permit 06110355
Permit Number 06110355
Review Stop B
Sequence Number 1
Notes
Date Text
2006-12-12 15:54:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT#06110355
 ADDRESS: 1400 CENTREPARK 1ST FLOOR LOBBY
 CONT: PASS INTERNATIONAL
 TELL NUMBER 954)421-9000
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 FBC*= 2004 FLORIDA BUILDING CODE WITH 2006 REVISIONS
  
 BUILDING PROVISOS:
  
 803.1 GENERAL.
 INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH ASTM E 84.
 SUCH INTERIOR FINISH MATERIALS SHALL BE GROUPED IN THE
 FOLLOWING CLASSES IN ACCORDANCE
 WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED INDEX.
 CLASS A:
 FLAME SPREAD INDEX 0-25; SMOKE-DEVELOPED INDEX 0-450.
 CLASS B:
 FLAME SPREAD INDEX 26-75; SMOKE-DEVELOPED INDEX 0-450.
  
 CLASS C:
 FLAME SPREAD INDEX 76-200; SMOKE-DEVELOPED INDEX 0-450.
  
  
  
 803.4.4 MATERIALS.
 AN INTERIOR WALL OR CEILING FINISH THAT IS NOT MORE
 THAN 0.25 INCH (6.4 MM) THICK SHALL BE
 APPLIED DIRECTLY AGAINST A NONCOMBUSTIBLE BACKING.
 EXCEPTIONS:
 1.CLASS A MATERIALS.
 2.MATERIALS WHERE THE QUALIFYING TESTS WERE MADE
 WITH THE MATERIAL SUSPENDED OR
 FURRED OUT FROM THE NONCOMBUSTIBLE BACKING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  