| Date |
Text |
| 2007-01-08 13:01:10 | *****DENIED***** |
| | |
| | |
| | 1. IN ADDITION TO NFPA 101 (2003 EDITION), THE FLORIDA |
| | FIRE PREVENTION CODE (2004 EDITION) SHALL ALSO BE |
| | REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER ACCESS TO OR EGRESS FROM OTHER |
| | TENANT SPACES ON THE NINTH FLOOR. |
| | |
| | 4.EXITS ARE TO REMAIN CLEAR AND SHALL BE MAINTAINED. |
| | |
| | 5.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. |
| | |
| | 6.FIRE PROTECTION SYSTEMS SHALL BE MAINTAINED |
| | OPERATIONAL AT ALL TIMES DURING ALTERATION.ANY |
| | MODIFICATIONS TO THE FIRE PROTECTIVE SYSTEMS DUE TO THE |
| | SCOPE OF WORK WILL REQUIRE SEPARATE PLANS AND PERMIT. |
| | |
| | 7.PROVIDE A LIFE SAFETY PLAN SHEET INDICATING THE |
| | TRAVEL DISTANCE TO REACH AN EXIT.THE LOCATION OF EXIT |
| | LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS MAY ALSO |
| | BE INCLUDED. |
| | |
| | 8.PROVIDE INTERIOR FINISH CLASSIFICATION FOR THE |
| | STRUCTURE.BE ADVISED THAT INTERIOR WALL AND CEILING |
| | FINISH MATERIALS IN EXITS AND IN EXIT ACCESS CORRIDORS |
| | SHALL BE CLASS "A" OR CLASS "B";SHALL BE CLASS A, |
| | CLASS B, OR CLASS C IN ALL OTHER AREAS. |
| | |
| | 9.SINCE TWO UNITS ARE BEING COMBINED TO FORM A SINGLE |
| | UNIT, THE APPROPIATE SUITE NUMBER SHALL BE IN THE TITLE |
| | BLOCK OF THE SUBMITTED PLAN SHEETS. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |