Plan Review Notes
Plan Review Notes For Permit 06110350
Permit Number 06110350
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-08 13:01:10*****DENIED*****
  
  
 1. IN ADDITION TO NFPA 101 (2003 EDITION), THE FLORIDA
 FIRE PREVENTION CODE (2004 EDITION) SHALL ALSO BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER ACCESS TO OR EGRESS FROM OTHER
 TENANT SPACES ON THE NINTH FLOOR.
  
 4.EXITS ARE TO REMAIN CLEAR AND SHALL BE MAINTAINED.
  
 5.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 6.FIRE PROTECTION SYSTEMS SHALL BE MAINTAINED
 OPERATIONAL AT ALL TIMES DURING ALTERATION.ANY
 MODIFICATIONS TO THE FIRE PROTECTIVE SYSTEMS DUE TO THE
 SCOPE OF WORK WILL REQUIRE SEPARATE PLANS AND PERMIT.
  
 7.PROVIDE A LIFE SAFETY PLAN SHEET INDICATING THE
 TRAVEL DISTANCE TO REACH AN EXIT.THE LOCATION OF EXIT
 LIGHTS, EMERGENCY LIGHTS, FIRE EXTINGUISHERS MAY ALSO
 BE INCLUDED.
  
 8.PROVIDE INTERIOR FINISH CLASSIFICATION FOR THE
 STRUCTURE.BE ADVISED THAT INTERIOR WALL AND CEILING
 FINISH MATERIALS IN EXITS AND IN EXIT ACCESS CORRIDORS
 SHALL BE CLASS "A" OR CLASS "B";SHALL BE CLASS A,
 CLASS B, OR CLASS C IN ALL OTHER AREAS.
  
 9.SINCE TWO UNITS ARE BEING COMBINED TO FORM A SINGLE
 UNIT, THE APPROPIATE SUITE NUMBER SHALL BE IN THE TITLE
 BLOCK OF THE SUBMITTED PLAN SHEETS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722