| Date |
Text |
| 2008-10-08 08:04:58 | REVISIONS DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT P2.31 A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED. |
| | PLEASE USE THE SIGNATURE REQUIRED. FS 471.025. |
| | |
| | 2. SHT P2.31 SHOWS A HOSE BIBB IN THE METER ROOM. NO |
| | FLOOR DRAIN IS INDICATED. PLEASE SHOW COMPLIANCE WITH |
| | SECTION 301.2 WHICH STATES THAT PLUMBING SHALL BE |
| | INSTALLED WITH DUE REGARD TO PRESERVATION OF THE |
| | STRENGTH OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE |
| | TO WALLS AND OTHER SURFACES THROUGH FIXTURE USEAGE. |
| | |
| | 3. SHT P2.31 SHOWS THE 3" VTR BEING CHANGED TO AN AIR |
| | ADMITTANCE VALVE. SECTION 903.1 REQUIRES AT LEAST ONE |
| | VENT STACK THE SIZE OF WHICH IS NOT LESS THAN 1/2 OF |
| | THE REQUIRED SIZE OF THE BUILDING DRAIN TO RUN |
| | UNDIMINISHED IN SIZE AND DIRECTLY AS POSSIBLE FROM THE |
| | BUILDING DRAIN THROUGH TO THE OPEN AIR OR TO A VENT |
| | HEADER THAT EXTENDS TO THE OPEN AIR. PLEASE INDICATE |
| | HOW THIS WILL BE COMPLIED WITH. |
| | |
| | 4. SHT P2.31 INDICATES A REVISION #10 ON THE FLOOR |
| | PLAN. REVISION #10 IS NOT INDICATED ON THE REVISION |
| | INDEX IN THE TITLE BLOCK. PLEASE CORRELATE. SECTION |
| | 106.1.3. |
| | |
| | 5. SHT P3.1.1 A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED. |
| | PLEASE USE THE SIGNATURE REQUIRED. FS 471.025. |
| | |
| | 6. SHT P3.1.1 LATEST REVISION SUBMITTED IS REVISION |
| | #10. REVISION #10 WAS SUBMITTED PREVIOUSLY AND WAS |
| | SIGNED, SEALED & DATED ON 6-2-08. SHEET HAS BEEN DENIED |
| | BECAUSE NO NEW REVISION IS INDICATED. SECTION 106.1.3. |
| | |
| | 7. SHT P5.1 A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME |
| | PER FAC 61G15-23.002(1). INITIALS HAVE BEEN USED. |
| | PLEASE USE THE SIGNATURE REQUIRED. FS 471.025. |
| | |
| | 8. SHT P5.1 SHOWS A HOSE BIBB IN THE METER ROOM. NO |
| | FLOOR DRAIN IS INDICATED. PLEASE SHOW COMPLIANCE WITH |
| | SECTION 301.2 WHICH STATES THAT PLUMBING SHALL BE |
| | INSTALLED WITH DUE REGARD TO PRESERVATION OF THE |
| | STRENGTH OF STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE |
| | TO WALLS AND OTHER SURFACES THROUGH FIXTURE USEAGE. |
| | |
| | 9. SHT P5.1 SHOWS THE 3" VTR BEING CHANGED TO AN AIR |
| | ADMITTANCE VALVE. SECTION 903.1 REQUIRES AT LEAST ONE |
| | VENT STACK THE SIZE OF WHICH IS NOT LESS THAN 1/2 OF |
| | THE REQUIRED SIZE OF THE BUILDING DRAIN TO RUN |
| | UNDIMINISHED IN SIZE AND DIRECTLY AS POSSIBLE FROM THE |
| | BUILDING DRAIN THROUGH TO THE OPEN AIR OR TO A VENT |
| | HEADER THAT EXTENDS TO THE OPEN AIR. PLEASE INDICATE |
| | HOW THIS WILL BE COMPLIED WITH. |
| | |
| | 10. INFORMATIONAL. AS PREVIOUSLY REQUESTED, WHEN |
| | SUBMITTING REVISIONS, PLEASE TURN OFF ALL PREVIOUSLY |
| | CLOUDED REVISIONS ON THE FLOOR PLANS & RISERS AS WELL |
| | AS THE REVISION NUMBERS AS THIS CAUSES DELAYS IN THE |
| | PLAN REVIEW PROCESS. EACH CLOUD HAS TO BE SCRUTINIZED |
| | IN ORDER TO MAKE SURE ALL REVISIONS SUBMITTED HAVE BEEN |
| | REVIEWED. THE REVISION INDEX SHALL STILL SHOW ALL |
| | REVISION NUMBERS AND DATES. SECTION 106.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |