| | ** DENIED4TH REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE KNOW A COMPLETE REVIEW OF ENERGY |
| | CALCULATIONS CAN NOT BE DONE AT THIS TIME AS SHEETS |
| | E1.1A, AND E1.2 DOES NOT CORRELATE. |
| | PLEASE SEE FIXTURES ON E1.1A FOR PARKING LOT SHOW |
| | DOUBLE FIXTURES ON WEST SIDE HOWEVER THE FIXTURES ON |
| | WEST SIDE OF E1.2 ARE ALL SINGLE FIXTURES. |
| | PLEASE SEE E1.1A AS THE FIXTURES ON THE NORTH, EAST AND |
| | SOUTH SIDES WHICH ARE SHOWN ON E1.2 ARE MISSING? CAN |
| | NOT CONFIRM LIGHTING ON THE INPUT DATA REPORT. PLEASE |
| | SEE THE LIGHTING FOR INTERIOR LIGHTING NEEDS TO BE |
| | ADJUSTED TO MATCH WITH PLANS. |
| | PLEASE SEE THE AMOUNT OF INTERIOR 64 WATT FIXTURES IS |
| | NOT THE SAME IN THE IDR AS SHOWN ON PLANS. (MISSING |
| | SEPARATE ROOMS). |
| | ** PLEASE CLARIFY THE 150 500W FIXTURES. IS THIS AN |
| | ASSUMPTION FOR FUTURE LIGHTS? |
| | IF SO, HOW IS IT THAT NO ASSUMPTION WAS FIGURED FOR |
| | BUILDING #1 FOR FUTURE? |
| | THIS WAS NOTED ON PREVIOUS REVIEW AND RESPONSE ONLY |
| | STATES TO *SEE REVISED ENERGY CALCULATIONS*. PLEASE SEE |
| | THE SQ FT DOES NOT CORRELATE WITH ARCHITECTURAL PLANS |
| | AND PLEASE SEE THE OCCUPANCY SHALL BE STATED AS ON |
| | ARCHITECTURAL SHEETS FOR F-1. THIS IS NOT RETAIL AS |
| | SHOWN ON COVER SHEET OF ENERGY CALCULATIONS. |
| | 13-415.2, 13-415.1.B. |
| | **PLEASE PROVIDE CORRECTED SHEETS FOR COORDINATION OF |
| | SITE AND UPDATE ENERGY CALCULATIONS. |
| | **PLEASE ALSO BE SURE WHEN RE-SUBMITTING PLANS THE |
| | OWNER AGENT IS SIGNED ON CERTIFICATION SHEET. |
| | 13-101.1.1.1 |
| | ** PLEASE KNOW AS THE FIXTURES FOR SITE ARE NOT |
| | CONFIRMED, CIRCUITING, LOADS AND PANEL SCHEDULES CAN |
| | NOT BE CONFIRMED AT THIS TIME. |
| | |
| | |
| | ** AS GONE OVER IN MEETING BEFORE PLANS WERE |
| | RESUBMITTED, PLEASE BE SURE ALL LIGHTING ON PLANS IS |
| | PLACED AND FIGURED INTO THE ENERGY CALCULATIONS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |