| 2007-10-25 15:45:33 | ****DENIED***** |
| | |
| | |
| | THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW |
| | STILL NEED TO BE ADDRESSED: |
| | |
| | 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE |
| | A LAYOUT OF THE FIRE SPRINKLER SYSTEM.THE PROJECT |
| | SITE ADDRESS IN THE TITLE BLOCK OF THE SUBMITTED FIRE |
| | SPRINKLER SHEETS IS INCORRECT.PLEASE BE ADVISED THAT |
| | THE SUBMITTED SPRINKLER SHEETS WILL BE INCLUDED WITH |
| | THE MASTER PERMIT SET OF PLANS; SPRINKLER SPEC SHEETS |
| | NOT NEEDED AT THIS TIME, BUT SHALL BE REQUIRED WHEN THE |
| | SPRINKLER CONTRACTOR APPLIES FOR THE SEPARATE PLANS AND |
| | PERMIT. |
| | |
| | 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE |
| | POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, |
| | VESSELS, EQUIPMENT, ETC.COULD NOT LOCATE THIS COMMENT |
| | AS PER YOUR RESPONSE |
| | |
| | 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE |
| | DEPARTMENT CONNECTIONS.COULD NOT LOCATE THIS COMMENT |
| | AS PER YOUR RESPONSE |
| | |
| | 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK |
| | IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.COULD |
| | NOT LOCATE THIS COMMENT AS PER YOUR RESPONSE |
| | |
| | 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE |
| | CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724 |
| | FOR APPLICATIONS.COULD NOT LOCATE THIS COMMENT AS PER |
| | YOUR RESPONSE |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING WHERE ON THE PLAN |
| | EACH ITEM WAS ADDRESSED |
| | |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |