| | **** DENIED 3RD REVIEW**** |
| | |
| | ** PLEASE KNOW THIS IS THE SECOND REVIEW UNDER PERMIT |
| | APPLICATION AND THE THIRD REVIEW TOTAL. |
| | ** PLEASE SEE THERE ARE STILL SEVERAL COMMENTS FROM THE |
| | PREVIOUS TWO REVIEWS WHICH NEED TO BE ADDRESSED. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED |
| | AND GAVE ALL CODES RELEVANT TO THE MINIMUM DESIGN TO BE |
| | PLACED ON PLANS. NFPA-20 2003 IS RELEVANT TO PROJECT |
| | AND WAS NOT PLACED ON PLANS WITH OTHER RELEVANT CODES. |
| | PLEASE ADD TO SHEETS FOR ELECTRICAL AND FORWARD TO |
| | ARCHITECT OF RECORD. |
| | |
| | 2) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WITH RESPECT |
| | TO FBC CHAPTER 13. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED STILL DO |
| | NOT CORRELATE WITH PLANS. |
| | PLEASE SEE THE NUMBER OF FIXTURES DOES NOT CORRELATE. |
| | PLEASE SEE THE METHOD OF CONTROLS. |
| | PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE. |
| | *FOR EXAMPLE: SEE THE INPUT DATA REPORT WHICH HAS |
| | 500WATT FIXTURES FOR INTERIOR FIXTURES, YET THE FIXTURE |
| | LEGEND DOES NOT INDICATE ANY FIXTURES WITH THIS SAME |
| | WATTAGE, IN FACT THE THERE ARE SEVERAL OTHER WATTAGES |
| | NONE OF WHICH ARE ON THE INPUT DATA REPORT. |
| | PLEASE SEE TYPE OF BUILDING NEEDS TO BE VERIFIED AS |
| | THIS IS NOT RETAIL. |
| | PLEASE SEE THE EXTERIOR LIGHTING DOES NOT CORRELATE |
| | WITH PLANS AS THE INPUT DATA REPORT CONTAINS NO |
| | FIXTURES FOR EXTERIOR LIGHTING. HOW IS THIS POSSIBLE |
| | WHEN THE PLANS CONTAIN DOZENS OF FIXTURES??? PLEASE BE |
| | SURE THE ADDRESS IS LISTED ON CALCULATIONS. PLEASE SEE |
| | 13-415.1.B, 13-415.2 |
| | |
| | 3) NOTE: PLEASE SEE METHOD OF CONTROLS FOR LIGHTING IS |
| | STILL NOT COMPLETE PER 13-415.1.ABC.1.1, .1.2. PLEASE |
| | OVER RIDE SWITCH LOCATIONS ARE NOT SHOWN ON PLANS AS |
| | REQUIRED FOR THE OCCUPANT ENTERING A SPACE AND BEING |
| | ABLE TO SEE THE LIGHTING IN WHICH IS BEING OVER |
| | RIDDEN. |
| | PLEASE SEE THERE ARE STILL STANDARD DEVICES SHOWN ON |
| | PLANS. |
| | PLEASE SEE NO TIME SCHEDULING, AND NO MAXIMUM TIMES ON |
| | OVER RIDES ARE SHOWN. |
| | NO ZONES, NO LAYOUTS ETC |
| | PLEASE SEE THE PREVIOUS TWO REVIEW NOTES BELOW: |
| | |
| | (REVIEW #2) |
| | **PREVIOUS REVIEW NOTES** |
| | PLEASE SEE FBC 2004 CHAPTER 13. THIS IS THE SAME |
| | COMMENT AS PREVIOUS REVIEW. PLEASE SEE THE VERSION AS |
| | SUBMITTED DOES NOT COMPLY WITH THE NEW CODE AS OF |
| | DECEMBER 8TH, 2006. |
| | PLEASE SEE AS THIS IS MENTIONED AS A SHELL BUILDING, |
| | PLEASE SEE METHOD. |
| | PLEASE SEE METHOD OF CONTROL STILL MENTIONS MANUAL |
| | ON/OFF WHICH IS NOT POSSIBLE WHEN AUTOMATED MEANS IS |
| | REQUIRED. |
| | PLEASE SEE MISSING OVER RIDE CONTROLS AT THE POINT OF |
| | ENTRANCE BY WAY OF CHOSEN DEVICES SO THE OCCUPANT CAN |
| | SEE THE LIGHTING WHICH IS BEING CONTROLLED. IF OS TYPE |
| | DEVICES ARE GOING TO BE INSTALLED FOR COVERAGE, PLEASE |
| | SHOW LOCATIONS, TYPE OF DEVICES AND MAXIMUM TIMES ON |
| | OVER RIDES |
| | PLEASE SEE SEPARATE SPACES WHICH ONLY INDICATE STANDARD |
| | SWITCHES. |
| | PLEASE SEE INTERIOR LIGHTING WHICH DOES NOT SHOW ANY |
| | AUTOMATED CONTROLS. |
| | PLEASE SEE ZONING NOT SHOWN FOR LARGER SPACES. PLEASE |
| | SEE ENERGY CALCULATIONS DO NOT INCLUDE ANY EXTERIOR |
| | LIGHTING AS PLANS DO. |
| | PLEASE BE SURE OWNER AGENT SIGNS ALL THREE COPIES. |
| | PLEASE SEE THE ADDRESS SHALL BE SPECIFIC ON |
| | CALCULATIONS. |
| | PLEASE SEE PREVIOUS REVIEW NOTES BELOW. |
| | PLEASE SEE FBC CHAPTER 13. |
| | |
| | (REVIEW #1) |
| | ** PREVIOUS NOTES** |
| | PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL" |
| | FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE |
| | ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR |
| | EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| | 13-415.1.AB.1, 13-415.2.ABC.1. |
| | PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN |
| | CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED |
| | AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES. |
| | PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING |
| | HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL |
| | BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE |
| | DOES NOT REQUIRE ONE DESIGN OVER ANOTHER. |
| | PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE |
| | SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT |
| | "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS |
| | CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS |
| | IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE |
| | ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE |
| | SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING |
| | CONTROL PANEL. (700.12E). |
| | |
| | |
| | 4) NOTE: PLEASE SEE THE LIGHTING LEVELS STILL DO NOT |
| | COMPLY WITH THE MINIMUM LEVELS AS REQUIRED FOR |
| | EXIT/EXIT DISCHARGE PER NFPA-101 7.8.1.3AND 7.9.2.2. |
| | PLEASE SEE PHOTO-METRICS INDICATE FOR NORMAL OR |
| | EMERGENCY FOR STAIRS LEADING TO THE PUBLIC RIGHT OF WAY |
| | HOWEVER THE LEVELS UNDER NORMAL ARE NOT MEETING THE |
| | MINIMUM OF 10FT CANDLES ON SEVERAL STAIRS. PLEASE ALSO |
| | SEE THE DESIGNATION OF STAIR #5 NORMAL AND EMERGENCY IS |
| | MISSING. |
| | |
| | 5) NOTE: AS REQUESTED ON THE TWO PREVIOUS REVIEWS, |
| | PLEASE COMPLETE ALL INFORMATION ON PLANS FOR FIRE PUMP, |
| | FIRE PUMP CONTROLLER ETC. |
| | . |
| | THE RESPONSE LETTER MENTIONS THIS WILL BE *DONE BY THE |
| | FIRE SPRINKLER CONTRACTOR* |
| | SOME CUT SHEETS WERE SUBMITTED HOWEVER NOT ALL. |
| | AS STATED CLEARLY ON THE TWO PREVIOUS REVIEWS THIS |
| | INFORMATION IS REQUIRED FOR *MINIMUM* CODE COMPLIANCE |
| | FOR THE BASE BUILDING AND ALL INFORMATION SHALL BE |
| | SUBMITTED UNDER THE BASE BUILDING PERMIT APPLICATION. |
| | THIS IS IRRELEVANT OF THE SEPARATE PERMIT REQUIRED FOR |
| | FIRE SPRINKLER AT A LATER DATE. |
| | PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS. PLEASE |
| | COMPLETE INFORMATION ON PLANS. |
| | NEC 695, NFPA-20 CHAPTER 6, 7 ETC |
| | CODES SECTIONS GIVEN BELOW FROM PREVIOUS REVIEWS REMAIN |
| | THE SAME. |
| | |
| | **PREVIOUS REVIEW #2 NOTE: |
| | AS NOTED ON PREVIOUS REVIEW. PLEASE COMPLETE ALL |
| | INFORMATION ON PLANS AND PLEASE SUBMIT ALL SPECS/CUT |
| | SHEETS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THE |
| | FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS REQUIRED |
| | UNDER THE BASE BUILDING PLANS FOR REVIEW OF CODE |
| | COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND |
| | FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE |
| | SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE |
| | NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS |
| | FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL |
| | BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC |
| | SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED. |
| | PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10 |
| | OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC. |
| | PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY |
| | CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE |
| | INFORMATION WAS NOT SUBMITTED. |
| | PLEASE SEE 110.3, AND 90.7. |
| | PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA |
| | 5 |
| | |
| | 6) NOTE:THIS NOTE FROM PREVIOUS REVIEW WILL REMAIN AS |
| | INFORMATION ON FIRE PUMP IS NOT COMPLETE AND |
| | VERIFICATION OF RISER CONDUCTORS ETC CAN NOT BE |
| | REVIEWED UNTIL ALL INFORMATION IS ON PLANS AND |
| | SUBMITTED. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED ABOVE FOR |
| | FEEDERS ETC. |
| | 240.4, 310.16, 695, NFPA-20 CHAPTER 9 |
| | |
| | 7 NOTE:PLEASE SEE ACTUAL CALCULATIONS FOR LIGHT POLES |
| | WILL BE REVIEWED BY STRUCTURAL REVIEWER. |
| | ** NOTED FOR INFORMATION. |
| | |
| | 8) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. AS THIS |
| | IS ONLY THE SECOND REVIEW UNDER PERMIT APPLICATION AS |
| | THE INITIAL REVIEW WAS UNDER *PLAN REVIEW*. |
| | PLEASE ADDRESS ALL COMMENTS. |
| | |
| | 9) NOTE: PLEASE SEE ALL LANDSCAPE PLANS AS SUBMITTED |
| | ARE NOT SIGNED DATED OR SEALED BY THE RESPONSIBLE |
| | DESIGNER(S) OF RECORD. |
| | SEE ONLY SHEET 1 OF 6 WAS SIGNED, AND SEALED. |
| | FS 481.221 |
| | |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| | AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| | PLANS. |
| | |
| | ** IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-10-15 07:47:17 | 2007-10-15 07:47:17 |
| | |
| | IN REVIEW |
| 2007-10-14 16:02:30 | 2007-10-14 16:02:30 |
| | REVIEW WILL CONTINUE ON 10/15, NOTES WILL FOLLOW ONCE |
| | COMPLETED. |
| | REVIEW WILL BE GOING INTO A *F* STATUS. |