| 2007-07-11 12:07:10 | ****DENIED***** |
| | |
| | |
| | THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW |
| | STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION SHALL COMPLY WITH NFPA241. |
| | |
| | 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF. |
| | |
| | 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE |
| | A LAYOUT OF THE FIRE SPRINKLER SYSTEM. |
| | |
| | 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE |
| | POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, |
| | VESSELS, EQUIPMENT, ETC. |
| | |
| | 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE |
| | DEPARTMENT CONNECTIONS. |
| | |
| | 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK |
| | IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY. |
| | |
| | 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE |
| | CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724 |
| | FOR APPLICATIONS. |
| | |
| | 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| | 80. |
| | |
| | 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND |
| | EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B". |
| | |
| | 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC. |
| | |
| | 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED |
| | FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
| | |
| | 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED. |
| | |
| | 19.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY |
| | ADDRESSABLE. |
| | |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING WHERE ON THE PLAN |
| | EACH ITEM WAS ADDRESSED |
| | |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |