| 2007-06-10 10:32:03 | **** UNSAT 2ND REVIEW**** |
| | |
| | ** PLANS NOW SUBMITTED FOR PERMIT. THIS IS THE FIRST |
| | REVIEW UNDER PERMIT. |
| | PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW |
| | UNDER *PLAN REVIEW* WHICH STILL NEED TO BE ADDRESSED |
| | ALONG WITH SOME NEW COMMENTS. |
| | ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED IN |
| | DESIGN OR INFORMATION PROVIDED FOR CODE COMPLIANCE |
| | REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT YET BE MADE. |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS SUBMITTED CONTAIN STAMPS |
| | FROM ANOTHER BUILDING DEPARTMENT AND MUNICIPALITY WHICH |
| | IS NOT PERMITTED. PLEASE KNOW ALL NEW SHEETS WILL BE |
| | REQUIRED TO BE SUBMITTED. |
| | PLEASE SEE SOME SHEETS EVEN CONTAIN SIGN OFFS FROM THAT |
| | SAME JURISDICTION ALTHOUGH PLANS INDICATE WORK IN THE |
| | CITY OF WEST PALM BEACH? |
| | |
| | 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW AS STATED |
| | REQUESTS FOR ALL OLD/VOIDED SHEETS TO BE COMPLETELY |
| | REMOVED FROM SETS AND ONLY TO INSERT NEW REVISED SHEETS |
| | INTO THE COMPLETED SETS FOR REVIEW AND STAMPING. PLEASE |
| | SEE SETS STILL CONTAIN OLD SHEETS, PLEASE REMOVE. |
| | PLEASE SEE COMMENT ABOVE FOR NEW SHEETS NEEDED. |
| | |
| | 3) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS FOR |
| | *INITIALS* BEING USED IN LIEU OF ARCHITECT SIGNATURE. |
| | PLEASE SEE FS 481.221. |
| | A LETTER FOR SIGNATURE VERIFICATION WILL BE REQUIRED. |
| | THIS IS ONLY BEING NOTED BY THIS REVIEWER AT THIS TIME |
| | FOR INFORMATIONAL PURPOSE. OTHER SHEETS ARE SIGNED. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS NOTES FOR CODE TO BE |
| | STATED ON PLANS. PLEASE SEE MOST WERE DONE, HOWEVER |
| | PLEASE SEE THE FOLLOWING. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2003 NFPA-20 |
| | |
| | 5) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. THIS IS THE |
| | SAME COMMENT AS PREVIOUS REVIEW. PLEASE SEE THE VERSION |
| | AS SUBMITTED DOES NOT COMPLY WITH THE NEW CODE AS OF |
| | DECEMBER 8TH, 2006. |
| | PLEASE SEE AS THIS IS MENTIONED AS A SHELL BUILDING, |
| | PLEASE SEE METHOD. |
| | PLEASE SEE METHOD OF CONTROL STILL MENTIONS MANUAL |
| | ON/OFF WHICH IS NOT POSSIBLE WHEN AUTOMATED MEANS IS |
| | REQUIRED. |
| | PLEASE SEE MISSING OVER RIDE CONTROLS AT THE POINT OF |
| | ENTRANCE BY WAY OF CHOSEN DEVICES SO THE OCCUPANT CAN |
| | SEE THE LIGHTING WHICH IS BEING CONTROLLED. IF OS TYPE |
| | DEVICES ARE GOING TO BE INSTALLED FOR COVERAGE, PLEASE |
| | SHOW LOCATIONS, TYPE OF DEVICES AND MAXIMUM TIMES ON |
| | OVER RIDES |
| | PLEASE SEE SEPARATE SPACES WHICH ONLY INDICATE STANDARD |
| | SWITCHES. |
| | PLEASE SEE INTERIOR LIGHTING WHICH DOES NOT SHOW ANY |
| | AUTOMATED CONTROLS. |
| | PLEASE SEE ZONING NOT SHOWN FOR LARGER SPACES. PLEASE |
| | SEE ENERGY CALCULATIONS DO NOT INCLUDE ANY EXTERIOR |
| | LIGHTING AS PLANS DO. |
| | PLEASE BE SURE OWNER AGENT SIGNS ALL THREE COPIES. |
| | PLEASE SEE THE ADDRESS SHALL BE SPECIFIC ON |
| | CALCULATIONS. |
| | PLEASE SEE PREVIOUS REVIEW NOTES BELOW. |
| | PLEASE SEE FBC CHAPTER 13. |
| | ** PREVIOUS NOTES** |
| | PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL" |
| | FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE |
| | ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR |
| | EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| | 13-415.1.AB.1, 13-415.2.ABC.1. |
| | PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN |
| | CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED |
| | AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES. |
| | PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING |
| | HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL |
| | BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE |
| | DOES NOT REQUIRE ONE DESIGN OVER ANOTHER. |
| | PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE |
| | SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT |
| | "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS |
| | CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS |
| | IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE |
| | ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE |
| | SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING |
| | CONTROL PANEL. (700.12E). |
| | |
| | |
| | 6) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9. PLEASE SEE NO |
| | PHOTO-METRICS INDICATE FOR NORMAL OR EMERGENCY FOR |
| | STAIRS LEADING TO THE PUBLIC RIGHT OF WAY. |
| | PLEASE SEE PHOTO-METRICS SHOULD INDICATE LEVELS UNDER |
| | NORMAL/EMERGENCY ON FLAT EGRESS PATHS (SAME FOR BOTH |
| | CONDITIONS). |
| | ** NOTES FROM PREVIOUS REVIEW** |
| | PLEASE SEE THAT MINIMUM BATTERY BACK UP LIGHTS OF SOME |
| | KIND WILL BE REQUIRED FOR EGRESS AREAS WHICH INCLUDE |
| | EXTERIOR STAIRS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE |
| | MINIMUM FOOT CANDLES UNDER NORMAL POWER AND MINIMUM |
| | FOOT CANDLES REQUIRED UNDER EMERGENCY POWER. 7.8.1.3, |
| | 7.9.2.2. PLEASE KNOW THESE LIGHTING LEVELS SHOWN ON |
| | PHOTO-METRICS WILL BE REQUIRED ON ELECTRICAL PLANS FOR |
| | REVIEW WHETHER OR NOT THESE COMMENTS ARE MADE BY FIRE |
| | REVIEW. |
| | |
| | 7) NOTE:AS NOTED ON PREVIOUS REVIEW, NOT ALL REQUIRED |
| | SIGNAGE OR NOTES IS ON PLANS. |
| | ** PREVIOUS REVIEW NOTES** PLEASE SEE 230.2E WHICH |
| | SPEAKS OF SIGNAGE REQUIRED FOR ALL SERVICE FEEDING ONE |
| | BUILDING. PLEASE SEE THAT RISER ONLY INDICATES 2-MAINS |
| | FOR THIS BUILDING, WHEN IN FACT THE MAIN FOR THE FIRE |
| | PUMP SHOULD ALSO BE NOTED AND LABELED. PLEASE ALSO |
| | PLACE NOTES ON RISER FOR SIGNAGE WHICH WILL BE REQUIRED |
| | FOR ALL MAINS AND SERVICE LOCATIONS. PLEASE SEE AS THE |
| | JOCKEY PUMP IS BEING FED FROM THE NORMAL HOUSE PANEL, |
| | THIS SHALL ALSO BE LABELED ACCORDINGLY. 695.4(B)3 |
| | |
| | 8) NOTE:AS NOTED ON PREVIOUS REVIEW. NO INFORMATION |
| | WAS SUBMITTED OR CHANGED ON PLANS. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THE |
| | FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS REQUIRED |
| | UNDER THE BASE BUILDING PLANS FOR REVIEW OF CODE |
| | COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND |
| | FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE |
| | SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE |
| | NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS |
| | FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL |
| | BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC |
| | SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED. |
| | PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10 |
| | OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC. |
| | PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY |
| | CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE |
| | INFORMATION WAS NOT SUBMITTED. |
| | PLEASE SEE 110.3, AND 90.7. |
| | PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA |
| | 5 |
| | |
| | 9) NOTE:THIS NOTE FROM PREVIOUS REVIEW WILL REMAIN AS |
| | INFORMATION ON FIRE PUMP IS NOT COMPLETE AND |
| | VERIFICATION OF RISER CONDUCTORS ETC CAN NOT BE |
| | REVIEWED. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED ABOVE FOR |
| | FEEDERS ETC. |
| | 240.4, 310.16, 695, NFPA-20 CHAPTER 9 |
| | |
| | 10) NOTE:SAME NOTE AS PREVIOUS REVIEW. NO INFORMATION |
| | SUBMITTED. AS THE POLES ON SITE ARE ALREADY BEING |
| | INSTALLED FOR OTHER BUILDINGS THIS INFORMATION SHOULD |
| | BE READILY AVAILABLE. |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SUBMIT OR INDICATE REQUIREMENTS FOR WIND LOAD |
| | CALCULATIONS FOR BUILDING REVIEW FOR FBC 2004 140MPH. |
| | |
| | 11) NOTE: PLEASE CLARIFY WHY LEVELS FOR STROBES ON |
| | SCHEDULE ARE STILL BEING SHOWN AT 15CD? |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC 2004 CHAPTER 11, MORE SPECIFICALLY |
| | 11-4.28, .1.2, AND .3(4). PLEASE ALSO SEE NFPA-72 |
| | 2002. |
| | THIS MAY OR MAY NOT CHANGE ACTUAL SHOWN UNITS. AS FOR |
| | MINIMUM CANDELA LEVELS SEE ABOVE AS NOTED. |
| | |
| | |
| | 12) NOTE: PLEASE SEE THE RESPONSE LETTER AS SUBMITTED |
| | DOES NOT RESPOND TO ALL COMMENTS AS REVIEWED FROM |
| | PREVIOUS REVIEW. |
| | PLEASE SEE FIRE REVIEW AND BUILDING REVIEW COMMENTS |
| | WITH RESPECT TO THE FIRE SPRINKLERS AS THE BASE |
| | BUILDING PLANS ARE REQUIRED TO SHOW COMPLIANCE AND |
| | STATUTORY REQUIREMENTS AS WELL AS THE FBC. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT ELECTRICAL PLANS OR DESIGN. |