| Plan Review Notes For Permit 06110349 |
| Permit Number |
06110349 |
|
| Review Stop |
B |
| Sequence Number |
14 |
|
| Notes |
| Date |
Text |
| 2008-07-31 13:38:02 | BUILDING PLAN REVIEW | | | PERMIT: 06110349 | | | ADD: 5720 PREMIER PARK DR. BLDG# 3 | | | CONT:GLOBAL CONSTRUCTION ASSOCIATES | | | LLC | | | TEL: (954)444-8463 | | | DATE:7-31-08 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006 | | | REVISIONS | | | * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE | | | | | | REVIEW- DENIED | | | SUBMITTALS: J.B.GARAGE DOORS | | | IN THE ORIGINAL SUBMITTALS FOR SECTIONAL DOORS THE | | | DESIGNER OF RECORD ALSO SUBMITTED DESIGN CRITERIA FOR | | | DOOR BUCK ATTACHMENTS. SINCE THIS IS A SEPERATE NOAAND | | | DOOR SIZE IS CONSIDERABLY LARGEER THAN THE 100 SQ FT | | | ORIGINALLY SUBMITTED THERE ARE TWO QUESTIONS THAT | | | ARISE: | | | 1) ARE DOOR BUCKS TO BE INSTALLED AGAIN, IF SO PLEASE | | | PROVIDE THE ENGINEERING FOR THE DOOR BUCKS, SEE SHEET 2 | | | OF 4 AND BUCK ATTACHMENTCOMMENTS AS WELL AS SHEET 1 OF | | | 4 COMMENT# 4 ANCHORING OR LOADING CONDITIONS OTHER THAN | | | THOSE SHOWN IN THESE DETAILS ARE NOT PART OF THIS | | | APPROVAL. | | | 2) IF BUCKS ARE NOT TO BE USED, THEN CIRCLE THE | | | CONDITIONS TO BE USED FOR THIS INSTALATION.AND ON SHEET | | | 4 OF 4 CIRCLE HEIGHT OF DOOR TO BE INSTALLED. | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 06110347 | | | ADD: 5655 PREMIER PARK DR. BLDG# 1 | | | CONT:GLOBAL CONSTRUCTION ASSOCIATES | | | LLC | | | TEL: (954)444-8463 | | | DATE:4-28-08 | | | | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE WITH 2006 | | | REVISIONS | | | * WEST PALM BEACH AMENDMENTS ADMINISTRATIVE CODE | | | | | | REVIEW- DENIED | | | SUBMITTALS: |
|