| Date |
Text |
| 2007-01-30 16:01:47 | ****DENIED***** |
| | |
| | |
| | 01.THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK IS |
| | CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH PLAN |
| | SHEET. |
| | |
| | 02.NFPA 101 - 2003 EDITION AND FLORIDA FIRE |
| | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION SHALL COMPLY WITH NFPA241. |
| | |
| | 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF. |
| | |
| | 05.SHOW THE LOCATION OF FIRE HYDRANT(S) WITHIN |
| | 300-500 FEET OF THE BUILDING. |
| | |
| | 06.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING |
| | ON THE PROPER ELEVATION VISIBLE FROM PREMIER PARK |
| | DRIVE.AS PER WEST PALM BEACH CODE, THOSE NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH. |
| | SUITE/UNIT/TENANT SPACE NUMBERS SHALL BE NO LESS THAN |
| | 3" IN HEIGHT AND 1" IN WIDTH. |
| | |
| | 07.IF A MONUMENT SIGN OR MARKEE IS REQUIRED, A |
| | NUMERICAL ADDRESS WILL ALSO BE POSTED.IF THERE ARE |
| | GOING TO BE SEVERAL ADDRESSED BUILDINGS WITHIN THE FED |
| | EX COMPLEX, A RANGE OF ADDRESSES FROM THE LOWEST TO THE |
| | HIGHEST WILL BE REQUIRED ON THE MONUMENT SIGN OR |
| | MARKEE. |
| | |
| | 08.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE |
| | A LAYOUT OF THE FIRE SPRINKLER SYSTEM. |
| | |
| | 09.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE |
| | POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, |
| | VESSELS, EQUIPMENT, ETC. |
| | |
| | 10.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE |
| | DEPARTMENT CONNECTIONS. |
| | |
| | 11.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK |
| | IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY. |
| | |
| | 12.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. PLEASE |
| | CONTACT THE FIRE PREVENTION BUREAU AT (561) 804-4724 |
| | FOR APPLICATIONS. |
| | |
| | 13.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| | 80. |
| | |
| | 14.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND |
| | EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B". |
| | |
| | 15.PROVIDE A LIFE SAFETY PLAN SHOWING THE TRAVEL |
| | DISTANCE TO AN EXIT MEASURED ON THE FLOOR OR OTHER |
| | WALKING SURFACE AS PER NFPA 1017.6.1* |
| | |
| | 16.FIRE EXTINGUISHERS ARE TO BE RATED 2A-10BC. |
| | |
| | 17.SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED |
| | FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS. |
| | |
| | 18.FIRE SPRINKLER SYSTEM IS TO BE MONITORED. |
| | |
| | 19.FIRE ALARM SYSTEM IS TO BE CLASS A OR FULLY |
| | ADDRESSABLE. |
| | |
| | 20.ON SHEET FA0.3, FIRE ALARM NOTE 17, DELETE WORDING |
| | " SUPERVISORY SIGNAL ONLY" AND INSERT WORDING "A |
| | GENERAL FIRE ALARM". |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED |
| | |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |