| 2006-12-04 13:03:12 | **** UNSAT **** |
| | |
| | PERMIT # 06110349 |
| | BUILDING # 3 |
| | PLEASE KNOW THAT THE ADDRESS SHALL BE PLACE ON THE |
| | PLANS TITLE BLOCK AS IT HAS NOW BEEN DESIGNATED TO THIS |
| | BUILDING LOCATION. |
| | |
| | 1) NOTE: PLEASE KNOW THAT THE PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW" ONLY AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT AT THIS TIME. PLEASE KNOW AS OF |
| | DECEMBER 8TH 2006 THE STATE OF FLORIDA WILL ADOPT THE |
| | NEW 2005 NATIONAL ELECTRICAL CODE NFPA-70. PLEASE ALSO |
| | KNOW THAT THE NEW 2006 REVISIONS TO THE 2004 FBC WILL |
| | ALSO GO INTO AFFECT. |
| | PLEASE KNOW THAT AS PERMITS HAVE NOT BEEN APPLIED FOR |
| | AT THIS TIME ALL NEW CODES AFTER THIS DATE WILL BE |
| | REQUIRED TO BE MET. |
| | |
| | 2) NOTE: PLEASE BE SURE ALL THE FOLLOWING RELEVANT |
| | CODES ARE REFLECTED ON PLANS. |
| | 2002 NFPA-70 ONLY IF A PERMIT IS APPLIED FOR BY THE 8TH |
| | OF DEC. PLEASE REFLECT THE 2005 NFPA-70, 2002 NFPA-72, |
| | 2003 NFPA-101, 2003 NFPA-20 AND THE 2004 FBC. |
| | |
| | 3) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. |
| | PLEASE SEE ENERGY CALCULATIONS WHICH INDICATE "MANUAL" |
| | FOR THE MEANS OF CONTROL FOR LIGHTING. PLEASE SEE |
| | ENERGY CALCULATIONS WHICH MENTIONS "NONE ENTERED" FOR |
| | EXTERIOR LIGHTING, HOWEVER PLANS DO INDICATE THIS. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| | 13-415.1.AB.1, 13-415.2.ABC.1. |
| | PLEASE SEE SOME OF THE INTERIOR LIGHTS ARE BEING SHOWN |
| | CIRCUITED THROUGH THE LIGHTING CONTROL PANELS AND NOTED |
| | AS EXTERIOR LIGHTS WHEN THESE ARE INTERIOR FIXTURES. |
| | PLEASE SEE ALL AREAS WHICH CONTAIN FLOOR TO CEILING |
| | HEIGHT PARTITIONS SHALL ALSO CONTAIN LIGHTING CONTROL |
| | BY ONE OF THE MEANS AS STATED IN THE CODE. THIS OFFICE |
| | DOES NOT REQUIRE ONE DESIGN OVER ANOTHER. |
| | PLEASE SEE MORE THAN OPTION IS AVAILABLE. PLEASE BE |
| | SURE TO CORRELATE CIRCUITING AS AN EXAMPLE OF CIRCUIT |
| | "3HP-5". ON THE LIGHTING CONTROL PANEL IS SHOWS THIS |
| | CIRCUIT AS FEEDING EXTERIOR LIGHTS, YET ON PLANS THIS |
| | IS THE CIRCUIT WHICH FEEDS THE INTERIOR LIGHTS. PLEASE |
| | ALSO SEE THAT ALL EMERGENCY AND EXIT LIGHTS SHALL BE |
| | SHOWN IN DETAIL WIRED ON THE LINE SIDE OF ANY LIGHTING |
| | CONTROL PANEL. (700.12E). |
| | |
| | |
| | 4) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9, WHICH MAY |
| | ALSO BE PART OF THE FIRE REVIEWER COMMENTS WITH RESPECT |
| | TO A MINIMUM OF LIGHTING REQUIRED IN SPACE UNTIL SUCH |
| | TIME FOR TENANT BUILD OUT. PLEASE SEE THAT MINIMUM |
| | BATTERY BACK UP LIGHTS OF SOME KIND WILL BE REQUIRED |
| | FOR EGRESS AREAS WHICH INCLUDE EXTERIOR STAIRS TO THE |
| | PUBLIC RIGHT OF WAY. PLEASE SEE MINIMUM FOOT CANDLES |
| | UNDER NORMAL POWER AND MINIMUM FOOT CANDLES REQUIRED |
| | UNDER EMERGENCY POWER. 7.8.1.3, 7.9.2.2. PLEASE KNOW |
| | THESE LIGHTING LEVELS SHOWN ON PHOTO-METRICS WILL BE |
| | REQUIRED ON ELECTRICAL PLANS FOR REVIEW WHETHER OR NOT |
| | THESE COMMENTS ARE MADE BY FIRE REVIEW. |
| | |
| | 5) NOTE: PLEASE SEE 230.2E WHICH SPEAKS OF SIGNAGE |
| | REQUIRED FOR ALL SERVICE FEEDING ONE BUILDING. PLEASE |
| | SEE THAT RISER ONLY INDICATES 2-MAINS FOR THIS |
| | BUILDING, WHEN IN FACT THE MAIN FOR THE FIRE PUMP |
| | SHOULD ALSO BE NOTED AND LABELED. PLEASE ALSO PLACE |
| | NOTES ON RISER FOR SIGNAGE WHICH WILL BE REQUIRED FOR |
| | ALL MAINS AND SERVICE LOCATIONS. PLEASE SEE AS THE |
| | JOCKEY PUMP IS BEING FED FROM THE NORMAL HOUSE PANEL, |
| | THIS SHALL ALSO BE LABELED ACCORDINGLY. 695.4(B)3 |
| | |
| | 6) NOTE: PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS |
| | FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.THIS IS |
| | REQUIRED UNDER THE BASE BUILDING PLANS FOR REVIEW OF |
| | CODE COMPLIANCE FOR THE BUILDINGS ELECTRICAL SYSTEM AND |
| | FEEDS TO THIS PUMP. PLEASE KNOW EVEN THOUGH THE FIRE |
| | SPRINKLER SYSTEM IS UNDER A SEPARATE PERMIT. PLEASE SEE |
| | NFPA-20 2003, PLEASE SEE 9.3, 9.3.2.2 ALL SECTIONS |
| | FOLLOWING. PLEASE SEE WHERE LOCKED ROTOR CURRENT SHALL |
| | BE MARKED, DISCONNECTING MEANS, ISOLATING SWITCHES ETC |
| | SHALL BE SHOWN WITH PLANS AND SPECS SHEETS SUBMITTED. |
| | PLEASE ALSO SEE NEC 695.4(B)(1). PLEASE SEE CHAPTER 10 |
| | OF NFPA-20 10.3.6, 10.4.2, 10.4.2.2 ETC. |
| | PLEASE KNOW THIS OFFICE IS UNABLE TO REVIEW FOR MANY |
| | CODE COMPLIANCE ITEMS AT THIS TIME AS THE ABOVE |
| | INFORMATION WAS NOT SUBMITTED. |
| | PLEASE SEE 110.3, AND 90.7. |
| | PLEASE SEE FBC ADMIN SECTION 106.1.2, 106.3.5.1.1PARA |
| | 5 |
| | |
| | 7) NOTE: PLEASE SEE NFPA-72 AS THE BREAKER WHICH FEEDS |
| | THE FIRE ALARM CONTROL PANEL (FACP) SHALL BE A BREAKER |
| | WHICH CONTAINS A "LOCK-ON" DEVICE WHICH IS AN INTEGRAL |
| | PART OF THE BREAKER. PLEASE KNOW THAT A "SNAP ON" TYPE |
| | DEVICE WILL NOT BE ACCEPTABLE TO THE AHJ. NFPA-72. |
| | 4.4.1.4.2.1THE DEDICATED BRANCH CIRCUIT(S) AND |
| | CONNECTIONS SHALL BE MECHANICALLY PROTECTED. |
| | 4.4.1.4.2.2CIRCUIT DISCONNECTING MEANS SHALL HAVE A |
| | RED MARKING, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED |
| | PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM |
| | CIRCUIT" |
| | 4.4.1.4.2.3THE LOCATION OF THE CIRCUIT DISCONNECTING |
| | MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM |
| | CONTROL UNIT. |
| | PLEASE ALSO SEE 90.7, 110.3 AND 90.4. |
| | THIS CAN BE ADDRESSED WITH IDENTIFICATION ON THE PANEL |
| | SCHEDULE AND A NOTE ON PANEL FOR TYPE OF BREAKER TO BE |
| | USED FOR THIS CIRCUIT. |
| | |
| | 8) NOTE: PLEASE COMPLETE RISER FOR FIRE PUMP AS NOTED |
| | ABOVE FOR FEEDERS ETC. |
| | 240.4, 310.16, 695, NFPA-20 CHAPTER 9 |
| | |
| | 9) NOTE: PLEASE INDICATE "FLOATING NEUTRAL" ON THE |
| | METERS ON THE SECONDARY SIDE OF THE PRIMARY MAIN. |
| | 250.6, 250.24B. |
| | |
| | 10) NOTE: PLEASE SUBMIT OR INDICATE REQUIREMENTS FOR |
| | WIND LOAD CALCULATIONS FOR BUILDING REVIEW FOR FBC 2004 |
| | 140MPH. |
| | |
| | 11) NOTE: PLEASE CLARIFY THE NOTIFICATION APPLIANCE |
| | CIRCUITS CALCULATIONS WHICH INDICATE A DATE OF |
| | 9/25/01? |
| | |
| | PLEASE SEE FBC 2004 CHAPTER 11. , MORE SPECIFICALLY |
| | 11-4.28, .1.2, AND .3(4). PLEASE ALSO SEE NFPA-72 |
| | 2002. |
| | THIS MAY OR MAY NOT CHANGE ACTUAL SHOWN UNITS. AS FOR |
| | MINIMUM CANDELA LEVELS SEE ABOVE AS NOTED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |