Plan Review Notes
Plan Review Notes For Permit 06110347
Permit Number 06110347
Review Stop E
Sequence Number 4
Notes
Date Text
2007-12-23 18:03:08** DENIED4TH REVIEW **
  
 ** PLEASE SEE COMMENT BELOW WHICH IS WAS ALSO THE SAME
 IN PREVIOUS REVIEW NOTE #2
  
 1) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WITH RESPECT
 TO FBC CHAPTER 13.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED STILL DO
 NOT CORRELATE WITH PLANS.
 PLEASE SEE THE NUMBER OF FIXTURES DOES NOT CORRELATE.
 PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE.
 *FOR EXAMPLE: SEE THE INPUT DATA REPORT FOR INTERIOR
 LIGHTING SHOWS 27 FIXTURES, YET PLANS HAVE MORE THAN
 THIS.(33 AS SHOWN ON PLANS).
 PLEASE SEE EXTERIOR WHICH ALSO DOES NOT CORRELATE AS
 IDR SHOWS 9-1000WATT FIXTURES YET 10-1000WATT FIXTURES
 ARE ON PLANS.
 PLEASE SEE SHEET E1.1B SHOWS 15-400W FIXTURES ON
 BUILDING #1 WHEN POWER SHEET SHOWS 14 FIXTURES. PLEASE
 SEE THE WALL SCONCES WHICH ARE SHOWN AS THE 70W MH ON
 PLANS AND 84WON IDR WHICH IS OK AS THIS IS MOST LIKELY
 THE OUTPUT OF BALLAST HOWEVER THE FIXTURE COUNT ON
 PLANS IS HIGHER THAN IDR.IDR SHOWS 8 AND PLANS SHOW
 10.
 PLEASE SEE PLANS SHOWS ALSO SHOWS 175W MH FIXTURE WHICH
 IS NOT EVEN SHOWN ON THE IDR FOR EXTERIOR LIGHTS. ** AS
 GONE OVER IN MEETING BEFORE PLANS WERE RESUBMITTED,
 PLEASE BE SURE ALL LIGHTING ON PLANS IS PLACED AND
 FIGURED INTO THE ENERGY CALCULATIONS. AS MENTIONED IN
 PREVIOUS REVIEW, PLEASE EXPLAIN HOW THE BUILDING
 DESIGNATION IS BEING NOTED AT *RETAIL* AND *OFFICE
 OPEN*
 BASED ON OCCUPANCY STATED ON ARCHITECTURAL SHEETS THIS
 IS DESIGNATED AS A F-1.
 PLEASE SEE SQ FT STILL DOES NOT MATCH WITH THE
 ARCHITECTURAL PLANS.
 PLEASE SEE 13-415.1.B, 13-415.2
 ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON
 CERTIFICATION SHEET BEFORE RE-SUBMITTAL.
 FBC 13-101.1.1.1
  
 ** PLEASE SEE NOTES UNDER 06110349 AND CLARIFICATION
 WITH RESPECT TO ASSUMPTIONS FOR FUTURE LIGHTING.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.