| 2007-12-23 18:03:08 | ** DENIED4TH REVIEW ** |
| | |
| | ** PLEASE SEE COMMENT BELOW WHICH IS WAS ALSO THE SAME |
| | IN PREVIOUS REVIEW NOTE #2 |
| | |
| | 1) NOTE: PLEASE SEE BOTH PREVIOUS REVIEWS WITH RESPECT |
| | TO FBC CHAPTER 13. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED STILL DO |
| | NOT CORRELATE WITH PLANS. |
| | PLEASE SEE THE NUMBER OF FIXTURES DOES NOT CORRELATE. |
| | PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE. |
| | *FOR EXAMPLE: SEE THE INPUT DATA REPORT FOR INTERIOR |
| | LIGHTING SHOWS 27 FIXTURES, YET PLANS HAVE MORE THAN |
| | THIS.(33 AS SHOWN ON PLANS). |
| | PLEASE SEE EXTERIOR WHICH ALSO DOES NOT CORRELATE AS |
| | IDR SHOWS 9-1000WATT FIXTURES YET 10-1000WATT FIXTURES |
| | ARE ON PLANS. |
| | PLEASE SEE SHEET E1.1B SHOWS 15-400W FIXTURES ON |
| | BUILDING #1 WHEN POWER SHEET SHOWS 14 FIXTURES. PLEASE |
| | SEE THE WALL SCONCES WHICH ARE SHOWN AS THE 70W MH ON |
| | PLANS AND 84WON IDR WHICH IS OK AS THIS IS MOST LIKELY |
| | THE OUTPUT OF BALLAST HOWEVER THE FIXTURE COUNT ON |
| | PLANS IS HIGHER THAN IDR.IDR SHOWS 8 AND PLANS SHOW |
| | 10. |
| | PLEASE SEE PLANS SHOWS ALSO SHOWS 175W MH FIXTURE WHICH |
| | IS NOT EVEN SHOWN ON THE IDR FOR EXTERIOR LIGHTS. ** AS |
| | GONE OVER IN MEETING BEFORE PLANS WERE RESUBMITTED, |
| | PLEASE BE SURE ALL LIGHTING ON PLANS IS PLACED AND |
| | FIGURED INTO THE ENERGY CALCULATIONS. AS MENTIONED IN |
| | PREVIOUS REVIEW, PLEASE EXPLAIN HOW THE BUILDING |
| | DESIGNATION IS BEING NOTED AT *RETAIL* AND *OFFICE |
| | OPEN* |
| | BASED ON OCCUPANCY STATED ON ARCHITECTURAL SHEETS THIS |
| | IS DESIGNATED AS A F-1. |
| | PLEASE SEE SQ FT STILL DOES NOT MATCH WITH THE |
| | ARCHITECTURAL PLANS. |
| | PLEASE SEE 13-415.1.B, 13-415.2 |
| | ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON |
| | CERTIFICATION SHEET BEFORE RE-SUBMITTAL. |
| | FBC 13-101.1.1.1 |
| | |
| | ** PLEASE SEE NOTES UNDER 06110349 AND CLARIFICATION |
| | WITH RESPECT TO ASSUMPTIONS FOR FUTURE LIGHTING. |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |