Plan Review Notes
Plan Review Notes For Permit 06110347
Permit Number 06110347
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2007-10-31 10:59:30THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 09.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE
 A LAYOUT OF THE FIRE SPRINKLER SYSTEM.THE ADDRESS ON
 THE SUBMITTED SPRINKLER PLAN SHEETS IS INCORRECT
  
 10.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE
 POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE,
 VESSELS, EQUIPMENT, ETC.NOT SHOWN ON PLAN THAT THIS
 COMMENT HAS BEEN ACKNOWLEDGED AS PER YOUR RESPONSE
 LETTER
  
 11.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.NOT SHOWN ON PLAN THAT THIS
 COMMENT HAS BEEN ACKNOWLEDGED AS PER YOUR RESPONSE
 LETTER
  
 15.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND
 EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
 ADD COMMENT TO SHEET A-17
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING WHERE ON THE PLANS
 EACH ITEM WAS ADDRESSED
  
  