| 2007-10-31 10:59:30 | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 09.SINCE THIS WILL BE A SPRINKLERED BUILDING, PROVIDE | | | A LAYOUT OF THE FIRE SPRINKLER SYSTEM.THE ADDRESS ON | | | THE SUBMITTED SPRINKLER PLAN SHEETS IS INCORRECT | | | | | | 10.FIRE DEPARTMENT CONNECTIONS (FDC'S) SHALL BE | | | POSITIONED SO THAT THEY CANNOT BE BLOCKED BY STORAGE, | | | VESSELS, EQUIPMENT, ETC.NOT SHOWN ON PLAN THAT THIS | | | COMMENT HAS BEEN ACKNOWLEDGED AS PER YOUR RESPONSE | | | LETTER | | | | | | 11.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE | | | DEPARTMENT CONNECTIONS.NOT SHOWN ON PLAN THAT THIS | | | COMMENT HAS BEEN ACKNOWLEDGED AS PER YOUR RESPONSE | | | LETTER | | | | | | 15.INTERIOR FINISH FOR WALLS AND CEILING IN EXITS AND | | | EXIT ACCESS CORRIDORS SHALL BE CLASS "A" OR CLASS "B". | | | ADD COMMENT TO SHEET A-17 | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING WHERE ON THE PLANS | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|