| 2007-10-25 14:38:58 | DATE OCTOBER 24, 2007 |
| | |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, |
| | FLORIDA33401 |
| | TEL:561-805-6713FAX: 561-805-6731 |
| | JAMES JOHNSTON,BUILDING PLAN EXAMINER II |
| | |
| | E-MAIL:JJOHNSTON @WPB.ORG |
| | |
| | PERMIT NO06110347 |
| | PROJECT BLDG. 1, PREMIER PARK |
| | ADDRESS 5655 PREMIER PARK OF COMMERCE |
| | |
| | |
| | BUILDINGPLANREVIEW FLORIDA BUILDING CODES |
| | 2004 |
| | |
| | THIS IS A PLAN REVIEW OF JIM WHITMER?S COMMENTS DATED |
| | JUNE 28, 2007. |
| | |
| | |
| | 1 |
| | FLORIDA STATUE553.80 (2)(B)ENFORCEMENT |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS' |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | COMMENT- THIS IS THE THIRD REVIEW OF THE PREVIOUS |
| | COMMENTS |
| | |
| | |
| | 2 |
| | (3) 3RD REQUESTFBCBUILDING1802.6 REPORTS. THE |
| | SOIL CLASSIFICATION AND DESIGN LOAD-BEARING CAPACITY |
| | SHALL BE SHOWN ON THE CONSTRUCTION DOCUMENT. WHERE |
| | REQUIRED BY THE BUILDING OFFICIAL, A WRITTEN REPORT OF |
| | THE INVESTIGATION SHALL BE SUBMITTED THAT INCLUDES, BUT |
| | NEED NOT BE LIMITED TO, THE FOLLOWING INFORMATION: 1. A |
| | PLOT SHOWING THE LOCATION OF TEST BORINGS AND/OR |
| | EXCAVATIONS. |
| | 2.A COMPLETE RECORD OF THE SOIL SAMPLES. |
| | 3.A RECORD OF THE SOIL PROFILE. |
| | 4.ELEVATION OF THE WATER TABLE, IF ENCOUNTERED. 5. |
| | RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN |
| | CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING |
| | CAPACITY OF NATURAL OR COMPACTED SOIL; PROVISIONS TO |
| | MITIGATE THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF |
| | THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT |
| | AND VARYING SOIL STRENGTH; AND THE EFFECTS OF ADJACENT |
| | LOADS. |
| | 6.EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT. 7. |
| | PILE AND PIER FOUNDATION INFORMATION IN ACCORDANCE WITH |
| | SECTION 1808.2.2 . |
| | 8.SPECIAL DESIGN AND CONSTRUCTION PROVISIONS FOR |
| | FOOTINGS OR FOUNDATIONS FOUNDED ON EXPANSIVE SOILS, AS |
| | NECESSARY. |
| | 9.COMPACTED FILL MATERIAL PROPERTIES AND TESTING |
| | IN ACCORDANCE WITH SECTION 1803.5 . |
| | |
| | COMMENT-THE SUBMITTED SOIL TEST REPORT IS NOT |
| | COMPLETE. THE SPECIFIC METHOD, TYPE OF EQUIPMENT, |
| | DESCRIPTION OF COMPACTION TO ACHIEVE THE STATED BEARING |
| | CAPACITY ARE NOT INCLUDED IN THIS REPORT. |
| | |
| | |
| | 3 |
| | (4A) 3RD REQUEST FBCBUILDING105.3 RESIDENT INSP. |
| | SUBMIT INSPECTOR RESUMEAND LICENSE TO HAROLD PISKURA, |
| | DIRECTOR RESIDENT INSPECTION PROGRAM. THE FOLLOWING |
| | ITEMS REQUIRE A RESIDENTINSPECTOR BUILDINGS/ADDITIONS |
| | TYPE I OR II CONSTRUCTION |
| | ANY MAJOR STRUCTURAL ALTERATIONS |
| | STRUCTURES IN WHICH THE CONCRETE DESIGN IS BASED ON |
| | COMPRESSIVE STRENGTH (F?C)IN EXCESS OF 3,000 PSI. |
| | PILE DRIVING |
| | BUILDINGS OVER 2,000 S.F. IN AREA |
| | BUILDINGS OVER 2 STORIES IN HEIGHT BUILDING/STRUCTURES |
| | OF UNUSUAL DESIGN OR METHODS OF CONSTRUCTION |
| | |
| | |
| | |
| | 4 |
| | (4B)3RD REQUEST FBCBUILDING105.3 |
| | DUE TO THE REQUIREMENT OF A RESIDENT INSPECTOR, SUBMIT |
| | 3 COPIES OF ALL DOCUMENTS FOR REVIEW |
| | |
| | |
| | 5 |
| | (5A COMPLIED |
| | |
| | |
| | 6 |
| | (5C)COMPLIED |
| | |
| | |
| | 7 |
| | (5-E) COMPLIED-UNITS LEASED |
| | |
| | |
| | 8 |
| | (5-F)COMPLIED |
| | |
| | |
| | |
| | |
| | 9 |
| | (8)3RD REQUEST FBCBUILDING |
| | PRODUCT APPROVALS REQUIRED |
| | FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3 |
| | REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS |
| | SUBMIT TWO COPIES OF EACH APPROVAL ( 3 COPIES IF A |
| | THRESHOLD BUILDING ) WITH FLORIDA PRODUCT APPROVAL |
| | COVER SHEET THE ARCHITECT?S / ENGINEER?S SIGNATURE AS |
| | APPLICABLE, STATING ?TO THE BEST OF THEIR KNOWLEDGE THE |
| | PRODUCT APPROVAL COMPLIES WITH THE PLANS AND |
| | SPECIFICATIONS.SEE:WEB SITE |
| | WWW.FLORIDABUILDING.COM |
| | NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE |
| | BY LEGACYFPA |
| | |
| | COMMENT-PRODUCT APPROVALS REQUIRED PLEASE SELECT |
| | APPLICABLE ITEMS LISTED BELOW |
| | |
| | |
| | OPERABLE WINDOWS |
| | FIXED GLASS |
| | MULLION TUBES |
| | PANEL WALLS |
| | STORE FRONT GLAZING SYSTEM |
| | ALUMINUM OUT -SWING DOORS |
| | HOLLOW METAL DOORS |
| | EXTERIOR GLAZED DOORS |
| | TRUSS ANCHORS |
| | ROOFINGCOMPONENTS |
| | SHUTTERS |
| | SKYLIGHTS |
| | EXTERIOR LOUVER DOORS |
| | EXTERIOR RAILINGS, ENGINEERING REQUIRED |
| | LOUVERS,NO REPORT SUBMITTED |
| | ROOF ASSEMBLIES, DENSE DECK, ATTACHMENTS, INSULATION, |
| | UNDERLAYMENT,ROOF TILE,ROOF SYSTEM |
| | EFIS WALL SYSTEM (IF USED) |
| | AQUA ROCK SHEATHING |
| | ROLL UP DOOR |
| | WOOD BASE STRUCTURAL PANELS |
| | |
| | |
| | |
| | 10 |
| | (11)COMPLIED |
| | |
| | |
| | |
| | |
| | 11 |
| | (14) COMPLIED |
| | |
| | |
| | |
| | 12 |
| | (15)COMPLIED |