Plan Review Notes
Plan Review Notes For Permit 06110347
Permit Number 06110347
Review Stop M
Sequence Number 2
Notes
Date Text
2007-06-15 15:00:50FOR PERMIT
 *** DENIED ***
 1) SEE PLANS PAGE A-5 ALL THE SKYLIGHTS HAVE A 7 WITH A
 CLOUD AROUND IT BUT THEIR IS NO NOTE 7 ON THAT PAGE
 PLEASE CORRECT OR EXPLAIN.
  
 2) SEE ENERGY CALCULATIONS INPUT DATA REPORT PAGE 3
 SHOWS NO SKYLIGHTS, PLANS SHOW 18 SKYLIGHTS, PLEASE
 CORRECT ENERGY CALCULATIONS.
  
 3) THE ENERGY CALCULATIONS ARE BEING DONE BY THE WRONG
 PROGRAM SEE 2004 FBC (2006 REV.) 13-400.3.B METHOD B
 FORMS.
 AN ACCURATELY COMPLETED FORM 400B-04R (GENERATED BY THE
 FLA/COM-2004 COMPUTER PROGRAM, VERSION 2.5)
 DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR METHOD
 B COMPLIANCE. CALCULATIONS SHALL BE PERFORMED FOR THE
 CLIMATE ZONE IN WHICH THE BUILDING WILL BE LOCATED AND
 ACCORDING TO THE PROCEDURES SPECIFIED FOR METHOD B IN
 THIS SUB-CHAPTER.
  
 4) SEE PLANS PAGE M2.1.1 KEY NOTES #2 AND #5. AS NOTED
 IN LAST REVIEW 1-26-07 NOTE #2 PLEASE SUBMIT PRODUCT
 APPROVAL FOR LOUVERS.
  
 5) SEE ELECTRICAL REVIEW NOTE #1 REGARDING OTHER
 BUILDING DEPT. STAMPS, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  