| Plan Review Notes For Permit 06110347 |
| Permit Number |
06110347 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-15 15:00:50 | FOR PERMIT | | | *** DENIED *** | | | 1) SEE PLANS PAGE A-5 ALL THE SKYLIGHTS HAVE A 7 WITH A | | | CLOUD AROUND IT BUT THEIR IS NO NOTE 7 ON THAT PAGE | | | PLEASE CORRECT OR EXPLAIN. | | | | | | 2) SEE ENERGY CALCULATIONS INPUT DATA REPORT PAGE 3 | | | SHOWS NO SKYLIGHTS, PLANS SHOW 18 SKYLIGHTS, PLEASE | | | CORRECT ENERGY CALCULATIONS. | | | | | | 3) THE ENERGY CALCULATIONS ARE BEING DONE BY THE WRONG | | | PROGRAM SEE 2004 FBC (2006 REV.) 13-400.3.B METHOD B | | | FORMS. | | | AN ACCURATELY COMPLETED FORM 400B-04R (GENERATED BY THE | | | FLA/COM-2004 COMPUTER PROGRAM, VERSION 2.5) | | | DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR METHOD | | | B COMPLIANCE. CALCULATIONS SHALL BE PERFORMED FOR THE | | | CLIMATE ZONE IN WHICH THE BUILDING WILL BE LOCATED AND | | | ACCORDING TO THE PROCEDURES SPECIFIED FOR METHOD B IN | | | THIS SUB-CHAPTER. | | | | | | 4) SEE PLANS PAGE M2.1.1 KEY NOTES #2 AND #5. AS NOTED | | | IN LAST REVIEW 1-26-07 NOTE #2 PLEASE SUBMIT PRODUCT | | | APPROVAL FOR LOUVERS. | | | | | | 5) SEE ELECTRICAL REVIEW NOTE #1 REGARDING OTHER | | | BUILDING DEPT. STAMPS, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|