Plan Review Notes
Plan Review Notes For Permit 06110347
Permit Number 06110347
Review Stop ENG
Sequence Number 2
Notes
Date Text
2007-06-22 13:09:53PLEASE PROVIDE THE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTING DETAILS FOR PARKING
 PER CITY CODES ETC.,, MUST MEET PER ADA,,ETC.,YOU CAN
 GET STANDARD NOTES OF CITY OFWPB IN A C.D. FROM 1000
 45TH STREET. ENG DEPT.WE SHOULD HAVE THOSE NOTES ON
 YOUR DRAWINGS.
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET THESE MINIMUM REQUIREMENTS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT AND SHOW CALCULATION FOR LENGTH OF EXFILTRATION
 TRENCH, & SAFETY FACTOR YOU USED IN CALCULATION OF
 EXFILTRATION LENGTH.
 5.PLEASE SHOW STORM WATER QUALITY CALCULATIONS, WHAT
 CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER
 ENTIRE SITE OR2.5"CRITERIA, ETC? WHAT CHANGES YOU
 MADE FROM PERMIT#06071716?
 6. PLEASE SHOW THE SITE AREA ON THE DRAWINGS, YOU ARE
 DEVELOPING FOR THIS PROJECT ? ALSO, WHAT IS TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT, LAKE AREA,
 PAVEMENT AREA BUILDING AREA ETC
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ? 8.
 POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE & CATCH
 BASINS.HEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER FDEP
 TO STOP DUST & PARTICLES.
 9. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI), YOU
 MUST APPLY AT FDEP FOR NOI.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 10.
 ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR
 SITE FOR STORM WATER DRAIN.
 11. ALL DRAWINGS MUST HAVE A P.E. SEAL & SIGNED, NO
 COPIES ARE ACCEPTABLE.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  