| Plan Review Notes For Permit 06110337 |
| Permit Number |
06110337 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-12 09:43:58 | *****PROVISO***** | | | | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | | PROPERTY OF THE VICINITY THEREOF. | | | | | | 3.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE | | | REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE | | | FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 4.DEMOLITION PLAN NOTE #7 STATES" FIRE ALARM PANEL | | | TO REMAIN " .WILL THE FIRE ALARM SYSTEM BE | | | OPERATIONAL DURING DEMOLITION OPERATIONS?IF SO, WHAT | | | MEASURE(S) WILL BE UTILIZED TO PREVENT FALSE FIRE | | | ALARMS? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|