| 2007-01-25 12:45:42 | *** UNSAT 2ND REVIEW** |
| | |
| | 1) NOTE:PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. |
| | PLANS AND SHEETS FOR EQUIPMENT, LIGHTING FEEDS ETC DO |
| | NOT CORRELATE. PLEASE SEE THERE ARE SEVERAL |
| | DIFFERENCES. |
| | PLEASE SEE ONE WHICH INDICATES ANEW SERVICE AND |
| | METER, ONE WHICH INDICATES MORE THAN ONE PANEL FEEDING |
| | LIGHTS, ETC. |
| | NO GFI PROTECTION, ETC. |
| | |
| | ** PLEASE CORRELATE ALL SHEETS, PLEASE COMPLETE PLANS |
| | FOR 2002 NEC CODE COMPLIANCE. |
| | |
| | 2) NOTE: PLEASE SEE FS 553.80(2)(B). |
| | |
| | |
| | ** PLEASE BE SURE TO KEEP ANY SHEETS WHICH CONTAIN |
| | PLUMBIING STAMPS. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |