| 2007-01-25 13:04:38 | *** UNSAT 2ND REVIEW** |
| | |
| | 1) NOTE:PLEASE SEE NOTES FROM PREVIOUS REVIEW. PLANS |
| | AND SHEETS FOR EQUIPMENT, LIGHTING FEEDS ETC DO NOT |
| | CORRELATE. PLEASE SEE THERE ARE SEVERAL DIFFERENCES. |
| | NO GFI PROTECTION, ETC. |
| | |
| | ** PLEASE CORRELATE ALL SHEETS; PLEASE COMPLETE PLANS |
| | FOR 2002 NEC, 215.5, 680, 240.4, 310.16 ETC FOR CODE |
| | COMPLIANCE. |
| | |
| | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. ONE SET OF ELEC IS |
| | BEING RETAINED SHEETS 4 AND 5. |
| | |
| | 3) NOTE:PLEASE KNOW THAT THE PLANS FOR THE ELECTRICAL |
| | DETAIL SHALL BE SPECIFIC TO THE SCOPE OF WORK ON THE |
| | JOB APPLIED FOR. PLEASE CORRELATE EQUIPMENT WITH NEW |
| | PROPOSED PANEL SCHEDULE AS SOME EQUIPMENT SHOWN IS NOT |
| | ON SCHEDULE? |
| | PLEASE SEE THE PANELS AS SHOWN ON PLANS DO NOT |
| | CORRELATE. |
| | 408.4, 310.16, |
| | FBC 106.1.2 |
| | FBC 106.3.5.1.2,106.3.5.5 ADMIN SECTION. |
| | |
| | 4) NOTE: PLEASE LIST THE FEEDER TO THE NEW VAK-PAK |
| | PANEL. |
| | 215.5, 215.3. |
| | |
| | 5) NOTE: PLEASE COMPLETE THE LOAD CALCULATIONS FOR ALL |
| | AND INDICATE THE CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 ETC. |
| | ** PLEASE BE SURE TO KEEP ANY SHEETS WHICH CONTAIN |
| | PLUMBING STAMPS. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |