| Date |
Text |
| 2006-11-21 16:08:51 | *** UNSAT*** |
| | |
| | ** PLEASE KNOW PERMIT PACKAGE CONTAIN ONE PLAN FOR |
| | COMMERCIAL POOL AND ONE FOR FOUNTAIN. LOCATED THE OTHER |
| | SET OF PLANS AND PLACED ALL SETS IN TO EACH OF THEIR |
| | RESPECTIVE PACKAGES. |
| | |
| | 1) NOTE:PLEASE KNOW THAT THE PLANS FOR THE ELECTRICAL |
| | DETAIL SHALL BE SPECIFIC TO THE SCOPE OF WORK ON THE |
| | JOB APPLIED FOR. PLEASE CORRELATE EQUIPMENT WITH NEW |
| | PROPOSED PANEL SCHEDULE AS SOME EQUIPMENT SHOWN IS NOT |
| | ON SCHEDULE? |
| | 408.4, 310.16, |
| | FBC 106.1.2 |
| | FBC 106.3.5.1.2,106.3.5.5 ADMIN SECTION. |
| | |
| | 2) NOTE: PLEASE KNOW AS THIS IS A THRESHOLD/ON-SITE |
| | INSPECTOR JOB, THREE SETS OF ALL PLANS MUST BE |
| | SUBMITTED. |
| | 109.3.6, 106.1.2 ADMIN SECTION. |
| | |
| | 3) NOTE: PLEASE KNOW THAT NO WHITE OUT OR HAND WRITTEN |
| | CHANGES MAY BE DONE TO PLANS WHICH ARE SIGNED, DATED OR |
| | SEALED BY AN ENGINEER. |
| | PLEASE ALSO SEE THAT ATTACHED SHEETS CHANGING OR |
| | MODIFYING PLANS IN ANY WAY IS ALSO NOT PERMITTED UNLESS |
| | DONE BY THE ENGINEER OF RECORD, SIGNED, DATED, SEALED |
| | ALONG WITH TITLE BLOCKS AS REQUIRED PER FAC |
| | 61G15-23.002, FS 471.025 |
| | |
| | 4) NOTE: PLEASE LIST THE FEEDER TO THE NEW VAK-PAK |
| | PANEL. |
| | 215.5, 215.3. |
| | |
| | 5) NOTE: PLEASE COMPLETE THE LOAD CALCULATIONS FOR ALL |
| | AND INDICATE THE CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 ETC. |
| | |
| | |
| | ** PLEASE KNOW AS INFORMATION NEEDED WAS NOT SUBMITTED |
| | AT THIS TIME THEIR MAY BE COMMENTS ON THE FOLLOWING |
| | REVIEW |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |