Plan Review Notes
Plan Review Notes For Permit 06110263
Permit Number 06110263
Review Stop B
Sequence Number 5
Notes
Date Text
2008-03-31 08:28:01****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE PREVIOUS LISTS REGARDING PROCESS FOR
 RESUBMITTAL.I WAS UNABLE TO LOCATE A RESPONSE LETTER.
 THIS EXPEDITES THE REVIEW PROCESS AND HELPS TO PREVENT
 AN ENTIRELY NEW REVIEW.
  
 2-5.ADDRESSED OR INFORMATIONAL.
  
 6.PLEASE SEE PREVIOUS LISTS REGARDING THE PRESTORM
 PREPARATION PLAN.USE OF REMOVABLE IMPACT PROTECTION
 ON COMMERCIAL BUILDINGS REQUIRES APPROVAL BY BUILDING
 OFFICIAL.A PLAN HAS BEEN SUBMITTED BY THE ARCHITECT,
 BUT THE AGREEMENT BETWEEN THE OWNER AND DOMINICK
 MASSERO WAS NOT PROVIDED AS REQUESTED.THE OWNER IS TO
 SIGN A COMMITMENT REGARDING IMPACT PROTECTION; THIS HAS
 BEEN REQUESTED BUT NOT PROVIDED.
  
 PLEASE NOTE THAT THE PLAN MAY BE SUBMITTED VIA EMAIL
 FOR PRELIMINARY REVIEW, SEPARATELY FROM THE PLAN REVIEW
 PROCESS.
  
 REGARDING THE PLAN SUBMITTED, PLEASE ADDRESS THE
 FOLLOWING:
  
 A.WHERE SPECIFICALLY WILL THE SHUTTERS BE STORED?
 WILL THEY BE STORED VERTICALLY OR STACKED ON THE
 GROUND?IF STORED VERTICALLY, METHOD OF SECURING THE
 SHUTTERS (TO PREVENT THEM FROM FALLING AND INJURING
 SOMEONE) WILL BE REQUIRED.IF STORED HORIZONTALLY, A
 FLOOR PLAN SHOWING THE LOCATION AND ADEQUATE FLOOR
 SPACE WILL BE REQUIRED.THE FLOOR PLAN ON A2.0 DOES
 NOT GIVE ANY DIMENSIONS FOR WHAT IS SHOWN AS THE
 HURRICANE SHUTTER STORAGE AREA.
  
 B.HOW WILL THE PANELS BE SECURED TO PREVENT THEFT?
 WHO HAS ACCESS TO THIS AREA?HOW WILL THE OWNER GET
 ACCESS TO THIS AREA, ESPECIALLY AS THIS APPEARS TO BE A
 DIFFERENT TENANT SPACE FROM THE LOCATION WHERE SOME OF
 THE PANELS WILL BE REQUIRED.
  
 C.ONLY ONE INDIVIDUAL IS SHOWN AS BEING RESPONSIBLE
 FOR THE SHUTTER INSTALLATION.WHAT WILL OWNER DO IN
 THE EVENT THAT THIS ONE INDIVIDUAL IS UNAVAILABLE
 (VACATION, ILLNESS)?
  
 PLEASE BE ADVISED THAT THIS IS ONLY A PRELIMINARY
 REVIEW.ONCE COMPLETE INFORMATION IS ESTABLISHED, THE
 PLAN IS FORWARDED TO THE BUILDING OFFICIAL FOR REVIEW
 AND APPROVAL.
  
 ALSO NOTE THAT, DUE TO FBC1003.6, IMPACT DOORS WILL BE
 REQUIRED.NOTE THAT YOU ARE PROPOSING TO BLOCK THE
 ONLY EXIT FOR THE TENANT SPACE NOTED AS 522 S DIXIE HWY
  
  
 7.SEE PREVIOUS LIST AND ATTACHED SAMPLE INSTALLATION
 SCHEDULE.THIS INFORMATION IS REQUIRED FOR HURRICANE
 SHUTTER PERMITS.IF REQUESTED, THIS CAN BE PROVIDED AS
 A SEPARATE HURRICANE SHUTTER PERMIT.
  
 8.PREVIOUS LIST INDICATED THAT THE NEW ENTRY DID NOT
 COMPLY WITH FBC11-4.13.6.A 2INCH ELEVATION CHANGE IS
 SHOWN BETWEEN THE EXISTING SIDEWALK AND FINISHED FLOOR.
 A NEW NOTE STATES THAT HEIGHT DIFFERENCE SHALL NOT
 EXCEED 1/2INCH.IT IS NOT CLEAR HOW 1/2INCH AT DOORWAY
 AND AGAIN FROM NEW SLAB TO SIDEWALK WILL EQUAL THE
 2INCH DIFFERENCE.ALSO SEE FBC11-4.5.2, ELEVATION
 DIFFERENCE IS TO BE LIMITED TO 1/4INCH.SEE
 FBC11-4.1.6, (1)(B).
  
 NEW COMMENTS:
  
 9.A2.0 DECLARES OCCUPANCY AS CLASS B, MERCANTILE.
 CLASS B IS BUSINESS, MERCANTILE IS CLASS M, 41
 OCCUPANTS.IF THIS IS M, GROUND FLOOR REQUIRES 30SF
 PER PERSON, MINIMUM OCCUPANT LOAD WOULD BE 46.PLANS
 APPEAR TO BE CODE COMPLIANT FOR OCCUPANT LOAD OF 46 BUT
 PLEASE EITHER CLARIFY OCCUPANT LOAD OF 41 AS STATED ON
 PLAN OR REVISE AND CONFIRM COMPLIANCE (NO RESPONSE
 OTHER THAN REVISION OF OCCUPANT LOAD REQUIRED).
 PLEASE NOTE THAT, HAD THE PLANS BEEN OTHERWISE CODE
 COMPLIANT, THIS ITEM WOULD NOT HAVE PREVENTED PERMIT
 ISSUANCE.
  
 10.FBC1003.6, ITEMS OTHER THAN THOSE ALLOWED IN
 CHAPTER 10 NOT PERMITTED IN THE EGRESS PATH.HURRICANE
 PANELS DO NOT COMPLY WITH THIS CODE SECTION.TO MY
 KNOWLEDGE THE ONLY PROVISION IN THE CODE FOR USE OF
 SHUTTERS IN EGRESS PATH IN EVENT OF AN EMERGENCY IS FOR
 RESIDENTIAL OCCUPANCY ONLY.SEE ALSO COMMENT 6, YOU
 ARE NOT ONLY BLOCKING THE REQUIRED EXIT BUT ALSO
 BLOCKING WHAT APPEARS TO BE THE ONLY EXIT FOR ONE OF
 THE TENANT SPACES.
  