2007-11-27 08:26:20** DENIED**
  
  
  
 1) NOTE:PLEASE PROVIDE LIGHTING POWER DENSITIES PER
 13-415.2. MAY NOT USE METHOD A FOR *WHOLE BUILDING* AS
 THIS IS NOT A WHOLE BUILDING WHICH IS BEING BROUGHT UP
 TO CODE.
 PLEASE KNOW THIS WAS CONFIRMED ON SEPT 26, 2007 WITH
 THE STATE OF FLORIDA, FLORIDA BUILDING COMMISSION.
 THE ENERGY CALCULATIONS SUBMITTED BACK WERE THE SAME
 FROM PREVIOUS REVIEW WHICH HAD COMMENTS FOR
 COORDINATION.
 PLEASE KNOW ONLY LIGHTING PERFORMANCE CALCULATIONS NEED
 BE SUBMITTED FOR ELECTRICAL. PLEASE CALL TO GO OVER
 THIS MAY BE DONE IF THERE ARE ANY QUESTIONS.
 PLANS ARE ALREADY COMING BACK FOR COMMENTS FROM OTHER
 TRADES.
  
 PLEASE KNOW, STRUCTURAL REVIEW WILL BE DONE BY BUILDING
 REVIEWER.