| Plan Review Notes For Permit 06110263 |
| Permit Number |
06110263 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-11-27 08:26:20 | ** DENIED** | | | | | | | | | | | | 1) NOTE:PLEASE PROVIDE LIGHTING POWER DENSITIES PER | | | 13-415.2. MAY NOT USE METHOD A FOR *WHOLE BUILDING* AS | | | THIS IS NOT A WHOLE BUILDING WHICH IS BEING BROUGHT UP | | | TO CODE. | | | PLEASE KNOW THIS WAS CONFIRMED ON SEPT 26, 2007 WITH | | | THE STATE OF FLORIDA, FLORIDA BUILDING COMMISSION. | | | THE ENERGY CALCULATIONS SUBMITTED BACK WERE THE SAME | | | FROM PREVIOUS REVIEW WHICH HAD COMMENTS FOR | | | COORDINATION. | | | PLEASE KNOW ONLY LIGHTING PERFORMANCE CALCULATIONS NEED | | | BE SUBMITTED FOR ELECTRICAL. PLEASE CALL TO GO OVER | | | THIS MAY BE DONE IF THERE ARE ANY QUESTIONS. | | | PLANS ARE ALREADY COMING BACK FOR COMMENTS FROM OTHER | | | TRADES. | | | | | | PLEASE KNOW, STRUCTURAL REVIEW WILL BE DONE BY BUILDING | | | REVIEWER. | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|