| 2007-11-19 16:01:34 | PERMIT: 06110263 |
| | ADD: 518 S DIXIE HWY |
| | CONT: ROOSTH CONSTRUCTION |
| | TEL: (561)221-7721 |
| | DATE: NOV 19, 2007 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 4THREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMMENT NUMBER (5) FROM THE PREVIOUS REVIEW, WPB |
| | ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT |
| | WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | THE DESIGNER OF RECORD IS TO REVIEW ALL PRODUCT |
| | APPROVALS REQUIRED BY RULE 9B-72 PLEASE PROVIDE A SHOP |
| | DRAWING STAMP. IF THE DESIGNER OF RECORD WISHES TO MAKE |
| | A COVER SHEET LISTING ALL PRODUCTS REVIEWED FOR THIS |
| | PROJECT, THEN THIS SHEET WOULD NEED TO BE SIGNED AND |
| | SEALED AND DATED. |
| | |
| | 6) COMMENT NUMBER (6) FROM THE PREVIOUS REVIEW,DEALS |
| | WITH THE HURRICANE PREPAREDNESS PLAN. THE ARCHITECT |
| | INDICATES BY LETTER HE HAS REVIEWED THE INFORMATION |
| | REQUIRED AND FOUND IT TO BE CODE COMPLIANT, BUT HE |
| | FAILED TO SIGN AND SEAL SAID LETTER. |
| | PLEASE SEE THE PLANS DO NOT INDICATE WHERE UNIT 522 S |
| | DIXIE IS OR WHERE THE SHUTTERS WILL BE STORED. |
| | WE ALSO FAIL TO SEE A NOTIRIZED LETTER OR ANY CONTRACT |
| | BETWEEN THE OWNER AND DOMINICK MASSERO FOR THE |
| | INSTALLATION OF SHUTTERS IN THE EVENT THIS COUNTY IS |
| | PLACED UNDER A HURRICANE WARNING. |
| | |
| | IF THE BUILDING IS TO BE STORM SHUTTERED RATHER THAN |
| | LARGE IMPACT WINDOWS AND DOORS, THE BUILDING OFFICIALS |
| | INTERPRETATION |
| | OF THE CODE REQUIRES A HURRICANE PREPAREDNESS PLAN WITH |
| | THE FOLLOWING:104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR |
| | WIND-BORNE DEBRIS IMPACT PROTECTION |
| | QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE |
| | OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS |
| | NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR |
| | IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR |
| | SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE |
| | HURRICANE? |
| | |
| | IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| | GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| | SECTION 104.6 OF THE FLORIDA BUILDING CODE,BUILDING, |
| | CHAPTER 1, |
| | ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| | OF WEST PALM BEACH, PROVDES THE ABILITY FOR THE |
| | BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| | ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| | OF EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| | MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE |
| | SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE |
| | SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR |
| | REVIEW BY THE CONSTRUCTION SRVICES DEPARTMENT. ANY SUCH |
| | PLAN SHALL INCLUDE, AT A MINMUM, ON SITE LOCATION OF |
| | THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| | COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| | THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE ACCOMPLISHEDWITHIN |
| | TWELVE (12) HOURS OR LESS OF THE |
| | OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| | OF A HURRICANE WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| | ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| | MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| | REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| | DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| | UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| | BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| | |
| | 7) COMMENT# 7 FROM THE PREVIOUS REVIEW,DEALS WITH A |
| | KET PLAN INDICATING THE LOCATION OF THE OPENING, AND |
| | HIGHLIGHTING THE TYPE OF SHUTTER APPLICATION USED IN |
| | THE INSTALATION, NOR HAS THE TYPE OF FASTENER HIGH |
| | LIGHTED AND SPACING REQUIREMENTS AS SPECIFIED BELOW. |
| | PLEASE TAKE THE TIME TO CREATE A SCHEDULE THAT WILL |
| | CONFORM TO THE CITYS' REQUIREMENTS. |
| | STORM SHUTTER REQUIREMENTS: 2004FL BLD CODE 2001 |
| | SECTION 104.6, 1609.1.4& 1714.5PROVIDE STORM PANEL |
| | INFORMATION WITH INSTALLATION SCHEDULE AND KEY PLAN |
| | WITH SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR ALL |
| | NON-IMPACT GLAZING. |
| | FBC 1609.1.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE.SEE ATTACHED EXAMPLE. |
| | |
| | 8)NEW COMMENT, THE NEW FRONT ENTRYS DO NOT MEET THE |
| | REQUIREMENTS FOR CLEAR FLOOR SPACE AT DOORWAYS. |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE |
| | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES |
| | SHALL BE CLEAR & LEVEL. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |