| 2007-04-25 15:24:23 | ** UNSAT3RD REVIEW** |
| | |
| | 1) NOTE: PLEASE SEE THE NUMBER OF WINDOW RECEPTACLES IS |
| | NOT COMPLIANT AT THIS TIME. PLEASE SEE THE NORTH WINDOW |
| | WHICH SCALES TO BE LONGER THAN 12FT WHICH WOULD REQUIRE |
| | ONE ADDITIONAL RECEPTACLE. |
| | PLEASE ALSO SEE THE SOUTH WINDOW WHICH DOES NOT CONTAIN |
| | ANY DEVICE. |
| | THESE COULD BE REDLINED ON PLANS ONCE THE FOLLOWING |
| | COMMENT IS ADDRESSED. |
| | |
| | 2) NOTE: PLEASE CORRELATE THE ENERGY CALCULATIONS FOR |
| | USE AND TYPE OF LIGHTING. (NOT LOW BAY MANUFACTURING). |
| | PLEASE ALSO SEE THE NUMBER OF FIXTURES SHOWN PLANS, THE |
| | WATTAGE AND THE TYPES OF FIXTURES DO NOT CORRELATE WITH |
| | THE PLANS AND FIXTURES AS SHOWN ON PLANS. |
| | PLEASE SEE THIS IS A NEW COMMENT AS THIS IS THE FIRST |
| | TIME ENERGY CALCULATIONS WERE SUBMITTED FOR REVIEW. |
| | PLEASE COORDINATE ALL FIXTURES, WATTAGES, TYPES, USE. |
| | 13-415.1.A |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |