Plan Review Notes
Plan Review Notes For Permit 06110263
Permit Number 06110263
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-25 15:24:23** UNSAT3RD REVIEW**
  
 1) NOTE: PLEASE SEE THE NUMBER OF WINDOW RECEPTACLES IS
 NOT COMPLIANT AT THIS TIME. PLEASE SEE THE NORTH WINDOW
 WHICH SCALES TO BE LONGER THAN 12FT WHICH WOULD REQUIRE
 ONE ADDITIONAL RECEPTACLE.
 PLEASE ALSO SEE THE SOUTH WINDOW WHICH DOES NOT CONTAIN
 ANY DEVICE.
 THESE COULD BE REDLINED ON PLANS ONCE THE FOLLOWING
 COMMENT IS ADDRESSED.
  
 2) NOTE: PLEASE CORRELATE THE ENERGY CALCULATIONS FOR
 USE AND TYPE OF LIGHTING. (NOT LOW BAY MANUFACTURING).
 PLEASE ALSO SEE THE NUMBER OF FIXTURES SHOWN PLANS, THE
 WATTAGE AND THE TYPES OF FIXTURES DO NOT CORRELATE WITH
 THE PLANS AND FIXTURES AS SHOWN ON PLANS.
 PLEASE SEE THIS IS A NEW COMMENT AS THIS IS THE FIRST
 TIME ENERGY CALCULATIONS WERE SUBMITTED FOR REVIEW.
 PLEASE COORDINATE ALL FIXTURES, WATTAGES, TYPES, USE.
 13-415.1.A
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  