2007-02-03 14:54:36DENIED;
 PLUMBING REVIEW COMMENTS ON 12/19/06 WERE NOT
 ADDRESSED;
 1. (SECOND REQUEST) PAGE A-1.0 SANITARY PLUMBING PIPES
 TO BE REMOVED BACK TO THE BUILDING DRAIN. NO DEAD ENDS
 PERMITTED IN THE DRAINAGE SYSTEM. FBC-2004 PLUMBING
 SECTION704.5. ADD NOTE TO DEMO PLAN "ALL PLUMBING DEMO
 WORK TO BE DONE BY A LICENSED PLUMBING CONTRACTOR
 PERMIT AND INSPECTIONS REQUIRED".
 2. (SECOND REQUEST) PAGE A-3.0 SANITARY RISER DIAGRAM.
 FUTURE SINKBRANCH DRAIN TO BE INSTALLED DOWN STREAM
 OF THE BATHROOM GROUO. SECTION 909.1.
 3. (SECOND REQUEST) PER TABLE 403.1 (6) M MINIMUM
 NUMBER OF FIXTURES REQUIRED, A DRINKING FOUNTAINIS
 REQUIRED. THE DRINKING FOUNTAIN MUST MEET THE
 REQUIREMENTS OF FBC-2004 BUILDING CHAPTER 11 SECTION
 11-4.1.3(10) HANDICAP AND FOR PEOPLE WITH BAD BACKS.
 SECTION 11-4.15.2 SPOUT HEIGHT, 11-4.15.3 SPOUT
 LOCATION, 11-4.15.4 CONTROLS, AND 11-4.15.5 CLEARANCES.
 SHOW ELEVATION ON DRAWINGS.
 4. (SECION REQUEST) PAGE A-3.0 WATER RISER DIAGRAM AIR
 CHAMBERS ARE NOT AN ENGINEER PRODUCT. REMOVE THE PLANS.
 WATER HAMMER ARRESTORS CAN BE INSTALLED AS REQUIRED PER
 SECTION 604.9 LIST MANUFACTURE AND MODEL NUMBER. WATER
 HAMMER ARRESTORS ARE TO BE INSTALL PER MANUFACTURE
 INSTALLATION INSTRUCTIONS AS CLOSE TO THE FIXTURE AS
 PERMITED NOT IN THE CEILING.
 5. (NEW COMMENTS) PLANS ARE BEING REVIEWED UNDER THE
 2004 CODE CORRECT UNDER GENERAL NOTES.
 6. (NEW COMMENT) PAGE A-3.0 BATHROOM WALL FINISH PAINT
 IS NOT A HARD SURFACE. SEE 2004 BUILDING SECTION
 12.10.2
 PLUMBING PLAN REVIEW BY;