| 2007-01-19 17:25:49 | ** UNSAT2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS BASED |
| | ON CHANGES MADE TO PLANS. |
| | PLEASE KNOW THAT THERE NEW COMMENTS BASED ON PLANS AND |
| | CHANGES MADE. |
| | |
| | ** PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY |
| | FROM PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER. THEY |
| | WILL CONTAIN A NO, OK, OR NO/OK. |
| | A) NO WILL BE FOLLOWED BY FURTHER EXPLANATION OF THE |
| | PREVIOUS COMMENT. |
| | B) OK, MAY REFERENCE TO ANY NEW NOTES, HOWEVER WILL |
| | HAVE PREVIOUS NOTE REMOVED. |
| | C) NO/OK, WILL BE FOLLOWED BY FURTHER EXPLANATION AS |
| | PART OF THE COMMENT MAY NOT HAVE BEEN ADDRESSED FULLY |
| | AND PART OF THE PREVIOUS COMMENT MAY BE OK. |
| | D) OK/N/A, AS THE PREVIOUS NOTE DOES NOT APPLY ANY |
| | FURTHER AS PLANS HAVE DELETED OR CHANGED. |
| | |
| | ** ANY NEW NOTES WILL BE AT THE BOTTOM AND IDENTIFIED |
| | AS *** NEW NOTES ***. |
| | |
| | 1) NOTE: NO/OK, PLEASE SEE SHEETS WHICH STILL INDICATE |
| | THE 2001 FBC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS REFLECT THE 2001 FBC; HOWEVER AS OF |
| | OCT 1ST, 2005 THE STATE OF FLORIDA ADOPTED THE 2004 |
| | FBC. PLEASE ADJUST AND CHANGE AS NEED. |
| | PLEASE ALSO SEE TWO SEPARATE LS CODES ARE REFERENCED ON |
| | PLANS. (2000& 2003). |
| | PLEASE SEE OTHER LOCATIONS WHERE THE PLANS REFLECT THE |
| | "LATEST ADOPTED" ETC. |
| | PLEASE BE SURE THE FOLLOWING CODES ARE REFLECTED ON |
| | PLANS AS REQUIRED. |
| | 2002 NFPA-70 (NEC), 2003 NFPA-101 (LS), 2004 FBC, AND |
| | ANY OTHER CODES FROM OTHER TRADES. SEE COMMENTS FROM |
| | OTHER REVIEWERS. |
| | |
| | 2) NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | 3) NOTE: OK/NO, PLEASE SEE THE OUTLET AND THE CIRCUIT |
| | WAS ADDED, HOWEVER PLEASE SEE THE LOCATION SHOULD BE |
| | SHOWN INSIDE OR OUTSIDE THE NEAREST POINT OF ENTRANCE. |
| | PLEASE SEE THAT PLANS ONLY NEED TO RELOCATE THIS OVER. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE A NEW OR EXISTING SIGN CIRCUIT(S) PEER |
| | 600.5 THIS SPACE AND THE SPACE NEXT DOOR AS SCOPE OF |
| | WORK ON ARCHITECTURAL PLANS INDICATE WORK BEING DONE ON |
| | THE STOREFRONT NEXT DOOR. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE:NO, PLEASE SEE SOME ADDED, HOWEVER NOT ALL AS |
| | REQUIRED. PLEASE SEE INDIVIDUAL SPACES AND WINDOWS |
| | WHICH EXCEED 12 LINEAR FT WILL BE REQUIRED TO CONTAIN |
| | ADDITIONAL RECEPTS. |
| | PLEASE ALSO SEE THE SECTION OF CODE GIVEN FOR LOAD |
| | CALCULATIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING SHOW WINDOW RECEPTS AS REQUIRED PER |
| | 210.62 AND PLEASE ADJUST LOAD CALCULATIONS AS REQUIRED. |
| | 220.12 |
| | |
| | 6) NOTE: OK. NO OTHER TENANT SPACE WILL BE FED FROM |
| | THIS METER/SERVICE. |
| | PLEASE SEE SERVICE NOTE AS THE SERVICE IS NOT CLEAR FOR |
| | FUTURE TENANT. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE:OK/NO, PLEASE SEE THE FUTURE TENANT SPACE(S) |
| | WHICH WILL A PART OF THIS BUILDING WILL NOT BE GRANTED |
| | AN ADDITIONAL SERVICE PER 230.2. THE RISER DOES NOT |
| | INDICATE ANY PROVISIONS FOR THIS POSSIBLE FUTURE TENANT |
| | AND THE NEW RISER WHICH IS BEING PROPOSED WOULD HAVE TO |
| | BE UPGRADED TO ACCOMMODATE THIS IN THE FUTURE. THE |
| | 2-STORY BUILDING TO THE NORTH OF THE SINGLE STORY |
| | BUILDING WITH THE MULTIPLE METERED SERVICES MAY NOT |
| | FEED THIS FUTURE TENANT. BASED ON THE CONSTRUCTION AT |
| | THE SITE AND THE AERIALS, THIS TWO STRUCTURES APPEAR TO |
| | CONTAIN A FIRE WALL WHICH PENETRATES THE ROOF LINE AND |
| | SEPARATES THESE TWO AS BUILDINGS AS DEFINED IN THE |
| | FBC. |
| | |
| | PLEASE KNOW BASED ON THE SERVICE AS SHOWN THIS WILL |
| | ONLY BE ONE TENANT AND UNLESS UPGRADING THE NEW |
| | PROPOSED SERVICE IN THE FUTURE, NO OTHER SEPARATE |
| | TENANTS WILL OCCUPY FUTURE SPACE OR THE SPACE NOT BEING |
| | BUILT OUT AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE SERVICE AS SHOWN ON PLANS AND THAT OF |
| | WHICH IS BEING SHOWN ON RISER. IF SERVICE IS GOING TO |
| | BE NEW AS SHOWN ON RISER, PLEASE SHOW. PLEASE VERIFY |
| | WHERE THE REST OF THE SERVICE IS FOR FEEDING THE |
| | BUILDING. PLEASE SEE 230.2, 230.72 FOR SERVICES |
| | PERMITTED, AND GROUPING. |
| | PLEASE SEE PLANS INDICATE 200A'S EXISTING AND RISER |
| | SHOWS 150A. |
| | PLEASE INDICATE THE SIZE OF THE SERVICE ENTRANCE |
| | CONDUCTORS IN THE EXISTING RISER. CAN NOT VERIFY THE |
| | SEC'S AT THIS TIME. (NONE SHOWN) |
| | 215.5, 310.16, 240.4 ETC |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: NO, PLEASE SEE RESPONSE LETTER DOES NOTE |
| | RESPOND TO THIS COMMENT, IT SEEMS TO REPLY TO #11. ? |
| | PLEASE SEE THE SECTIONS GIVEN AS THE LOAD |
| | SUMMARY/CALCULATIONS ARE STILL NEEDED FOR REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT THE LOAD CALCULATIONS BASED ON THE NEC |
| | 220.3, 220.10, 220.11, 220.13 AND CONTINUOUS LOADS AT |
| | 125% 215.3, 230.42 ETC. |
| | |
| | 11) NOTE: NO, THIS WAS IN RESPONSE LETTER AS COMMENT |
| | #10; HOWEVER PLEASE SEE THE ONLY AIC RATING WHICH COULD |
| | BE LOCATED ON E-2.0 WAS THE RATING FOR THE BRANCH |
| | BREAKERS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT. PLANS INDICATE THE RATINGS FOR THE BRANCH |
| | BREAKERS ONLY ON THE PANEL SCHEDULE. |
| | PLEASE SEE 110.9, 240.12 |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 12) NOTE: OK. |
| | |
| | |
| | *** NEW NOTES *** |
| | |
| | 13) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. 106.1.2, |
| | 106.3.5.1.2 |
| | NEC 408.4, 310.16, 240.4 |
| | |
| | 14) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS FOR SPACE |
| | PER CHAPTER 13 OF TEH FBC 2004. 13-415.1.AB.1 |
| | THIS WAS NOT REQUESTED ON THE PREVIOUS REVIEW, HOWEVER |
| | DUE TO NEW STORE FRONT, OCCUPANCY, SPACE NOT CURRENTLY |
| | OCCUPIED , REMOVAL OF WALLS, NEW CEILING, NE INSULATION |
| | ETC, CALCULATIONS FOR LIGHTING ETC WILL BE NEEDED. |
| | PLEASE SEE MECHANICAL COMMENTS AS THE PLANS INDICATE |
| | NEW SPACE BEING INTRODUCED FOR CONDITIONING FROM AN |
| | EXISTING A/C SYSTEM. |
| | PLEASE SEE NOTE ON ARCHITECTURAL SHEETS WHICH MENTIONS |
| | NEW A/C WORK. PLEASE CLARIFY. |
| | |
| | 15) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |