Plan Review Notes
Plan Review Notes For Permit 06110263
Permit Number 06110263
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-19 17:25:49** UNSAT2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS BASED
 ON CHANGES MADE TO PLANS.
 PLEASE KNOW THAT THERE NEW COMMENTS BASED ON PLANS AND
 CHANGES MADE.
  
 ** PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY
 FROM PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER. THEY
 WILL CONTAIN A NO, OK, OR NO/OK.
 A) NO WILL BE FOLLOWED BY FURTHER EXPLANATION OF THE
 PREVIOUS COMMENT.
 B) OK, MAY REFERENCE TO ANY NEW NOTES, HOWEVER WILL
 HAVE PREVIOUS NOTE REMOVED.
 C) NO/OK, WILL BE FOLLOWED BY FURTHER EXPLANATION AS
 PART OF THE COMMENT MAY NOT HAVE BEEN ADDRESSED FULLY
 AND PART OF THE PREVIOUS COMMENT MAY BE OK.
 D) OK/N/A, AS THE PREVIOUS NOTE DOES NOT APPLY ANY
 FURTHER AS PLANS HAVE DELETED OR CHANGED.
  
 ** ANY NEW NOTES WILL BE AT THE BOTTOM AND IDENTIFIED
 AS *** NEW NOTES ***.
  
 1) NOTE: NO/OK, PLEASE SEE SHEETS WHICH STILL INDICATE
 THE 2001 FBC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS REFLECT THE 2001 FBC; HOWEVER AS OF
 OCT 1ST, 2005 THE STATE OF FLORIDA ADOPTED THE 2004
 FBC. PLEASE ADJUST AND CHANGE AS NEED.
 PLEASE ALSO SEE TWO SEPARATE LS CODES ARE REFERENCED ON
 PLANS. (2000& 2003).
 PLEASE SEE OTHER LOCATIONS WHERE THE PLANS REFLECT THE
 "LATEST ADOPTED" ETC.
 PLEASE BE SURE THE FOLLOWING CODES ARE REFLECTED ON
 PLANS AS REQUIRED.
 2002 NFPA-70 (NEC), 2003 NFPA-101 (LS), 2004 FBC, AND
 ANY OTHER CODES FROM OTHER TRADES. SEE COMMENTS FROM
 OTHER REVIEWERS.
  
 2) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 3) NOTE: OK/NO, PLEASE SEE THE OUTLET AND THE CIRCUIT
 WAS ADDED, HOWEVER PLEASE SEE THE LOCATION SHOULD BE
 SHOWN INSIDE OR OUTSIDE THE NEAREST POINT OF ENTRANCE.
 PLEASE SEE THAT PLANS ONLY NEED TO RELOCATE THIS OVER.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE A NEW OR EXISTING SIGN CIRCUIT(S) PEER
 600.5 THIS SPACE AND THE SPACE NEXT DOOR AS SCOPE OF
 WORK ON ARCHITECTURAL PLANS INDICATE WORK BEING DONE ON
 THE STOREFRONT NEXT DOOR.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: OK.
  
 5) NOTE:NO, PLEASE SEE SOME ADDED, HOWEVER NOT ALL AS
 REQUIRED. PLEASE SEE INDIVIDUAL SPACES AND WINDOWS
 WHICH EXCEED 12 LINEAR FT WILL BE REQUIRED TO CONTAIN
 ADDITIONAL RECEPTS.
 PLEASE ALSO SEE THE SECTION OF CODE GIVEN FOR LOAD
 CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SHOW WINDOW RECEPTS AS REQUIRED PER
 210.62 AND PLEASE ADJUST LOAD CALCULATIONS AS REQUIRED.
 220.12
  
 6) NOTE: OK. NO OTHER TENANT SPACE WILL BE FED FROM
 THIS METER/SERVICE.
 PLEASE SEE SERVICE NOTE AS THE SERVICE IS NOT CLEAR FOR
 FUTURE TENANT.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE:OK/NO, PLEASE SEE THE FUTURE TENANT SPACE(S)
 WHICH WILL A PART OF THIS BUILDING WILL NOT BE GRANTED
 AN ADDITIONAL SERVICE PER 230.2. THE RISER DOES NOT
 INDICATE ANY PROVISIONS FOR THIS POSSIBLE FUTURE TENANT
 AND THE NEW RISER WHICH IS BEING PROPOSED WOULD HAVE TO
 BE UPGRADED TO ACCOMMODATE THIS IN THE FUTURE. THE
 2-STORY BUILDING TO THE NORTH OF THE SINGLE STORY
 BUILDING WITH THE MULTIPLE METERED SERVICES MAY NOT
 FEED THIS FUTURE TENANT. BASED ON THE CONSTRUCTION AT
 THE SITE AND THE AERIALS, THIS TWO STRUCTURES APPEAR TO
 CONTAIN A FIRE WALL WHICH PENETRATES THE ROOF LINE AND
 SEPARATES THESE TWO AS BUILDINGS AS DEFINED IN THE
 FBC.
  
 PLEASE KNOW BASED ON THE SERVICE AS SHOWN THIS WILL
 ONLY BE ONE TENANT AND UNLESS UPGRADING THE NEW
 PROPOSED SERVICE IN THE FUTURE, NO OTHER SEPARATE
 TENANTS WILL OCCUPY FUTURE SPACE OR THE SPACE NOT BEING
 BUILT OUT AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE SERVICE AS SHOWN ON PLANS AND THAT OF
 WHICH IS BEING SHOWN ON RISER. IF SERVICE IS GOING TO
 BE NEW AS SHOWN ON RISER, PLEASE SHOW. PLEASE VERIFY
 WHERE THE REST OF THE SERVICE IS FOR FEEDING THE
 BUILDING. PLEASE SEE 230.2, 230.72 FOR SERVICES
 PERMITTED, AND GROUPING.
 PLEASE SEE PLANS INDICATE 200A'S EXISTING AND RISER
 SHOWS 150A.
 PLEASE INDICATE THE SIZE OF THE SERVICE ENTRANCE
 CONDUCTORS IN THE EXISTING RISER. CAN NOT VERIFY THE
 SEC'S AT THIS TIME. (NONE SHOWN)
 215.5, 310.16, 240.4 ETC
 FBC 106.1.2
  
 10) NOTE: NO, PLEASE SEE RESPONSE LETTER DOES NOTE
 RESPOND TO THIS COMMENT, IT SEEMS TO REPLY TO #11. ?
 PLEASE SEE THE SECTIONS GIVEN AS THE LOAD
 SUMMARY/CALCULATIONS ARE STILL NEEDED FOR REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE LOAD CALCULATIONS BASED ON THE NEC
 220.3, 220.10, 220.11, 220.13 AND CONTINUOUS LOADS AT
 125% 215.3, 230.42 ETC.
  
 11) NOTE: NO, THIS WAS IN RESPONSE LETTER AS COMMENT
 #10; HOWEVER PLEASE SEE THE ONLY AIC RATING WHICH COULD
 BE LOCATED ON E-2.0 WAS THE RATING FOR THE BRANCH
 BREAKERS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE AIC RATINGS FOR ALL SERVICE
 EQUIPMENT. PLANS INDICATE THE RATINGS FOR THE BRANCH
 BREAKERS ONLY ON THE PANEL SCHEDULE.
 PLEASE SEE 110.9, 240.12
 FBC 106.1.2 ADMIN SECT.
  
 12) NOTE: OK.
  
  
 *** NEW NOTES ***
  
 13) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. 106.1.2,
 106.3.5.1.2
 NEC 408.4, 310.16, 240.4
  
 14) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS FOR SPACE
 PER CHAPTER 13 OF TEH FBC 2004. 13-415.1.AB.1
 THIS WAS NOT REQUESTED ON THE PREVIOUS REVIEW, HOWEVER
 DUE TO NEW STORE FRONT, OCCUPANCY, SPACE NOT CURRENTLY
 OCCUPIED , REMOVAL OF WALLS, NEW CEILING, NE INSULATION
 ETC, CALCULATIONS FOR LIGHTING ETC WILL BE NEEDED.
 PLEASE SEE MECHANICAL COMMENTS AS THE PLANS INDICATE
 NEW SPACE BEING INTRODUCED FOR CONDITIONING FROM AN
 EXISTING A/C SYSTEM.
 PLEASE SEE NOTE ON ARCHITECTURAL SHEETS WHICH MENTIONS
 NEW A/C WORK. PLEASE CLARIFY.
  
 15) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]