Plan Review Notes
Plan Review Notes For Permit 06110263
Permit Number 06110263
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-19 14:29:41DENIED;
 1. PAGE A-1.0 SANITARY PLUMBING PIPES TO BE REMOVED
 BACK TO THE BUILDING DRAIN. NO DEAD ENDS PERMITED IN
 THE DRAINAGE SYSTEM. FBC-2004 SECTION 704.5. PLEASE ADD
 NOTE TO DEMO. PLAN, "ALLPLUMBING DEMO WORK TO BE DONE
 BY A LICENSED PLUMBING CONTRACTOR PERMIT AND
 INSPECTIONS REQUIRED".
 2. PAGE A-3.0 SANITARY RISER DIAGRAM. FUTURE SINK
 BRANCH DRAIN TO BE INSTALLED DOWN STREAM OF THE
 BATHROOM GROUP. SECTION 909.1.
 3. PER TABLE 403.1 (6) M MINIMUM NUMBER OF FIXTURES
 REQUIRED, A DRINKING FOUNTAIN IS REQUIRED. THE DRINKING
 FOUNTAIN MUST MEET THE REQUIREMENTS OF FBC-2004
 BUILDING CHAPTER11 SECTIONS 11-4.1.3(10). HANDICAP
 AND PEOPLE WITH BAD BACKS. SECTION 11-4.15.2 SPOUT
 HEIGH. SECTION 11-4.15.3 SPOUT LOCATION, SECTION
 11-4.15.4 CONTROLS, SECTION 11-4.15.5 CLEARANCES.
 PLEASE SHOW ELEVATION ON DRAWINGS.
 4.PAGE A-3.0 WATER RISER AIR CHAMBERS ARE NOT AN
 ENGINEER PRODUCT. PLEASE REMOVE FROM PLANS. WATER
 HAMMER ARRESTORS CAN BE INSTALLED AS REQUIRED BY
 SECTION 604.9. LIST MANUFACTURE AND MODEL NUMBER. WHA'S
 ARE TO BE INSTALLED PER MANUFACTURE INSTALLATION
 INSTRUCTIONS, AS CLOSE TO THE SOURCE OF HAMMERAS
 PERMITED NOT IN THE CEILING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695