| Plan Review Notes For Permit 06110263 |
| Permit Number |
06110263 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-19 14:29:41 | DENIED; | | | 1. PAGE A-1.0 SANITARY PLUMBING PIPES TO BE REMOVED | | | BACK TO THE BUILDING DRAIN. NO DEAD ENDS PERMITED IN | | | THE DRAINAGE SYSTEM. FBC-2004 SECTION 704.5. PLEASE ADD | | | NOTE TO DEMO. PLAN, "ALLPLUMBING DEMO WORK TO BE DONE | | | BY A LICENSED PLUMBING CONTRACTOR PERMIT AND | | | INSPECTIONS REQUIRED". | | | 2. PAGE A-3.0 SANITARY RISER DIAGRAM. FUTURE SINK | | | BRANCH DRAIN TO BE INSTALLED DOWN STREAM OF THE | | | BATHROOM GROUP. SECTION 909.1. | | | 3. PER TABLE 403.1 (6) M MINIMUM NUMBER OF FIXTURES | | | REQUIRED, A DRINKING FOUNTAIN IS REQUIRED. THE DRINKING | | | FOUNTAIN MUST MEET THE REQUIREMENTS OF FBC-2004 | | | BUILDING CHAPTER11 SECTIONS 11-4.1.3(10). HANDICAP | | | AND PEOPLE WITH BAD BACKS. SECTION 11-4.15.2 SPOUT | | | HEIGH. SECTION 11-4.15.3 SPOUT LOCATION, SECTION | | | 11-4.15.4 CONTROLS, SECTION 11-4.15.5 CLEARANCES. | | | PLEASE SHOW ELEVATION ON DRAWINGS. | | | 4.PAGE A-3.0 WATER RISER AIR CHAMBERS ARE NOT AN | | | ENGINEER PRODUCT. PLEASE REMOVE FROM PLANS. WATER | | | HAMMER ARRESTORS CAN BE INSTALLED AS REQUIRED BY | | | SECTION 604.9. LIST MANUFACTURE AND MODEL NUMBER. WHA'S | | | ARE TO BE INSTALLED PER MANUFACTURE INSTALLATION | | | INSTRUCTIONS, AS CLOSE TO THE SOURCE OF HAMMERAS | | | PERMITED NOT IN THE CEILING. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|