| 2006-11-21 07:44:59 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE PLANS REFLECT THE 2001 FBC; HOWEVER |
| | AS OF OCT 1ST, 2005 THE STATE OF FLORIDA ADOPTED THE |
| | 2004 FBC. PLEASE ADJUST AND CHANGE AS NEED. |
| | PLEASE ALSO SEE TWO SEPARATE LS CODES ARE REFERENCED ON |
| | PLANS. (2000& 2003). |
| | PLEASE SEE OTHER LOCATIONS WHERE THE PLANS REFLECT THE |
| | "LATEST ADOPTED" ETC. |
| | PLEASE BE SURE THE FOLLOWING CODES ARE REFLECTED ON |
| | PLANS AS REQUIRED. |
| | 2002 NFPA-70 (NEC), 2003 NFPA-101 (LS), 2004 FBC, AND |
| | ANY OTHER CODES FROM OTHER TRADES. SEE COMMENTS FROM |
| | OTHER REVIEWERS. |
| | |
| | 2) NOTE: PLEASE 2004 FBC 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2 |
| | THIS SPACE APPEARS TO BE IN A BUILDING (BY DEFINITION) |
| | LARGER THAN 5K SQ FT AND MEETS OTHER SECTIONS OF THE |
| | CODE WHICH INVOKE CHAPTER 13. |
| | |
| | 3) NOTE: PLEASE INDICATE A NEW OR EXISTING SIGN |
| | CIRCUIT(S) PEER 600.5 THIS SPACE AND THE SPACE NEXT |
| | DOOR AS SCOPE OF WORK ON ARCHITECTURAL PLANS INDICATE |
| | WORK BEING DON ON THE STOREFRONT NEXT DOOR. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: PLEASE VERIFY THE SCOPE OF WORK BEING DONE ON |
| | THE TWO SPACES ADJACENT TO THIS SPACE. SEEMS TO BE |
| | INSTALLING NEW STOREFRONT, HOWEVER NO ELECTRICAL IS |
| | BEING SHOWN FOR SIGNAGE OR SHOW WINDOW RECEPTS. 600.5, |
| | 210.62, 220.12. |
| | SUBMIT DETAILS/PLANS. FBC 106.1.2 ADMIN SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 5) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTS AS |
| | REQUIRED PER 210.62 AND PLEASE ADJUST LOAD CALCULATIONS |
| | AS REQUIRED. 220.12 |
| | |
| | 6) NOTE: PLEASE SEE PLANS APPEAR TO SHOW "COMMON AREA" |
| | LIGHTING WHICH IS BEING FED FROM THIS TENANT'S SPACE. |
| | PLEASE KNOW THIS IS NOT PERMITTED UNLESS THIS IS INDEED |
| | LOCATED ON THIS TENANT'S REAR SECTION OF SPACE. THE |
| | OTHER SCENARIO WOULD BE TO SERVE THE COMMON AREA LIGHT |
| | FROM A "HOUSE PANEL". |
| | 210.25. |
| | 230.2. |
| | |
| | 7) NOTE: PLEASE SEE PLANS DO NOT SEEM TO INDICATE ANY |
| | LIGHTING IN THE TOILET AREA. THERE IS A SWITCH; HOWEVER |
| | THIS IS NOT SHOWN FEEDING ANYTHING? |
| | PLEASE SEE LS 101 7.8 WHICH WILL REQUIRE SOME SORT OF |
| | FIXTURE. |
| | |
| | 8) NOTE: PLEASE SEE COLOR CODING FOR OTHER ELECTRICAL |
| | SYSTEM VOLTAGES ARE PRESENT ON PLANS, HOWEVER THERE ARE |
| | NO COLOR CODING FOR THE VOLTAGE ACTUALLY BEING |
| | INSTALLED. |
| | PLEASE SEE SERVICE IS BEING SHOWN AS A 120/240V |
| | /HIGH-LEGSERVICE. |
| | PLEASE SEE NEC 215.8 |
| | |
| | 9) NOTE: PLEASE CORRELATE SERVICE AS SHOWN ON PLANS AND |
| | THAT OF WHICH IS BEING SHOWN ON RISER. IF SERVICE IS |
| | GOING TO BE NEW AS SHOWN ON RISER, PLEASE SHOW. PLEASE |
| | VERIFY WHERE THE REST OF THE SERVICE IS FOR FEEDING THE |
| | BUILDING. PLEASE SEE 230.2, 230.72 FOR SERVICES |
| | PERMITTED, AND GROUPING. |
| | PLEASE SEE PLANS INDICATE 200A'S EXISTING AND RISER |
| | SHOWS 150A. |
| | PLEASE INDICATE THE SIZE OF THE SERVICE ENTRANCE |
| | CONDUCTORS IN THE EXISTING RISER. CAN NOT VERIFY THE |
| | SEC'S AT THIS TIME. (NONE SHOWN) |
| | 215.5, 310.16, 240.4 ETC |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SUBMIT THE LOAD CALCULATIONS BASED ON |
| | THE NEC 220.3, 220.10, 220.11, 220.13 AND CONTINUOUS |
| | LOADS AT 125% 215.3, 230.42 ETC. |
| | |
| | 11) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL |
| | SERVICE EQUIPMENT. PLANS INDICATE THE RATINGS FOR THE |
| | BRANCH BREAKERS ONLY ON THE PANEL SCHEDULE. |
| | PLEASE SEE 110.9, 240.12 |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 12) NOTE: PLEASE SEE PLANS MENTIONS TO PLACE PANEL IN |
| | THE STOCKROOM WHICH WILL NOT BE PERMITTED. PLEASE |
| | RELOCATE AT THIS TIME. PLEASE SEE 408.7, 240.24, AND |
| | 110.26. |
| | |
| | ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED OR |
| | WILL BE REQUIRED TO BE ADJUSTED, THERE MAY BE COMMENTS |
| | ON THE NEXT REVIEW. |
| | |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF |
| | THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE |
| | NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO |
| | NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |