Plan Review Notes
Plan Review Notes For Permit 06110263
Permit Number 06110263
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-21 07:44:59*** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS REFLECT THE 2001 FBC; HOWEVER
 AS OF OCT 1ST, 2005 THE STATE OF FLORIDA ADOPTED THE
 2004 FBC. PLEASE ADJUST AND CHANGE AS NEED.
 PLEASE ALSO SEE TWO SEPARATE LS CODES ARE REFERENCED ON
 PLANS. (2000& 2003).
 PLEASE SEE OTHER LOCATIONS WHERE THE PLANS REFLECT THE
 "LATEST ADOPTED" ETC.
 PLEASE BE SURE THE FOLLOWING CODES ARE REFLECTED ON
 PLANS AS REQUIRED.
 2002 NFPA-70 (NEC), 2003 NFPA-101 (LS), 2004 FBC, AND
 ANY OTHER CODES FROM OTHER TRADES. SEE COMMENTS FROM
 OTHER REVIEWERS.
  
 2) NOTE: PLEASE 2004 FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE 13-415.1.AB.1, 13-415.2
 THIS SPACE APPEARS TO BE IN A BUILDING (BY DEFINITION)
 LARGER THAN 5K SQ FT AND MEETS OTHER SECTIONS OF THE
 CODE WHICH INVOKE CHAPTER 13.
  
 3) NOTE: PLEASE INDICATE A NEW OR EXISTING SIGN
 CIRCUIT(S) PEER 600.5 THIS SPACE AND THE SPACE NEXT
 DOOR AS SCOPE OF WORK ON ARCHITECTURAL PLANS INDICATE
 WORK BEING DON ON THE STOREFRONT NEXT DOOR.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE VERIFY THE SCOPE OF WORK BEING DONE ON
 THE TWO SPACES ADJACENT TO THIS SPACE. SEEMS TO BE
 INSTALLING NEW STOREFRONT, HOWEVER NO ELECTRICAL IS
 BEING SHOWN FOR SIGNAGE OR SHOW WINDOW RECEPTS. 600.5,
 210.62, 220.12.
 SUBMIT DETAILS/PLANS. FBC 106.1.2 ADMIN SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 5) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTS AS
 REQUIRED PER 210.62 AND PLEASE ADJUST LOAD CALCULATIONS
 AS REQUIRED. 220.12
  
 6) NOTE: PLEASE SEE PLANS APPEAR TO SHOW "COMMON AREA"
 LIGHTING WHICH IS BEING FED FROM THIS TENANT'S SPACE.
 PLEASE KNOW THIS IS NOT PERMITTED UNLESS THIS IS INDEED
 LOCATED ON THIS TENANT'S REAR SECTION OF SPACE. THE
 OTHER SCENARIO WOULD BE TO SERVE THE COMMON AREA LIGHT
 FROM A "HOUSE PANEL".
 210.25.
 230.2.
  
 7) NOTE: PLEASE SEE PLANS DO NOT SEEM TO INDICATE ANY
 LIGHTING IN THE TOILET AREA. THERE IS A SWITCH; HOWEVER
 THIS IS NOT SHOWN FEEDING ANYTHING?
 PLEASE SEE LS 101 7.8 WHICH WILL REQUIRE SOME SORT OF
 FIXTURE.
  
 8) NOTE: PLEASE SEE COLOR CODING FOR OTHER ELECTRICAL
 SYSTEM VOLTAGES ARE PRESENT ON PLANS, HOWEVER THERE ARE
 NO COLOR CODING FOR THE VOLTAGE ACTUALLY BEING
 INSTALLED.
 PLEASE SEE SERVICE IS BEING SHOWN AS A 120/240V
 /HIGH-LEGSERVICE.
 PLEASE SEE NEC 215.8
  
 9) NOTE: PLEASE CORRELATE SERVICE AS SHOWN ON PLANS AND
 THAT OF WHICH IS BEING SHOWN ON RISER. IF SERVICE IS
 GOING TO BE NEW AS SHOWN ON RISER, PLEASE SHOW. PLEASE
 VERIFY WHERE THE REST OF THE SERVICE IS FOR FEEDING THE
 BUILDING. PLEASE SEE 230.2, 230.72 FOR SERVICES
 PERMITTED, AND GROUPING.
 PLEASE SEE PLANS INDICATE 200A'S EXISTING AND RISER
 SHOWS 150A.
 PLEASE INDICATE THE SIZE OF THE SERVICE ENTRANCE
 CONDUCTORS IN THE EXISTING RISER. CAN NOT VERIFY THE
 SEC'S AT THIS TIME. (NONE SHOWN)
 215.5, 310.16, 240.4 ETC
 FBC 106.1.2
  
 10) NOTE: PLEASE SUBMIT THE LOAD CALCULATIONS BASED ON
 THE NEC 220.3, 220.10, 220.11, 220.13 AND CONTINUOUS
 LOADS AT 125% 215.3, 230.42 ETC.
  
 11) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL
 SERVICE EQUIPMENT. PLANS INDICATE THE RATINGS FOR THE
 BRANCH BREAKERS ONLY ON THE PANEL SCHEDULE.
 PLEASE SEE 110.9, 240.12
 FBC 106.1.2 ADMIN SECT.
  
 12) NOTE: PLEASE SEE PLANS MENTIONS TO PLACE PANEL IN
 THE STOCKROOM WHICH WILL NOT BE PERMITTED. PLEASE
 RELOCATE AT THIS TIME. PLEASE SEE 408.7, 240.24, AND
 110.26.
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED OR
 WILL BE REQUIRED TO BE ADJUSTED, THERE MAY BE COMMENTS
 ON THE NEXT REVIEW.
  
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF
 THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-21 06:59:23IN PRGRESS
2006-11-20 20:28:01NOTES TO FOLLOW.