| Date |
Text |
| 2006-12-24 16:21:03 | PLANS WERE REVIEWED ON 11/17/06, THESE HAVE NOT BEEN |
| | RESUBMITTED. |
| 2006-11-17 16:59:36 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE THE PERMIT APPLICATION SUBMITTED |
| | WAS SUBMITTED BY AN ELECTRICAL CONTRACTOR WHEREAS |
| | SCOPES OF WORK SUBMITTED ON PLANS ARE FOR OTHER TRADES |
| | WHICH AN ELECTRICAL CONTRACTOR CAN NOT PERFORM. PLEASE |
| | CLARIFY SCOPE AS APPLIED FOR AS PLANS INDICATE |
| | INSTALLATION OF NEW CONCRETE SUPPORTS (TYP) ON "M" |
| | SHEETS, HOWEVER NOT ON "S' SHEETS? SEE BUILDING REVIEW |
| | NOTES. |
| | FS 489 |
| | |
| | 2) NOTE: PLEASE SEE VALUE ON PLANS FOR SCOPE OF WORK |
| | SUBMITTED SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF |
| | EQUIPMENT/MATERIALS IS OWNER SUPPLIED. |
| | FBC 108.3 |
| | |
| | 3) NOTE: PLEASE SEE ADDRESS ON TITLE BLOCKS FOR CAMP, |
| | DRESSER & MCKEE INC, DOES NOT CORRELATE WITH THE |
| | STATE'S WEBSITE. PLEASE OBTAIN WRITTEN DOCUMENTATION |
| | FROM THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION THAT THE ADDRESS AS SHOWN LOCALLY IS OK, |
| | WHICH DOES NOT CORRESPOND TO THE STATE'S TAMPA |
| | ADDRESS. |
| | |
| | OPT#2, PLEASE ADJUST TITLE BLOCKS TO REFLECT THE |
| | ADDRESS AS LISTED ON STATE'S WEBSITE. PLEASE SEE THAT I |
| | HAVE ATTACHED A PRINT FROM THE STATE DBPR'S WEBSITE |
| | WHICH REFLECTS THIS. |
| | |
| | |
| | |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.**IF |
| | THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE |
| | NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO |
| | NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |