| Plan Review Notes For Permit 06110259 |
| Permit Number |
06110259 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-15 13:56:09 | | | | | | | | | | NONCOMPLIANT | | | THIS PERMIT IS BEING ISSUED TO | | | FACILITATE THE START OF THIS PROJECT. | | | THE PLANS HOWEVER NEED TO BE REVISED. | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW WITHIN 15 WORKING | | | DAYS OF THE PERMIT BEING ISSUED. | | | | | | 1} THE #4 COPPER GROUNDING ELECTRODE CONDUCTORS LOCATED | | | AT THE "SERVICE POINTA & BPOWER RISER DIAGRAM", DO | | | NOT COMPLY WITH ARTICLE 250.66 NEC. FOR 300MCMA #2 | | | COPPERGEC WOULD BE REQUIRED. SHEET L-23, LAKEVIEW TO | | | PALM BEACH LAKES PLAN, SHEET L-20. PALM BEACH LAKES TO | | | 26TH, SERVICE POINT "A" SHEET L-24. | | | | | | 2} THERE IS NO SCHEDULE FOR THE 300 AMP "MAIN" FEEDING | | | THE CONTACTORS THEN THE 200 AMP PANEL WITH #3/0 | | | CONDUCTORS. PLEASE PROVIDE A SCHEDULE INDICATING OCP | | | FOR THIS FEEDAND THE #12 CONDUCTORS OR INSTALL OCP | | | FOR THOSE CONDUCTORS. ALSO THERE IS NO OCP SHOWN FOR | | | PANEL "AV". | | | | | | 3} THE METRIC DESIGNATOR USED FOR THE CONDUIT SIZE IS | | | INCORRECT. SEE 300.1(C) AND ANNEX "C". ALL SHEETS. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|