| Plan Review Notes For Permit 06110243 |
| Permit Number |
06110243 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-27 15:36:29 | *****DENIED***** | | | | | | | | | | | | 1.THE PERMIT APPLICATION AND THE DOCUMENT SUBMITTAL | | | SHEETS REFLECT THE JOB ADDRESS AS 1675 PALM BEACH LAKES | | | BOULEVARD, WHEREAS THE ASSIGNED PERMIT NUMBER HAS THE | | | ADDRESS OF 1665 PALM BEACH LAKES BOULEVARD. | | | | | | 2.SINCE THE CONTRACT IS GREATER THAN $2500.00, THE | | | APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED | | | NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT | | | THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A | | | COPY THEREOF. | | | | | | 3.THE LOCATION OF THE SCOPE OF THE WORK SHOULD BE IN | | | THE TITLE BLOCK OF THE SUBMITTED PLANS. | | | | | | 4.AS PER WPB FIRE PREVENTION, DUCT SMOKE DETECTORS | | | SHALL INITIATE GENERAL FIRE ALARM.AMEND NOTE #8 ON | | | LEGEND PLAN SHEET. | | | | | | 5.HOW WILL THE PROPOSED FIRE ALARM WORK IN THE | | | BUILDING BE SCHEDULED?I.E. HOW MANY FLOORS WILL BE | | | DONE AT ONE TIME? | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|