Plan Review Notes
Plan Review Notes For Permit 06110243
Permit Number 06110243
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-27 15:36:29*****DENIED*****
  
  
  
 1.THE PERMIT APPLICATION AND THE DOCUMENT SUBMITTAL
 SHEETS REFLECT THE JOB ADDRESS AS 1675 PALM BEACH LAKES
 BOULEVARD, WHEREAS THE ASSIGNED PERMIT NUMBER HAS THE
 ADDRESS OF 1665 PALM BEACH LAKES BOULEVARD.
  
 2.SINCE THE CONTRACT IS GREATER THAN $2500.00, THE
 APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT
 THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A
 COPY THEREOF.
  
 3.THE LOCATION OF THE SCOPE OF THE WORK SHOULD BE IN
 THE TITLE BLOCK OF THE SUBMITTED PLANS.
  
 4.AS PER WPB FIRE PREVENTION, DUCT SMOKE DETECTORS
 SHALL INITIATE GENERAL FIRE ALARM.AMEND NOTE #8 ON
 LEGEND PLAN SHEET.
  
 5.HOW WILL THE PROPOSED FIRE ALARM WORK IN THE
 BUILDING BE SCHEDULED?I.E. HOW MANY FLOORS WILL BE
 DONE AT ONE TIME?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722