| Plan Review Notes For Permit 06110215 |
| Permit Number |
06110215 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-05-16 17:01:03 | *** PROVISO/REVISION *** | | | | | | 1) NOTE: PLEASE SEE THE MICROWAVE AS SHOWN ON PANEL | | | SCHEDULE IS NOT SHOWN OR FIGURED INTO LOAD | | | CALCULATIONS. | | | PLEASE ADJUST AND UPDATE. 220, 408.4. | | | FBC 106.1.2, 106.3.5.4 | | | | | | 2) NOTE: PLEASE SEE THE DINING ROOM CIRCUIT WHICH IS | | | BEING SHOWN AS 15AMP, WHEN 210.52B1, 210.11C1 REQUIRES | | | THIS AS A 20AMP CIRCUIT. | | | | | | 3) NOTE: PLEASE CORRECT ANY CIRCUITING ON PLANS AND | | | CORRELATE WITH THE PANEL SCHEDULE. PLEASE SEE SOME | | | CIRCUITS SHOWN, SOME NOT, AND SOME OF THE SHOWN | | | CIRCUITS DO NOT CORRELATE WITH THE SUBMITTED PANEL | | | SCHEDULE. 408.4 | | | | | | ** PLEASE SUBMIT THE ABOVE CORRECTIONS ALONG WITH ANY | | | OTHER REVISIONS BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | 561-805-6717 |
|