| Plan Review Notes For Permit 06110215 |
| Permit Number |
06110215 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-05-02 09:14:46 | DENIED; | | | 1. (2ND REQUEST) REMOVE OR CHANGE , PLUMBING NOTE # 1 | | | ON PAGE C-1. PIPES 2 1/2" OR LESS SHALL SLOPE 1/4" PER | | | FOOT SEE SECTION 704.1. | | | 2. WATER HEATER NOT SHOWN ON FLOOR PLAN. | | | 3. PAGE E-1 IS NOT SIGNED OR DATED. STONE ELECTRIC | | | CANNOT DESIGN A PLUMBING SANITARY RISER DIAGRAM. | | | 4. SANITARY RISER DIAGRAM LOOKS LIKE ONE OF THE | | | BATHROOMS IS ON THE 2ND FLOOR OF A ONE STORE HOME. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|