| 2007-04-21 07:46:48 | *** UNSAT 3RD REVIEW *** |
| | |
| | ** IMPORTANT** |
| | THE REVIEW PROCESS HAS BEEN STOPPED AND PLANS HAVE BEEN |
| | PLACED OUT FRONT UNTIL THE RE-SUB FEE IS PAID. ALL FEES |
| | ARE DUE AT THE TIME OF SUBMITTING PLANS. THIS OFFICE |
| | HAS INFORMED THE CONTRACTOR OF THIS ON SEVERAL |
| | OCCASIONS. THE FEE OF $290.80 MUST BE PAID BEFORE PLANS |
| | CONTINUE THE ROUTING/REVIEW PROCESS. |
| | |
| | ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS |
| | REVIEWS WHICH ARE STILL NOT DONE. |
| | |
| | 1) NOTE: THIS WAS THE SAME NOTE ON PREVIOUS REVIEW. |
| | PLEASE SEE THAT THE PLANS WHEN FALLING UNDER THE |
| | EXCEPTIONS OF THE FLORIDA STATUTES FOR A SF RESIDENCE |
| | MUST STILL CONTAIN A *PRINTED NAME* AND *SIGNATURE* OF |
| | THE PERSON TAKING RESPONSIBILITY OF PLANS. |
| | FS 471.003, 481.229, 489 |
| | FBC 106.1.2 |
| | |
| | 2) NOTE:PLEASE SEE THIS IS THE SAME NOTE FROM |
| | PREVIOUS REVIEWS. MANY ITEMS WERE CHANGED HOWEVER NOT |
| | ALL. |
| | PLEASE SEE THAT THERE ARE LOADS WHICH ARE SHOWN ON THE |
| | PANEL SCHEDULE WHICH DO NOT CORRELATE WITH THE LOAD |
| | CALCULATIONS. PLEASE CORRELATE AND SEE THE NEC FOR ALL |
| | MINIMUM LOADS TO BE SHOWN AND FIGURED FOR DEDICATED |
| | CIRCUITS AND APPLIANCE LOADS. |
| | PLEASE SEE STILL MISSING : |
| | MICROWAVE |
| | POOL PUMP |
| | EVEN IF THESE ITEMS ARE SHOWN AS OPTIONAL, THEY WOULD |
| | STILL BE FIGURED INTO THE LOAD CALCULATIONS. |
| | NEC 220. |
| | FBC 106.3.5.4 |
| | |
| | 3) NOTE: SAME NOTE AS TWO PREVIOUS REVIEWS. |
| | THIS LEADS DIRECTLY INTO THE FOLLOWING COMMENT. |
| | PLEASE SEE MISSING BATH DEDICATED CIRCUIT(S). 210.52D, |
| | 210.11C3 |
| | PREVIOUS NOTES. |
| | |
| | 4) NOTE:PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED |
| | A DETAILED PANEL SCHEDULE AS REQUIRED BY THE CODE. |
| | PLEASE SEE THAT THE PANEL SCHEDULE SHOWN IS MOSTLY SET |
| | UP AND LOAD CALCULATIONS. PLEASE KNOW THAT A PANEL |
| | SCHEDULE MUST SHOW ALL MINIMUM CIRCUITS (NOTE #3) |
| | PLEASE SEE IF A PANEL SCHEDULE STILL INDICATES A |
| | CERTAIN AMOUNT OF CIRCUITS AS GENERAL LTS, GENERAL |
| | RECEPTS, THEN THE MINIMUM REQUIRED DEDICATED CIRCUITS |
| | AS NOTED FOR NOTE #3 ABOVE, AND OTHER AREAS AS NOTED ON |
| | THE PREVIOUS REVIEW FOR DINING ROOM ETC CAN NOT BE |
| | VERIFIED. |
| | PLEASE COMPLETE. IT IS KNOWN THAT THESE ITEMS MAY BE |
| | CHANGED DURING CONSTRUCTION, HOWEVER THE *MINIMUM* IS |
| | REQUIRED BY CODE TO BE SHOWN. |
| | PLEASE SEE THAT THE PANEL SCHEDULE FOR ALL CIRCUITS |
| | SHALL BE SPECIFIC AS REQUESTED ON PREVIOUS REVIEW. |
| | PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM |
| | THE NEC CODE COMMENTARY. |
| | |
| | *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4, |
| | 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 5) NOTE: AS NOTED ON PREVIOUS REVIEWS AND AS THE PANEL |
| | SCHEDULE IS NOT COMPLETE AT THIS TIME THE MINIMUM |
| | CIRCUITS AND LOADS CAN NOT BE VERIFIED AT THIS TIME. |
| | PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR ALL MINIMUM |
| | LOADS FOR ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS. |
| | THE DINING ROOM, BREAKFAST ROOMS/AREAS ARE ALSO |
| | CONSIDERED IN THIS REQUIREMENT AS STATED IN 210.52B1. |
| | PLEASE SEE THE TOTAL OF 1500VA IS TO BE SHOWN FOR EACH |
| | OF THESE DEDICATED CIRCUITS. PLEASE INDICATE HOW THE |
| | DINING ROOM RECEPTACLES AND BREAKFAST AREA RECEPTACLES |
| | ARE BEING FED. PLEASE BE SURE TO ADJUST ANY LOAD |
| | CALCULATIONS AS NEEDED. |
| | PLEASE CORRELATE AND ADJUST. |
| | |
| | 6) NOTE:PLEASE SEE PREVIOUS REVIEW GAVE A NOTICE TO |
| | THIS SECTION OF THE FLORIDA STATUTES WHICH REQUIRES A |
| | LOCAL JURISDICTION TO ASSESS A FEE WHEN *ANY* OF THE |
| | SAME REPEAT CODE COMPLIANT COMMENT IS MADE THREE OR |
| | MORE TIMES THIS FEE IS ASSESSED AS REQUIRED. A FEE OF |
| | $3,489.56 IS DUE UPON RE-SUBMITTAL OF PLANS. |
| | AS STATED IN THE TWO PREVIOUS REVIEWS, IF THERE ARE ANY |
| | QUESTIONS TO PLEASE CONTACT THIS OFFICE TO GO OVER |
| | COMMENTS. |
| | PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE SEE THERE ARE SOME COMMENTS WHICH ARE THE SAME |
| | FROM PREVIOUS REVIEW. THIS IS ONLY GIVEN AS A NOTICE AT |
| | THIS TIME. |
| | PLEASE GO THROUGH ALL NOTES CAREFULLY AND ADJUST |
| | PLANS. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |