Plan Review Notes
Plan Review Notes For Permit 06110215
Permit Number 06110215
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-21 07:46:48*** UNSAT 3RD REVIEW ***
  
 ** IMPORTANT**
 THE REVIEW PROCESS HAS BEEN STOPPED AND PLANS HAVE BEEN
 PLACED OUT FRONT UNTIL THE RE-SUB FEE IS PAID. ALL FEES
 ARE DUE AT THE TIME OF SUBMITTING PLANS. THIS OFFICE
 HAS INFORMED THE CONTRACTOR OF THIS ON SEVERAL
 OCCASIONS. THE FEE OF $290.80 MUST BE PAID BEFORE PLANS
 CONTINUE THE ROUTING/REVIEW PROCESS.
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEWS WHICH ARE STILL NOT DONE.
  
 1) NOTE: THIS WAS THE SAME NOTE ON PREVIOUS REVIEW.
 PLEASE SEE THAT THE PLANS WHEN FALLING UNDER THE
 EXCEPTIONS OF THE FLORIDA STATUTES FOR A SF RESIDENCE
 MUST STILL CONTAIN A *PRINTED NAME* AND *SIGNATURE* OF
 THE PERSON TAKING RESPONSIBILITY OF PLANS.
 FS 471.003, 481.229, 489
 FBC 106.1.2
  
 2) NOTE:PLEASE SEE THIS IS THE SAME NOTE FROM
 PREVIOUS REVIEWS. MANY ITEMS WERE CHANGED HOWEVER NOT
 ALL.
 PLEASE SEE THAT THERE ARE LOADS WHICH ARE SHOWN ON THE
 PANEL SCHEDULE WHICH DO NOT CORRELATE WITH THE LOAD
 CALCULATIONS. PLEASE CORRELATE AND SEE THE NEC FOR ALL
 MINIMUM LOADS TO BE SHOWN AND FIGURED FOR DEDICATED
 CIRCUITS AND APPLIANCE LOADS.
 PLEASE SEE STILL MISSING :
 MICROWAVE
 POOL PUMP
 EVEN IF THESE ITEMS ARE SHOWN AS OPTIONAL, THEY WOULD
 STILL BE FIGURED INTO THE LOAD CALCULATIONS.
 NEC 220.
 FBC 106.3.5.4
  
 3) NOTE: SAME NOTE AS TWO PREVIOUS REVIEWS.
 THIS LEADS DIRECTLY INTO THE FOLLOWING COMMENT.
 PLEASE SEE MISSING BATH DEDICATED CIRCUIT(S). 210.52D,
 210.11C3
 PREVIOUS NOTES.
  
 4) NOTE:PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 A DETAILED PANEL SCHEDULE AS REQUIRED BY THE CODE.
 PLEASE SEE THAT THE PANEL SCHEDULE SHOWN IS MOSTLY SET
 UP AND LOAD CALCULATIONS. PLEASE KNOW THAT A PANEL
 SCHEDULE MUST SHOW ALL MINIMUM CIRCUITS (NOTE #3)
 PLEASE SEE IF A PANEL SCHEDULE STILL INDICATES A
 CERTAIN AMOUNT OF CIRCUITS AS GENERAL LTS, GENERAL
 RECEPTS, THEN THE MINIMUM REQUIRED DEDICATED CIRCUITS
 AS NOTED FOR NOTE #3 ABOVE, AND OTHER AREAS AS NOTED ON
 THE PREVIOUS REVIEW FOR DINING ROOM ETC CAN NOT BE
 VERIFIED.
 PLEASE COMPLETE. IT IS KNOWN THAT THESE ITEMS MAY BE
 CHANGED DURING CONSTRUCTION, HOWEVER THE *MINIMUM* IS
 REQUIRED BY CODE TO BE SHOWN.
 PLEASE SEE THAT THE PANEL SCHEDULE FOR ALL CIRCUITS
 SHALL BE SPECIFIC AS REQUESTED ON PREVIOUS REVIEW.
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC CODE COMMENTARY.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: AS NOTED ON PREVIOUS REVIEWS AND AS THE PANEL
 SCHEDULE IS NOT COMPLETE AT THIS TIME THE MINIMUM
 CIRCUITS AND LOADS CAN NOT BE VERIFIED AT THIS TIME.
 PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR ALL MINIMUM
 LOADS FOR ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS.
 THE DINING ROOM, BREAKFAST ROOMS/AREAS ARE ALSO
 CONSIDERED IN THIS REQUIREMENT AS STATED IN 210.52B1.
 PLEASE SEE THE TOTAL OF 1500VA IS TO BE SHOWN FOR EACH
 OF THESE DEDICATED CIRCUITS. PLEASE INDICATE HOW THE
 DINING ROOM RECEPTACLES AND BREAKFAST AREA RECEPTACLES
 ARE BEING FED. PLEASE BE SURE TO ADJUST ANY LOAD
 CALCULATIONS AS NEEDED.
 PLEASE CORRELATE AND ADJUST.
  
 6) NOTE:PLEASE SEE PREVIOUS REVIEW GAVE A NOTICE TO
 THIS SECTION OF THE FLORIDA STATUTES WHICH REQUIRES A
 LOCAL JURISDICTION TO ASSESS A FEE WHEN *ANY* OF THE
 SAME REPEAT CODE COMPLIANT COMMENT IS MADE THREE OR
 MORE TIMES THIS FEE IS ASSESSED AS REQUIRED. A FEE OF
 $3,489.56 IS DUE UPON RE-SUBMITTAL OF PLANS.
 AS STATED IN THE TWO PREVIOUS REVIEWS, IF THERE ARE ANY
 QUESTIONS TO PLEASE CONTACT THIS OFFICE TO GO OVER
 COMMENTS.
 PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE THERE ARE SOME COMMENTS WHICH ARE THE SAME
 FROM PREVIOUS REVIEW. THIS IS ONLY GIVEN AS A NOTICE AT
 THIS TIME.
 PLEASE GO THROUGH ALL NOTES CAREFULLY AND ADJUST
 PLANS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  