Plan Review Notes
Plan Review Notes For Permit 06110215
Permit Number 06110215
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-21 07:41:14NOTE ADDED, PLEASE SEE THE NOTICE OF COMMENCMENT HAS
 SINCE EXPIRED AND IS NOW VOID. FS 713.13(2).
2007-03-21 07:36:21 
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEWS AND MANY NEW COMMENTS AND NEW OR CHANGED
 ELECTRICAL SHEETS AND INFORMATION IS NOW SUBMITTED OR
 DIFFERENT ON PLANS SUBMITTED.
  
 1) NOTE: PLEASE SEE THAT THE PLANS WHEN FALLING UNDER
 THE EXCEPTIONS OF THE FLORIDA STATUTES FOR A SF
 RESIDENCE MUST STILL CONTAIN A *PRINTED NAME* AND
 *SIGNATURE* OF THE PERSON TAKING RESPONSIBILITY OF
 PLANS.
 FS 471.003, 481.229, 489
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE PLANS STILL INDICATE A MAIN
 DISCONNECT OUTSIDE ON THE PLANS WHEREAS THE RISER DOES
 NOT INDICATE ANY MAIN. PLEASE CORRELATE AND KNOW IF A
 MAIN IS INSTALLED OUTSIDE, THEN AN EQUIPMENT GROUNDING
 CONDUCTOR WOULD BE REQUIRED FROM THE MAIN TO THE SUB
 PANEL INSIDE.
 PLEASE CORRELATE.
 NEC 215.5, 250.24B, 250.122
 FBC 106.1.2, 106.3.5.4
  
 3) NOTE: PLEASE SEE THAT THERE ARE NUMEROUS LOADS WHICH
 ARE SHOWN ON THE PANEL SCHEDULE WHICH DO NOT CORRELATE
 WITH THE LOAD CALCULATIONS. PLEASE CORRELATE AND SEE
 THE NEC FOR ALL MINIMUM LOADS TO BE SHOWN AND FIGURED
 FOR DEDICATED CIRCUITS AND APPLIANCE LOADS.
 PLEASE SEE:
 SMALL APPLIANCES
 GARAGE DOOR OPENER,
 WATER HEATER
 DRYER,
 MICROWAVE,
 DISHWASHER,
 DISPOSAL,
 ETC ETC.
 NEC 220.
  
 4) NOTE: PLEASE SEE MISSING BATH DEDICATED CIRCUIT(S).
 210.52D, 210.11C3
 PREVIOUS NOTES.
  
 5) NOTE: PLEASE SEE THAT THE PANEL SCHEDULE FOR ALL
 CIRCUITS SHALL BE SPECIFIC AS REQUESTED ON PREVIOUS
 REVIEW.
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC CODE COMMENTARY.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 6) NOTE: PLEASE SEE PLANS IN KITCHEN ARE MISSING THE
 RECEPTACLE OUTLETS FOR THE DISHWASHER AND DISPOSAL.
 PLEASE SEE THAT THE PANEL SCHEDULE INDICATES THESE ON A
 2-POLE BREAKER WHICH WOULD MEANS BOTH ARE BEING SERVED
 FROM THE SAME YOKE AS STATED IN 210.4, HOWEVER PLANS DO
 NOT SHOW ANY DEVICES.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE SAME AREA OF KITCHEN COUNTER
 SPACE AS DISH/DISPOSAL IS MISSING GFI RECEPTACLES AS
 REQUIRED PER 210.52C1. THIS WAS ON PREVIOUS NOTES. SEE
 REDLINED PLANS.
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE PER 210.52 IN
 BEDROOM #2.
  
 9) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR ALL
 MINIMUM LOADS FOR ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. THE DINING ROOM, BREAKFAST ROOMS/AREAS ARE
 ALSO CONSIDERED IN THIS REQUIREMENT AS STATED IN
 210.52B1. PLEASE SEE THE SMALL APPLIANCE CIRCUITS AS
 BEING SHOWN AT 750VA EACH??? PLEASE SEE THE TOTAL OF
 1500VA IS BEING SHOWN FOR BOTH ON THE LOAD
 CALCULATIONS.
 PLEASE CORRELATE AND ADJUST.
  
 10) NOTE: PLEASE SEE MISPRINT FOR NFPA-70, SHOWS NFPA-7
 WHICH IS DIFFERENT CODE. THIS WOULD HAVE BEEN
 RED-LINED, HOWEVER PLANS ARE COMING BACK FOR OTHER
 COMMENTS.
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. PLEASE SEE THERE ARE SOME COMMENTS WHICH
 ARE THE SAME FROM PREVIOUS REVIEW. THIS IS ONLY GIVEN
 AS A NOTICE AT THIS TIME.
 PLEASE GO THROUGH ALL NOTES CAREFULLY AND ADJUST
 PLANS.
  
 12) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE
 SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS
 SMOKE DETECTORS.
 PLEASE SEENFPA-72 AS THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS USE OF SD ON PLANS WAS INGENERAL USED SMOKE
 DETECTORS AND WAS ALWAYS ACCEPTED HOWEVER AS THERE IS
 SPECIFIC DIFFERENCE IN THE CODE PLEASE CHANGE PLANS FOR
 ACTUAL DEIVCES. PLEASE SEE THAT THIS IS NOT A NEW
 CODE.
  
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-20 20:35:432007-03-20 20:35:43
 NOTES TO FOLLOW