| 2007-03-21 07:41:14 | NOTE ADDED, PLEASE SEE THE NOTICE OF COMMENCMENT HAS |
| | SINCE EXPIRED AND IS NOW VOID. FS 713.13(2). |
| 2007-03-21 07:36:21 | |
| | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS |
| | REVIEWS AND MANY NEW COMMENTS AND NEW OR CHANGED |
| | ELECTRICAL SHEETS AND INFORMATION IS NOW SUBMITTED OR |
| | DIFFERENT ON PLANS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE THAT THE PLANS WHEN FALLING UNDER |
| | THE EXCEPTIONS OF THE FLORIDA STATUTES FOR A SF |
| | RESIDENCE MUST STILL CONTAIN A *PRINTED NAME* AND |
| | *SIGNATURE* OF THE PERSON TAKING RESPONSIBILITY OF |
| | PLANS. |
| | FS 471.003, 481.229, 489 |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE PLANS STILL INDICATE A MAIN |
| | DISCONNECT OUTSIDE ON THE PLANS WHEREAS THE RISER DOES |
| | NOT INDICATE ANY MAIN. PLEASE CORRELATE AND KNOW IF A |
| | MAIN IS INSTALLED OUTSIDE, THEN AN EQUIPMENT GROUNDING |
| | CONDUCTOR WOULD BE REQUIRED FROM THE MAIN TO THE SUB |
| | PANEL INSIDE. |
| | PLEASE CORRELATE. |
| | NEC 215.5, 250.24B, 250.122 |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 3) NOTE: PLEASE SEE THAT THERE ARE NUMEROUS LOADS WHICH |
| | ARE SHOWN ON THE PANEL SCHEDULE WHICH DO NOT CORRELATE |
| | WITH THE LOAD CALCULATIONS. PLEASE CORRELATE AND SEE |
| | THE NEC FOR ALL MINIMUM LOADS TO BE SHOWN AND FIGURED |
| | FOR DEDICATED CIRCUITS AND APPLIANCE LOADS. |
| | PLEASE SEE: |
| | SMALL APPLIANCES |
| | GARAGE DOOR OPENER, |
| | WATER HEATER |
| | DRYER, |
| | MICROWAVE, |
| | DISHWASHER, |
| | DISPOSAL, |
| | ETC ETC. |
| | NEC 220. |
| | |
| | 4) NOTE: PLEASE SEE MISSING BATH DEDICATED CIRCUIT(S). |
| | 210.52D, 210.11C3 |
| | PREVIOUS NOTES. |
| | |
| | 5) NOTE: PLEASE SEE THAT THE PANEL SCHEDULE FOR ALL |
| | CIRCUITS SHALL BE SPECIFIC AS REQUESTED ON PREVIOUS |
| | REVIEW. |
| | PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM |
| | THE NEC CODE COMMENTARY. |
| | |
| | *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4, |
| | 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 6) NOTE: PLEASE SEE PLANS IN KITCHEN ARE MISSING THE |
| | RECEPTACLE OUTLETS FOR THE DISHWASHER AND DISPOSAL. |
| | PLEASE SEE THAT THE PANEL SCHEDULE INDICATES THESE ON A |
| | 2-POLE BREAKER WHICH WOULD MEANS BOTH ARE BEING SERVED |
| | FROM THE SAME YOKE AS STATED IN 210.4, HOWEVER PLANS DO |
| | NOT SHOW ANY DEVICES. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE SAME AREA OF KITCHEN COUNTER |
| | SPACE AS DISH/DISPOSAL IS MISSING GFI RECEPTACLES AS |
| | REQUIRED PER 210.52C1. THIS WAS ON PREVIOUS NOTES. SEE |
| | REDLINED PLANS. |
| | |
| | 8) NOTE: PLEASE SEE MISSING RECEPTACLE PER 210.52 IN |
| | BEDROOM #2. |
| | |
| | 9) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR ALL |
| | MINIMUM LOADS FOR ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS. THE DINING ROOM, BREAKFAST ROOMS/AREAS ARE |
| | ALSO CONSIDERED IN THIS REQUIREMENT AS STATED IN |
| | 210.52B1. PLEASE SEE THE SMALL APPLIANCE CIRCUITS AS |
| | BEING SHOWN AT 750VA EACH??? PLEASE SEE THE TOTAL OF |
| | 1500VA IS BEING SHOWN FOR BOTH ON THE LOAD |
| | CALCULATIONS. |
| | PLEASE CORRELATE AND ADJUST. |
| | |
| | 10) NOTE: PLEASE SEE MISPRINT FOR NFPA-70, SHOWS NFPA-7 |
| | WHICH IS DIFFERENT CODE. THIS WOULD HAVE BEEN |
| | RED-LINED, HOWEVER PLANS ARE COMING BACK FOR OTHER |
| | COMMENTS. |
| | |
| | 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. PLEASE SEE THERE ARE SOME COMMENTS WHICH |
| | ARE THE SAME FROM PREVIOUS REVIEW. THIS IS ONLY GIVEN |
| | AS A NOTICE AT THIS TIME. |
| | PLEASE GO THROUGH ALL NOTES CAREFULLY AND ADJUST |
| | PLANS. |
| | |
| | 12) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE |
| | SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS |
| | SMOKE DETECTORS. |
| | PLEASE SEENFPA-72 AS THE USE OF SD FOR SMOKE |
| | DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT |
| | ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER |
| | THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS |
| | SA/SMOKE ALARMS. |
| | THIS USE OF SD ON PLANS WAS INGENERAL USED SMOKE |
| | DETECTORS AND WAS ALWAYS ACCEPTED HOWEVER AS THERE IS |
| | SPECIFIC DIFFERENCE IN THE CODE PLEASE CHANGE PLANS FOR |
| | ACTUAL DEIVCES. PLEASE SEE THAT THIS IS NOT A NEW |
| | CODE. |
| | |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |