| Plan Review Notes For Permit 06110215 |
| Permit Number |
06110215 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-13 14:12:05 | *** DENIED *** | | | 1) THE MECHANICAL PLANS NEED THE JOB ADDRESS ON THEM. | | | | | | 2) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. PER FBC 104.2.1 . | | | | | | 3) PLEASE SHOW THE SIZE OF THE SUPPLY AIR DUCTS TO THE | | | DINING ROOM AND THE KITCHEN. | | | | | | 4) WATER CLOSET IN MASTER BATHROOM REQUIRES AN EXHAUST | | | FAN, PER 2004 FBC/R M1506.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|