Plan Review Notes
Plan Review Notes For Permit 06110215
Permit Number 06110215
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-13 10:12:00****** UNSAT ******
  
 1) NOTE: PLEASE SEE FAC 61G15-23.001, AS THE SEAL FOR
 THE ENGINEER OF RECORD IS NO LONGER VALID AS OF JANUARY
 1ST, 2006.
  
 2) NOTE: PLEASE SEE SHEETS WHICH DO NOT CONTAIN TITLE
 BLOCKS FOR SHEETS WHICH DO CONTAIN SEALS FROM THE
 ENGINEER. PLEASE ALSO SEE SHEETS WHICH ARE SEALED,
 HOWEVER NOT SIGNED BY THE ENGINEER. PLEASE SEE COMMENT
 #1, AS ALL SHEETS WILL BE REQUIRED TO BE RE-DONE. FAC
 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE SEE FS 481.229(C)1 WITH EXCEPTIONS OF
 WHO CAN DRAW RESIDENTIAL AND WHO SIGN AND SEAL PLANS
 DONE BY ANOTHER DESIGNER.
 PLEASE ALSO SEE FS 471.025/481.221
  
 4) NOTE: PLEASE KNOW THAT NO HAND DRAWN ITEMS MAY BE
 DONE TO PLANS WHICH ARE SIGNED AND SEALED BY ANY DESIGN
 PROFESSIONAL.
 PLEASE SEE BOTH FS 481, AND471.
  
 5) NOTE: PLEASE SEE 210.70 FOR MISSING EGRESS LIGHTING
 REQUIRED IN SEVERAL LOCATIONS. EGRESS IN AND OUT OF
 DWELLING, INTO HABITABLE ROOMS ETC. PLEASE SEE LIGHT
 FIXTURES OF SOME SORT WILL BE REQUIRED FOR FINAL.
 PLEASE ALSO SEE SOME ROOMS ONLY CONTAIN WHAT SEEMS TO
 BE A FAN.
 PLEASE SEE LS 101 7.8
  
 6) NOTE: PLEASE SEE MISSING AIC RATINGS FOR SERVICE
 EQUIPMENT. 110.9, 240.12, PLEASE SUBMIT.
  
 7) NOTE: PLEASE SEE MISSING REQUIRED FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM PER 250.50.
  
 8) NOTE: PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S)
 SUBMITTED.
 ALL CIRCUITING SHALL BE SPECIFIC TO ROOMS ETC. EXAMPLE:
 MASTER BEDRM LTS, KITCHEN LTS , BATH RECEPTS ETC.
 240.4,408.4,310.16
 FBC 106.1.2 ADMIN SECT.
  
 9) NOTE: PLEASE SEE MISSING DEDICATED BATH(S)
 CIRCUIT(S) PER 210.52D, 210.11C3.
 MUST BE 20A AND #12.
 PLEASE ALSO SEE A ROOM WHICH MENTIONS BEING
 STORAGE/UTILITY, HOWEVER IF CONTAINING BOTH THE ITEMS
 SHOWN AS A LAVATORY AND WATER CLOSET, GFI RECEPT AS
 REQUIRED PER ABOVE SHALL BE INSTALLED.
  
 10) NOTE: PLEASE SEE 424.3B FOR MIN OCP FOR THE AHU.
 PLEASE SEE A MIN OF 125% BASED ON THE 10KW HEAT.
  
 11) NOTE: PLEASE SEE MISSING COUNTER SPACE RECEPTS PER
 210.52C1
  
 12) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE SHALL BE GFI/ GFI PROTECTED.
  
 13) NOTE: PLEASE SEE MISSING GFI DESIGNATION ON SEVERAL
 RECEPTACLE OUTLETS PER THE FOLLOWING.
 210.8A2, 210.8A1, 210.8A3 ETC.
  
 14) NOTE: PLEASE SEE NO LOAD INDICATED FOR THE
 DEDICATED GARAGE DOOR OPENER?
 CAN NOT REVIEW AT THIS TIME FOR COMPLIANCE FOR SIZING
 OF OCP AND AWG.
 310.16, 240.4, 430?
  
 15) NOTE: PLEASE SEE 210.11C1 AND 220.16 FOR MISSING
 REQUIRED LOAD FOR SMALL APPLIANCE CIRCUITS.
  
 16) NOTE: PLEASE SEE 210.11C2 AND 220.16 FOR MISSING
 REQUIRED LOAD FOR LAUNDRY/WASHER CIRCUIT.
  
 17) NOTE: PLEASE SEE SOME AREAS WHICH DO NOT INDICATE
 3-WAY SWITCHING WHERE SWITCH LEGS ON PLANS APPEAR TO
 SHOW THIS??
 PLEASE SEE OTHER AREAS WHERE CONTROL FOR EGRESS
 LIGHTING MAY BE REQUIRED ALSO.
 210.70
  
 18) NOTE: PLEASE SEE NO SYMBOL LEGEND OR SCHEDULE IS
 SHOWN OR WAS SUBMITTED ON SAID PLANS.
 PLEASE SUBMIT AND CORRELATE.
 FBC 106.1.2 ADMIN SECT.
  
 19) NOTE: PLEASE COMPLETE, SUBMIT AND SHOW LOAD
 CALCULATIONS BASED ON SERVICE AND DWELLING AS SHOWN.
 PLEASE SEE 220.31.
 UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS TIME BASED
 ON THE FACT THAT NO CALCULATIONS WERE SUBMITTED.
  
 20) NOTE: PLEASE INDICATE AND SHOWN SERVICE AND PANEL
 LOCATIONS ON PLANS.
 PLEASE SEE 230.70, 240.24 ETC. AS THE LOCATION WAS NOT
 SUBMITTED OR SHOWN.
  
 21) NOTE: PLEASE SEE MISSING SMOKE ALARMS AS REQUIRED
 PER NFPA-72 11.5.1.1, 11.8.3
  
 22) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON THE PLANS AS SUBMITTED.
 2002 NFPA-70 (NEC), 2002 NFPA-72
  
 ** PLEASE KNOW BASED ON THE COMMENTS ON THIS REVIEW,
 THERE MAY BE FURTHER COMMENTS DUE TO POSSIBLE CHANGES
 IN PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  