| 2006-11-13 10:12:00 | ****** UNSAT ****** |
| | |
| | 1) NOTE: PLEASE SEE FAC 61G15-23.001, AS THE SEAL FOR |
| | THE ENGINEER OF RECORD IS NO LONGER VALID AS OF JANUARY |
| | 1ST, 2006. |
| | |
| | 2) NOTE: PLEASE SEE SHEETS WHICH DO NOT CONTAIN TITLE |
| | BLOCKS FOR SHEETS WHICH DO CONTAIN SEALS FROM THE |
| | ENGINEER. PLEASE ALSO SEE SHEETS WHICH ARE SEALED, |
| | HOWEVER NOT SIGNED BY THE ENGINEER. PLEASE SEE COMMENT |
| | #1, AS ALL SHEETS WILL BE REQUIRED TO BE RE-DONE. FAC |
| | 61G15-23.002, FS 471.025 |
| | |
| | 3) NOTE: PLEASE SEE FS 481.229(C)1 WITH EXCEPTIONS OF |
| | WHO CAN DRAW RESIDENTIAL AND WHO SIGN AND SEAL PLANS |
| | DONE BY ANOTHER DESIGNER. |
| | PLEASE ALSO SEE FS 471.025/481.221 |
| | |
| | 4) NOTE: PLEASE KNOW THAT NO HAND DRAWN ITEMS MAY BE |
| | DONE TO PLANS WHICH ARE SIGNED AND SEALED BY ANY DESIGN |
| | PROFESSIONAL. |
| | PLEASE SEE BOTH FS 481, AND471. |
| | |
| | 5) NOTE: PLEASE SEE 210.70 FOR MISSING EGRESS LIGHTING |
| | REQUIRED IN SEVERAL LOCATIONS. EGRESS IN AND OUT OF |
| | DWELLING, INTO HABITABLE ROOMS ETC. PLEASE SEE LIGHT |
| | FIXTURES OF SOME SORT WILL BE REQUIRED FOR FINAL. |
| | PLEASE ALSO SEE SOME ROOMS ONLY CONTAIN WHAT SEEMS TO |
| | BE A FAN. |
| | PLEASE SEE LS 101 7.8 |
| | |
| | 6) NOTE: PLEASE SEE MISSING AIC RATINGS FOR SERVICE |
| | EQUIPMENT. 110.9, 240.12, PLEASE SUBMIT. |
| | |
| | 7) NOTE: PLEASE SEE MISSING REQUIRED FOOTER STEEL AS |
| | PART OF THE GROUNDING ELECTRODE SYSTEM PER 250.50. |
| | |
| | 8) NOTE: PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS |
| | ON PLANS AND CORRELATE WITH THE PANEL SCHEDULE(S) |
| | SUBMITTED. |
| | ALL CIRCUITING SHALL BE SPECIFIC TO ROOMS ETC. EXAMPLE: |
| | MASTER BEDRM LTS, KITCHEN LTS , BATH RECEPTS ETC. |
| | 240.4,408.4,310.16 |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 9) NOTE: PLEASE SEE MISSING DEDICATED BATH(S) |
| | CIRCUIT(S) PER 210.52D, 210.11C3. |
| | MUST BE 20A AND #12. |
| | PLEASE ALSO SEE A ROOM WHICH MENTIONS BEING |
| | STORAGE/UTILITY, HOWEVER IF CONTAINING BOTH THE ITEMS |
| | SHOWN AS A LAVATORY AND WATER CLOSET, GFI RECEPT AS |
| | REQUIRED PER ABOVE SHALL BE INSTALLED. |
| | |
| | 10) NOTE: PLEASE SEE 424.3B FOR MIN OCP FOR THE AHU. |
| | PLEASE SEE A MIN OF 125% BASED ON THE 10KW HEAT. |
| | |
| | 11) NOTE: PLEASE SEE MISSING COUNTER SPACE RECEPTS PER |
| | 210.52C1 |
| | |
| | 12) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING |
| | KITCHEN COUNTER SPACE SHALL BE GFI/ GFI PROTECTED. |
| | |
| | 13) NOTE: PLEASE SEE MISSING GFI DESIGNATION ON SEVERAL |
| | RECEPTACLE OUTLETS PER THE FOLLOWING. |
| | 210.8A2, 210.8A1, 210.8A3 ETC. |
| | |
| | 14) NOTE: PLEASE SEE NO LOAD INDICATED FOR THE |
| | DEDICATED GARAGE DOOR OPENER? |
| | CAN NOT REVIEW AT THIS TIME FOR COMPLIANCE FOR SIZING |
| | OF OCP AND AWG. |
| | 310.16, 240.4, 430? |
| | |
| | 15) NOTE: PLEASE SEE 210.11C1 AND 220.16 FOR MISSING |
| | REQUIRED LOAD FOR SMALL APPLIANCE CIRCUITS. |
| | |
| | 16) NOTE: PLEASE SEE 210.11C2 AND 220.16 FOR MISSING |
| | REQUIRED LOAD FOR LAUNDRY/WASHER CIRCUIT. |
| | |
| | 17) NOTE: PLEASE SEE SOME AREAS WHICH DO NOT INDICATE |
| | 3-WAY SWITCHING WHERE SWITCH LEGS ON PLANS APPEAR TO |
| | SHOW THIS?? |
| | PLEASE SEE OTHER AREAS WHERE CONTROL FOR EGRESS |
| | LIGHTING MAY BE REQUIRED ALSO. |
| | 210.70 |
| | |
| | 18) NOTE: PLEASE SEE NO SYMBOL LEGEND OR SCHEDULE IS |
| | SHOWN OR WAS SUBMITTED ON SAID PLANS. |
| | PLEASE SUBMIT AND CORRELATE. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 19) NOTE: PLEASE COMPLETE, SUBMIT AND SHOW LOAD |
| | CALCULATIONS BASED ON SERVICE AND DWELLING AS SHOWN. |
| | PLEASE SEE 220.31. |
| | UNABLE TO REVIEW FOR CODE COMPLIANCE AT THIS TIME BASED |
| | ON THE FACT THAT NO CALCULATIONS WERE SUBMITTED. |
| | |
| | 20) NOTE: PLEASE INDICATE AND SHOWN SERVICE AND PANEL |
| | LOCATIONS ON PLANS. |
| | PLEASE SEE 230.70, 240.24 ETC. AS THE LOCATION WAS NOT |
| | SUBMITTED OR SHOWN. |
| | |
| | 21) NOTE: PLEASE SEE MISSING SMOKE ALARMS AS REQUIRED |
| | PER NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 22) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE |
| | REFLECTED ON THE PLANS AS SUBMITTED. |
| | 2002 NFPA-70 (NEC), 2002 NFPA-72 |
| | |
| | ** PLEASE KNOW BASED ON THE COMMENTS ON THIS REVIEW, |
| | THERE MAY BE FURTHER COMMENTS DUE TO POSSIBLE CHANGES |
| | IN PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |