| 2006-11-28 09:09:29 | DENIED |
| | |
| | |
| | 1.SHOW SIZE AND LOCATION OF ATTIC ACCESS COMPLYING |
| | WITH R-806. |
| | |
| | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.BASED ON ICC BUILDING VALUATION DATA THE PERMIT |
| | VALUE HAS BEEN REVISED TO $240,797.00.ADDITIONAL |
| | PERMIT FEES ARE DUE. |
| | |
| | 4.SAFTEY GLAZING REQUIRED FOR WINDOWS AT TUB |
| | LOCATIONS.R-308.4 |
| | |
| | 5.PRODUCT APPROVALS REQUIRED FOR LINTELS, STRAPS AND |
| | TIE-DOWNS AND MULLIONS.OVERHEAD DOOR ONLY STATE |
| | PRODUCT APPROVAL SUBMITTED. |
| | |
| | 6.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY |
| | ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL |
| | ATTACHED. |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF |
| | THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN |
| | APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC |
| | FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 7.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3. |
| | |
| | |
| | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS FOR REVIEW PER |
| | 2004 FBC R-802.10.1TRUSS DRAWING REQUIRED TO BE |
| | APPROVED PRIOR TO INSTALLATION. |
| | |
| | 9.SHOW PRESSURES ON DOOR AND WINDOW OPENINGS. |
| | |
| | 10.R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS |
| | TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| | GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM |
| | OF 6 INCHESWITHIN THE FIRST 10 FEET. |
| | |
| | 11.SUBMIT A WINDOW, LINTEL AND SHUTTER SCHEDULE. |
| | |
| | 12.SHOW DIMENTIONS ON ELEVATIONS. |
| | |
| | 13.SMOKE DETECTORS FOR BEDROOMS SHALL COMPLY WITHR |
| | 313.1 |
| | |
| | 14.ENGINEERS SEAL IS EXPIRED AND SHOULD READ |
| | "LICENSED"61G1-16.001 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE |
| | COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | |
| | |