Plan Review Notes
Plan Review Notes For Permit 06110189
Permit Number 06110189
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-12 10:28:55****APPROVED W/REMINDERS*****
  
  
  
 1. THE SAID OPERATION SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID BUILDING OR VICINITY
 THEREOF.
  
 2.PROVIDE ONE OR MORE DEDICATED FIRE EXTINGUISHERS
 THAT HAVE A MINIMUM CAPABILITY OF 40:BC LOCATED WITHIN
 100 FEET OF THE WORK AREA.
  
 3.CUTTING AND/OR WELDING OPERATIONS USED IN THE SCOPE
 OF WORK SHALL COMPLY WITH NFPA 51B.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW