| 2009-02-13 14:13:04 | ** DENIED REVIEW ** |
| | |
| | REVISIONS |
| | |
| | |
| | 1) NOTE: PLEASE GO THROUGH AND COORDINATE ALL CHANGES |
| | AND REVISIONS. |
| | |
| | FOR EXAMPLE: SHEET E4.1 NOW HAS EQUIPMENT AND MAINS IN |
| | THE MAIN ELECTRICAL ROOM REMOVED HOWEVER THE POWER |
| | PLANS STILL SHOW THIS EQUIPMENT AND OTHER EQUIPMENT. IF |
| | THIS EQUIPMENT AND OTHERS ARE NO LONGER LOCATED IN THIS |
| | ROOM PLEASE SUBMIT PLANS FOR NEW LOCATION(S). |
| | 110.26,240.24, 230.71,230.71 ETC |
| | |
| | FOR EXAMPLE: PLEASE SEE RISER AS MAIN IS STILL NOTED AS |
| | MAIN 2 OF 2. THIS WOULD BE MAIN ONE IF THIS IS STILL A |
| | SEPARATE BUILDING AS STATED IN PREVIOUS REVIEWS AND |
| | REVISIONS. |
| | 230.2E |
| | |
| | FOR EXAMPLE: RISER NOW SHOWS A REVISION WITH THE |
| | ADDITION OF A NEW PANEL *L2AB* HOWEVER THE RISER SHOWS |
| | THIS PANEL BEING FED FROM *DP2A*. IF YOU GO TO THE |
| | PANEL *DP2A* YOU WILL NOT FIND ANY SUCH PANEL. |
| | |
| | ** PLEASE COORDINATE ALL OF THE ABOVE. |
| | 215.5,230,240,220 ETC |
| | |
| | 2) NOTE: PLEASE REMOVE DESIGNATION OF IT ROOM FROM ALL |
| | SHEETS AS THIS DOES NOT MEET 645.4. PLEASE ALSO INCLUDE |
| | NOTE WHICH WILL STATE: |
| | THIS IS NOT AN IT ROOM WIRING METHODS PER NEC 645 NOT |
| | PERMITTED. (OR WORDS TO THAT AFFECT). |
| | |
| | |
| | |
| | ** NOT ALL NOTES PROVIDED ON SHEETS SUBMITTED DENOTING |
| | CHANGES MATCH WITH PLANS. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |