| Plan Review Notes For Permit 06110152 |
| Permit Number |
06110152 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2008-07-17 08:55:45 | ** DENIEDREVISIONS ** | | | | | | | | | 1) NOTE:PLEASE PROVIDE WHERE THE MAIN ONE OF ONE | | | WENT. PLEASE KNOW ALL MAINS SHALL BE GROUPED PER | | | 230.72. | | | THE EXISTING ELECTRICAL ROOM SERVICE EQUIPMENT IS NO | | | LONGER ON PLANS YET THIS BUILDING IS PART OF THE NEW | | | BUILDING. | | | IT IS UNCLEAR WHAT THE INTENT IS AND WHERE ELECTRICAL | | | SERVICE EQUIPMENT IS. | | | 230.70,230.2,230.71,230.72, 230.76, 230.79 | | | | | | ** CALLED WAS PLACED TO ENGINEER, AS OF REVIEW NOTES | | | WAITING FOR RETURN CALL. | | | | | | 2) NOTE: REVISED EENRGY CALCULATIONS NOT REVIEWED. NEED | | | TO SUBMI WITH ANY OTHER CHANGES DURING PROJECT BEFORE | | | FINAL. | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|