| 2007-09-08 05:59:32 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | |
| | 8. SHT P3-1.1 RPZV BACKFLOWS ARE REQUIRED ON EACH WATER |
| | SUPPLY LINE INTO THE BUILDING. SECTION 608.13.2. SHOW |
| | ON THE PLANS. |
| | ****RESPONSE NOTED, BUT THE CIVIL SHEET WERE NOT |
| | SUBMITTED WITH THESE PLANS. PLEASE INDICATE ON THE |
| | PLANS LOCATION OF REQUIRED BACKFLOWS. |
| | ******RESPONSE NOTED, BUT THE RPZV BACKFLOWS ARE NOT |
| | INDICATED ON THE CIVIL PLANS AS REQUIRED FOR EACH |
| | BUILDING. |
| | |
| | 9. SHT P5.1 VENT SHOWN UPSTREAM OF THE SANITARY STACK |
| | AND PRIOR TO THE FIRST WATER CLOSETS IS NOT SHOWN ON |
| | THE FLOOR PLAN. (TOILET ROOMS 221 & 223). PLEASE |
| | CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND THE |
| | RISER DIAGRAM. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. ROOMS |
| | 221 & 223 ARE ONLY SHOWN ON SHT P2.2 AND NO CHANGE TO |
| | FLOOR PLAN SHOWN. |
| | ******RESPONSE NOTED, BUT THE VENT IS STILL NOT SHOWN |
| | ON THE FLOOR PLAN TO REFLECT THE RISER DIAGRAM. |
| | |
| | 10. OK |
| | 11. OK |
| | |
| | 12. SHT P6.1 DOMESTIC WATER ISOMETRIC. SHOW THE |
| | REQUIRED RPZV BACKFLOWS ON THE WATER SERVICES, AND SHOW |
| | AN RPZV ON THE SUPPLY LINE FOR THE 2" MAKE UP WATER TO |
| | THE ROOF. SECTION 608.13.2. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. - NOT |
| | SHOWN ON ISOMETRIC AS INDICATED. |
| | ******RESPONSE NOTED, BUT THE RPZV BACKFLOWS ARE NOT |
| | SHOWN ON THE WATER SERVICE TO EACH BUILDING. |
| | |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. ALL SHEETS FOR PME SHALL BE SIGNED, SEALED & DATED |
| | ON THE DATE THE SEAL & SIGNATURE ARE AFFIXED TO SAID |
| | PLANS. SECTION 106.1. |
| | ******RESPONSE NOTED, BUT ONE ELECTRICAL SHEET DOES NOT |
| | HAVE A SIGNATURE ON ONE SET. |
| | |
| | 2B. OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |