| Plan Review Notes For Permit 06110152 |
| Permit Number |
06110152 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-09-14 18:58:24 | *****DENIED***** | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | . | | | 09. ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA | | | 80.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE SHALL | | | REQUIRED ON ALL EXIT DOORS THAT SERVE AND OCCUPANT LOAD | | | OF 100 OR MORE PERSONS.ADD COMMENT TO AN APPROPIATE | | | PLAN SHEET | | | | | | | | | 14.INTERIOR WALL AND CEILING FINISH CLASSIFICATION | | | SHALL BE CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS | | | HAVING AN OCCUPANT LOAD OF MORE THAN 300 AND SHALL BE | | | CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING | | | OCCUPANTS OF 300 OR FEWER.SPECIFY | | | | | | 15.ELEVATORS TO COMPLY WITH ASME A17.1; WARNING SIGNS | | | WILL BE REQUIRED IN ELEVATOR LOBBY.THE ELEVATORS (OR | | | AT LEAST ONE ELEVATOR) SHOULD BE ACCESSIBLE FOR AN | | | EMERGENCY MEDICAL STRETCHER OR GOURNEY.ADD COMMENT TO | | | AN APPROPIATE PLAN SHEET | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT | | | WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|