| 2007-09-04 14:42:58 | BUILDING PLAN REVIEW |
| | PERMIT: 06110152 |
| | ADD: 807 N. FLAGLER DR. |
| | CONT: ANDERSON-MOORE |
| | TEL: (561)662-1819 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE |
| | CODE |
| | |
| | 3RDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A PERMIT WILL BE |
| | ISSUED. NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE |
| | NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE |
| | IS NULL & VOID. |
| | |
| | 3) BUILDING PROVISO: 109.3.10 IMPACT OF CONSTRUCTION. |
| | |
| | 4) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION. |
| | |
| | 5) COMPLIED, SPECIAL INSPECTOR AGREEMENT, THANK YOU. |
| | |
| | 6) COMPLIED, 3-SOILS REPORTS. |
| | |
| | 7)SECOND REQUEST,FLOOD ELEVATION CERTIFICATE WILL |
| | BE REQUIRED BEFORE THE ISSUANCE OF THE CERTIFICATE OF |
| | OCCUPANCY. THE ISSUE WITH THE FLOOD ELEVATION |
| | CERTIFICATE IS IT WILL BE REQUIRED FOR THE "WHOLE |
| | BUILDING" BEING THAT THE PROPOSED, THE ADDITION IS OVER |
| | 50% WORTH OF THE EXISTING BUILDING "SUBSTANTIAL |
| | IMPROVEMENTS" NEED TO BE MET UNDER W. P. B. CODE OF |
| | ORDNANCES |
| | CITY CODEARTICLE XVII FLOOD PREVENTION & CONTROL SEE |
| | ATTACHED DOCUMENT FOR COMPLIANCE. NOTE UNDER SECTION |
| | 94-546(B)(2) NONRESIDENTIAL CONSTRUCTION COMPLIANCE |
| | THROUGH |
| | FLOOD PROOFING.SEE THE EXISTING MARGARET TIGHE |
| | MACHLIN THEATER FINISH FLOOR IS 5.13'N A VD 88. SEE |
| | CIVIL PLAN C-1. |
| | CITY CODE OF ORDNANCES |
| | 94-546 (B)(2)NONRESIDENTIAL CONSTRUCTION.ALL NEW |
| | CONSTRUCTION |
| | OR SUBSTANTIAL IMPROVEMENT OF ANY COMMERCIAL, |
| | INDUSTRIAL OR OTHER NONRESIDENTIAL STRUCTURE SHALL |
| | EITHER HAVE THE LOWEST FLOOR, BASE FLOOD ELEVATION OR, |
| | TOGETHER WITH ATTENDANT UTILITY AND SANITARY |
| | FACILITIES, BE FLOOD PROOFED SO THAT BELOW SIX INCHES |
| | ABOVE THE FLOOD BASE LEVEL THE STRUCTURE IS WATERTIGHT, |
| | WITH WALLS SUBSTANTIALLY IMPERMEABLE TO THE PASSAGE OF |
| | WATER AND WITH STRUCTURAL COMPONENTS HAVING THE |
| | CAPABILITY OF RESISTING HYDROSTATIC AND HYDRODYNAMIC |
| | LOADS AND EFFECTS OF BUOYANCY. A REGISTERED |
| | PROFESSIONAL ENGINEER OR ARCHITECT SHALL CERTIFY THAT |
| | THE STANDARDS OF THIS SUBSECTION ARE SATISFIED. SUCH |
| | CERTIFICATION SHALL BE PROVIDED TO THE CITY ENGINEER. |
| | |
| | 8-12 COMPLIED. |
| | |
| | 13) COMPLIED, NOTED THE EXISTING DROP OFF ZONE FOR THE |
| | ROSARIAN ACADEMY IS AT THE MARY ALICE FORTIN BUILDING. |
| | |
| | 14-28)COMPLIED. |
| | |
| | 29) 2ND REQUEST,1609.1.4 PROTECTION OF OPENINGS. IN |
| | WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 |
| | FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE REST |
| | OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR |
| | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, |
| | OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN |
| | AS FOLLOWS: 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET |
| | (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE |
| | LARGE MISSILE TEST. 2.GLAZED OPENINGS LOCATED MORE |
| | THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE |
| | PROVISIONS OF THE SMALL MISSILE TEST. |
| | |
| | 30)2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED |
| | TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 31)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS:A) |
| | EXTERIOR GLAZED SWING DOORS, SINGLE AND PAIRS ?OK |
| | |
| | B) EXTERIOR HOLLOW METAL FRAME DOORS, SINGLE AND PAIRS |
| | FL 6224- OK |
| | |
| | C) ROOF HATCHES: THIS WILL BE A PROVISO, IF AT TIME OF |
| | CERTIFICATE OF COMPLETION THE MANUFACTURER HAS NOT |
| | RECEIVED EITHER STATE APPROVAL OR A MIAMI-DADE NOAA |
| | LOCAL PRODUCT APPROVAL WILL NEED TO BE ACHIEVED BEFORE |
| | C/O. |
| | |
| | D) FIXED WINDOWS-OK |
| | |
| | E) OPERABLE WINDOWS-OK |
| | |
| | F) SPANDREL GLASS-OK |
| | |
| | G) MULLIONS VERTICAL AND HORIZONTAL PART OF NOA. |
| | |
| | H) WALL LOUVERS- OK |
| | |
| | I) STRUCTURAL ANCHORS TRUSS ANCHORS-NO APPROVALS |
| | SUBMITTED |
| | |
| | J) ROOFING ASSEMBLIES, ROOFING INSULATION, FLAT ROOFS |
| | MODIFIED |
| | ROOF TILE AND ASSEMBLIES. NOA 06-0606.06 ENTEGRA |
| | TILE PLEASE HIGHLIGHT THE METHOD OF ATTACHMENT FOUND ON |
| | PAGES 4 & 5. |
| | |
| | MODIFIED, THIS INFORMATION WILL BE NEEDED FOR A REVIEW |
| | OF ROOFING PRODUCTS: |
| | THIS FLAT ROOF (MODIFIED) IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | _XX__NOTE ROOF IS OVER 4 FEET FROM GRADE, THE ROOF |
| | TABLE 1609.6.2.1(4) SEE HEIGHT |
| | ADJUSTMENT FACTOR 1.12. |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _XX__ |
| | CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO BE |
| | USED. |
| | PAGES 9-26, PLEASE HIGHLIGHT WHICH SYSTEM WILL |
| | BE INSTALLED. |
| | _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE |
| | 2& 3__ . |
| | _XX__ THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THATREQUIRED, AS |
| | DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER |
| | SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE |
| | SUBMITTED. |
| | ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | 32) 2ND REQUEST, W P B ADMINISTRATIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| | BY DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 33-35) COMPLIED. |
| | |
| | 36) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |