| 2007-06-13 14:53:14 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT A0.0.1 INDICATES ASSEMBLY OCCUPANCY FOR THE 1ST |
| | & 2ND FLOORS. PER SECTION 403.1.1, POTTY PARITY, |
| | RESTROOMS WHICH ARE OPEN TO THE PUBLIC, MUST HAVE A |
| | RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE |
| | COMBINED TOTAL OF WATER CLOSETS & URINALS PROVIDED FOR |
| | MEN. POTTY PARITY DOES NOT SEEM TO BE COMPLIED WITH. |
| | PLEASE SHOW COMPLIANCE WITH SECTION 403.1.1. |
| | ****RESPONSE NOTED, BUT ACCORDING TO TABLE 403.1, FIRST |
| | FLOOR ASSEMBLY OF 271 FOR WOMEN @ 1/65 COMES OUT TO |
| | 4.169 AND ALL FRACTIONS SHALL BE ROUNDED UP. SO THE |
| | TOTAL WOMENS W/C'S REQUIRED IS 18, NOT 17 AS SHOWN. |
| | |
| | 2. SHT A2.4.1 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE OF EACH |
| | AREA TO BE DRAINED, AND 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS AS WELL AS ANY ROOF AREA FROM ABOVE |
| | THAT DRAINS ON TO THE LOWER ROOFS IN THE CALCULATIONS. |
| | SECTIONS 106.3.5.1.3(7)(13) & TABLES 1106.2, 1106.3 & |
| | 1106.6. INDICATE THE SIZE OF THE GUTTERS AND SHOW SLOPE |
| | WITH THE HIGH POINTS OF THE GUTTER INDICATED. |
| | ****RESPONSE NOTED, BUT NO CALCULATIONS WERE FOUND. THE |
| | 1/2 AREA OF ALL VERTICAL WALLS WAS NOT INDICATED AND NO |
| | SQUARE FOOTAGE IS INDICATED FOR THE ROOF DRAINS SHOWN |
| | ON SHT P2.3.1 & ASSOCIATED DRAINS ON THE STORM RISER |
| | DIAGRAM SHT P5.2. UPON FURTHER REVIEW, NO CALCULATIONS |
| | WERE FOUND FOR THE EXISTING ROOF DRAINS THAT HAVE THE |
| | ADDED VERTICAL CONTRIBUTION FROM THE NEW ADDIITION |
| | PLEASE INDICATE TOTAL SQUARE FOOTAGE BEING DRAINED BY |
| | THE DRAINS ADJACENT TO THE NEW ADDITION. SHOW EXISTING |
| | SF AND 1/2 AREA OF NEW VERTICAL WALL ADDED TO SF. |
| | INDICATE THE SIZE OF THE EXISTING ROOF DRAINS AND THE |
| | SIZE OF THE EXISTING ROOF LEADERS. |
| | |
| | 3. SHTS A4.1.1 & A4.1.2 SHOW THE CLEAR FLOOR SPACE FOR |
| | THE URINAL, ACCESSIBLE SHOWERS AND DRINKING FOUNTAINS |
| | PER SECTIONS 11-4.18..3, 11-4.21.2, & 11-4.15.5. ****NO |
| | RESPONSE, NOT ADDRESSED. |
| | |
| | 4. SHT A7.1.1 FINISH SCHEDULE. BOY'S RESTROOM 107 & |
| | GIRL'S RESTROOM 109 INDICATE PAINTED GWB FOR THE WALL |
| | FINISH. SECTION 1210.2 REQUIRES A "SMOOTH, HARD, |
| | NONABSORBENT" SURFACE. PAINTED GWB IS NOT CONSIDERED A |
| | "HARD" SURFACE. PLEASE INDICATE HOW THIS REQUIREMENT |
| | WILL BE COMPLIED WITH. ALSO SEE BOY'S RESTROOM 302 AND |
| | GIRL'S RESTROOM 304. NO FINISH IS INDICATED. PLEASE |
| | INDICATE WALL FINISH TO COMPLY WITH SECTION 1210.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 5. SHT A8.1.3 SHOW THE FOLLOWING REQUIREMENTS: |
| | A. 11-4.16.6 DISPENSERS (FIG 29(B) |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.21.2 SIZE & CLEARANCES |
| | E. 11-4.21.3 SEAT |
| | F. 11-4.21.4 GRAB BARS (FIG 11-37) |
| | G. 11-4.21.5 CONTROLS |
| | H. 11-4.21.6 SHOWER UNIT |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 6. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| | FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS INCLUDING ALSO SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING AND |
| | STOOPING. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 7. SHT P0.1 WATER HEATER DETAIL. SUBMIT CALCULATION FOR |
| | THE EXPANSION TANK FOR THE 1230 GAL W/H. SUBMIT THE |
| | MANUF. SPECIFICATION SHEETS AND INDICATE THE MODEL |
| | NUMBER SHOWING TANK SIZE. SECTION 607.3.2. ****RESPONSE |
| | NOTED, BUT THE CALCULATIONS WERE NOT SUBMITTED. (SEE |
| | EXAMPLES OF TWO DIFFERENT MANUF. CALCULATIONS FOR |
| | EXPANSION TANKS). |
| | |
| | 8. SHT P3-1.1 RPZV BACKFLOWS ARE REQUIRED ON EACH WATER |
| | SUPPLY LINE INTO THE BUILDING. SECTION 608.13.2. SHOW |
| | ON THE PLANS. |
| | ****RESPONSE NOTED, BUT THE CIVIL SHEET WERE NOT |
| | SUBMITTED WITH THESE PLANS. PLEASE INDICATE ON THE |
| | PLANS LOCATION OF REQUIRED BACKFLOWS. |
| | |
| | 9. SHT P5.1 VENT SHOWN UPSTREAM OF THE SANITARY STACK |
| | AND PRIOR TO THE FIRST WATER CLOSETS IS NOT SHOWN ON |
| | THE FLOOR PLAN. (TOILET ROOMS 221 & 223). PLEASE |
| | CORRELATE INFORMATION BETWEEN THE FLOOR PLAN AND THE |
| | RISER DIAGRAM. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. ROOMS |
| | 221 & 223 ARE ONLY SHOWN ON SHT P2.2 AND NO CHANGE TO |
| | FLOOR PLAN SHOWN. |
| | |
| | 10. SHT P5.1 SANITARY RISER DIAGRAM. SHOW THE DFU'S AS |
| | THEY ACCUMULATE IN THE SYSTEM TO VERIFY THE PIPE SIZES. |
| | SECTION 106.1.1 AND TABLES 709.1, 710.1(1) & 710.1(2). |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | |
| | 11. OK |
| | |
| | 12. SHT P6.1 DOMESTIC WATER ISOMETRIC. SHOW THE |
| | REQUIRED RPZV BACKFLOWS ON THE WATER SERVICES, AND SHOW |
| | AN RPZV ON THE SUPPLY LINE FOR THE 2" MAKE UP WATER TO |
| | THE ROOF. SECTION 608.13.2. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. - NOT |
| | SHOWN ON ISOMETRIC AS INDICATED. |
| | |
| | 13. SHT P6.1 WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE |
| | CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | 14. SHT P6.1 SHUT OFF VALVES ARE REQUIRED ON BOTH SIDES |
| | OF THE CIRCULATION PUMP FOR THE WATER HEATERS. ALSO |
| | SHOW THE VALVES ON THE WATER HEATER DETAIL SHT P0.1. |
| | SECTION 606.2(3). |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED FOR SHUT OFF |
| | VALVES FOR THE CIRCULATION PUMP. |
| | |
| | 15. SUBMIT A STORM RISER ISOMETRIC RISER DIAGRAM. SHOW |
| | ALL PIPE SIZES, OFFSETS, AND SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. SECTION 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT THE SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM IS NOT SHOWN ON THE RISER. |
| | THE RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN FOR |
| | THE 6" @3535SF. |
| | |
| | 16. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. ALL SHEETS FOR PME SHALL BE SIGNED, SEALED & DATED |
| | ON THE DATE THE SEAL & SIGNATURE ARE AFFIXED TO SAID |
| | PLANS. SECTION 106.1. |
| | |
| | 2B. SEE THE ATTACHED SHEET CONCERNING FS 553.80(2)(B) |
| | AND THE DESIGN PROFESSIONAL. THIS IS GIVEN AS A NOTICE |
| | AT THIS TIME. |
| | |
| | REVIEW BY KEN STEVENS |