Plan Review Notes
Plan Review Notes For Permit 06110152
Permit Number 06110152
Review Stop B
Sequence Number 14
Notes
Date Text
2009-01-27 11:01:13BUILDING PLAN REVIEW
 PERMIT: 06110152
 ADD: 821 N. FLAGLER DR.
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS TO THE ADMINISTRATIVE
 CODE
  
 REVISION REVIEW DATED; 10-06-08
 ACTION:DENIED
  
 1) SHEET A3.2.1 & A5.2.3
  
 A) REVISION# 4 OF THIS SHEET INDICATES THE CHANGE IN
 FILL MATERIAL FROM EARTHENED FILL TO A GEO FOAM TO
 LESSEN THE LATERAL LOAD OR PRESSURES ON THE STAIR
 WALLS. PLEASE PROVIDE DOCUMENTATION THAT THE FOAM WILL
 MEET THE REQUIREMENTS OF SUPPORTING 3000 PSF FOUNDATION
 NOTES SHEET S-5. SHEET A.5.2.3 DETAIL# 1 INDICATES SEE
 STRUCTURAL DRAWINGS. STRUCTURAL SHEET S-2.1 THE WEST
 END OF THE SECOND FLOOR SLAB HAS A CUT SECTION DETAIL
 3/ S-9. WHEN REVIEWING THIS DETAIL THE PLANS STILL
 INDICATE EARTHENED FILL NOT A GEO FOAM, THE NOTE ON
 THIS SHEET INDICATES CONCRETE STAIRS ON GRADE SEE
 TYPICAL DETAIL. S-6 . S-6 AGAIN INDICATES EARTHENED
 FILL WITH WIRE MESH W.F 6X6 /W1.4XW1.4 NOT A STRUCTURAL
 STEEL REINFORCED SLAB.
  
 B CHAPTER 26 DEALS WITH FOAM PLASTICS WHEN USED IN
 CONSTRUCTION OF STRUCTURES AND BUILDINGS. THERE IS NO
 SECTION THAT INDICATES THE USE OF FOAM AS A FILLER
 BENEATH SLABS BUT TO USE FOAM FOR THIS APPLICATION IT
 WILL NEED TO COMPLY WITH 2603.8. SUCH TESTING SHALL BE
 RELATED TO THE ACTUAL END-USE CONFIGURATION AND BE
 PERFORMED ON THE FINISHED MANUFACTURED FOAM PLASTIC
 ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED FOR USE.
  
 2) SHEET A4.1.2
  
 A) CITY STAMPED SET OF PLANS INDICATES A REVISION# 2
 DATED 7/13/07 MUSIC CLASSROOM # 3 WHERE REVISION# 2
 INDICATES A LEVEL FLOOR. IN TTHE REVISION SET,
 REVISION# 3 WHERE THE CITY PLANS SHOW A FLAT FLOOR
 SURFACE THE NEW REVISION 3 SET SHOWS DASHED LINES UNDER
 REVISION# 2, WHAT APPEARS TO BE RAISED PLATFORM? THIS
 WAS AN ISSUE THAT I BELIEVE YOU WERE GOING TO THE STATE
 FOR A WAIVER TO THE STATE FOR VERTICAL ACCESSIBILITY,
 IF YOU RECEIVED THE WAIVER PLEASE PROVIDE A COPY, IF
 NOT REMOVE THE DASHED LINES AS IN THE ISSUED SET OF
 PLANS.VERTICAL ACCESSIBILITY 11-4.1.3(5).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved